Plan Review Notes For Permit 18120471 |
Permit Number |
18120471 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-12-13 18:46:21 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE VULT WINDSPEED FOR CATEGORY II BUILDINGS IN WEST | | PALM BEACH IS 170 MPH. FBC 1604.5 AND 1609.1.1 | | | | 2) THE DEFAULT EXPOSURE CATEGORY IS C. IF YOU WANT TO | | USE EXPOSURE CATEGORY B, SUBMIT AN ANALYSIS REPORT FROM | | A FLORIDA LICENSED ENGINEER. FBC 1609.4.3 | | | | |
|