Plan Review Notes
Plan Review Notes For Permit 18120461
Permit Number 18120461
Review Stop Z
Sequence Number 1
Notes
Date Text
2019-01-04 16:35:02FAILED
  
 1) EXTEND THE PHOTOMETRICS TO THE PROPERTY LINE TO THE
 NORTH AND EAST OF THE GARAGE. THE ZONING CODE STATES,
 "ANY SOURCE OF ILLUMINATION LOCATED WITHIN A COMMERCIAL
 OR INDUSTRIAL PLANNED DEVELOPMENT DISTRICT SHALL NOT
 EXCEED ONE FOOTCANDLE AT OR BEYOND THE BOUNDARIES OF
 SUCH DEVELOPMENT." THE EXTENDED PHOTOMETRICS MUST
 VERIFY THEY DO NOT EXCEED THIS REQUIREMENT.
  
 2) NO SPEC PAGES FOR THE FIXTURES (ESPECIALLY THE
 ROOFTOP FIXTURES) WERE PROVIDED. HOW WILL THE FIXTURES
 KEEP GLARE FROM EXISTING THE SITE?
  