Date |
Text |
2019-12-13 16:34:32 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT #18120436 |
| 12/13/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE AC CALCULATIONS ARE INDICATING MARGATE AS THE |
| LOCATION- PLEASE CORRECT TO INDICATE WEST PALM BEACH. |
| |
| 2) THERE ARE NO DUCTWORK SPECIFICATIONS INDICATED TO |
| VERIFY COMPLIANCE WITH THE EXCEPTIONS LISTED UNDER |
| SECTION 607.5.4 FBC M COPIED BELOW. |
| |
| 607.5.4 CORRIDORS/SMOKE BARRIERS. |
| A LISTED SMOKE DAMPER DESIGNED TO RESIST THE PASSAGE OF |
| SMOKE SHALL BE PROVIDED AT EACH POINT A DUCT OR AIR |
| TRANSFER OPENING PENETRATES A SMOKE BARRIER WALL OR A |
| CORRIDOR ENCLOSURE REQUIRED TO HAVE SMOKE AND DRAFT |
| CONTROL DOORS IN ACCORDANCE WITH THE FLORIDA BUILDING |
| CODE, BUILDING. |
| A CORRIDOR DAMPER SHALL BE PROVIDED WHERE CORRIDOR |
| CEILINGS, CONSTRUCTED AS REQUIRED FOR THE CORRIDOR |
| WALLS AS PERMITTED IN SECTION 708.4, EXCEPTION 3, OF |
| THE FLORIDA BUILDING CODE, BUILDING, ARE PENETRATED. |
| A CEILING RADIATION DAMPER SHALL BE PROVIDED WHERE THE |
| CEILING MEMBRANE OF A FIRE-RESISTANCE-RATED |
| FLOOR/CEILING OR ROOF/CEILING ASSEMBLY, CONSTRUCTED AS |
| PERMITTED IN SECTION 708.4, EXCEPTION 2, OF THE FLORIDA |
| BUILDING CODE, BUILDING, IS PENETRATED. |
| SMOKE DAMPERS AND SMOKE DAMPER ACTUATION METHODS SHALL |
| COMPLY WITH SECTION 607.5.4.1. |
| |
| EXCEPTIONS: |
| 1. SMOKE DAMPERS ARE NOT REQUIRED IN CORRIDOR |
| PENETRATIONS WHERE THE BUILDING IS EQUIPPED THROUGHOUT |
| WITH AN APPROVED SMOKE CONTROL SYSTEM IN ACCORDANCE |
| WITH SECTION 513 AND SMOKE DAMPERS ARE NOT NECESSARY |
| FOR THE OPERATION AND CONTROL OF THE SYSTEM. |
| 2. SMOKE DAMPERS ARE NOT REQUIRED IN SMOKE BARRIER |
| PENETRATIONS WHERE THE OPENINGS IN DUCTS ARE LIMITED TO |
| A SINGLE SMOKE COMPARTMENT AND THE DUCTS ARE |
| CONSTRUCTED OF STEEL. |
| 3. SMOKE DAMPERS ARE NOT REQUIRED IN CORRIDOR |
| PENETRATIONS WHERE THE DUCT IS CONSTRUCTED OF STEEL NOT |
| LESS THAN 0.019 INCH (0.48 MM) IN THICKNESS AND THERE |
| ARE NO OPENINGS SERVING THE CORRIDOR. |
| 4. SMOKE DAMPERS ARE NOT REQUIRED IN SMOKE BARRIERS |
| REQUIRED BY SECTION 407.5 OF THE FLORIDA BUILDING CODE, |
| BUILDING FOR GROUP I-2 CONDITION 2 WHERE THE HVAC |
| SYSTEM IS FULLY DUCTED IN ACCORDANCE WITH SECTION 603 |
| AND WHERE BUILDINGS ARE EQUIPPED THROUGHOUT WITH AN |
| AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION |
| 903.3.1.1 OF THE FLORIDA BUILDING CODE, BUILDING AND |
| EQUIPPED WITH QUICK-RESPONSE SPRINKLERS IN ACCORDANCE |
| WITH SECTION 903.3.2 OF THE FLORIDA BUILDING CODE, |
| BUILDING. |
| |
| 3) M002: PLEASE VERIFY THE RTU'S WILL BE EQUIPPED WITH |
| MOTORIZED O/A DAMPERS- SECTION C403.2.4.3 FBC EC. |
| |
| 4) M002: VERIFY COMPLIANCE WITH SECTION C403.4.6 HOT |
| GAS BYPASS LIMITATION. |
| COOLING SYSTEMS SHALL NOT USE HOT GAS BYPASS OR OTHER |
| EVAPORATOR PRESSURE CONTROL SYSTEMS UNLESS THE SYSTEM |
| IS DESIGNED WITH MULTIPLE STEPS OF UNLOADING OR |
| CONTINUOUS CAPACITY MODULATION. THE CAPACITY OF THE HOT |
| GAS BYPASS SHALL BE LIMITED AS INDICATED IN TABLE |
| C403.4.6, AS LIMITED BY SECTION C403.3.1. |
| |
| TABLE C403.4.6 |
| MAXIMUM HOT GAS BYPASS CAPACITY |
| RATED CAPACITY MAXIMUM HOT GAS BYPASS CAPACITY (% OF |
| TOTAL CAPACITY) |
| ? 240,000 BTU/H 50 |
| > 240,000 BTU/H 25 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |