Plan Review Notes For Permit 18120436 |
Permit Number |
18120436 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-09-16 18:11:35 | PLUMBING 2ND REVIEW**DENIED** SOME OF THE UPLOADS | | APPEAR TO BE DUPLICATE. | | ALL OF THESE COMMENTS ARE 2ND REQUEST: | | #1- ANSWERED | | #2-PROVIDE ALL 3 GAS WATER HEATER INSTALLATION MANUALS. | | FBC 107.2.1 | | #3-PROVIDE A COMPLETE ISOMETRIC OF THE STORM DRAIN | | SYSTEM. FBC 107.3.5 | | #4-ANSWERED | | #5-SHT.301 DOMESTIC WATER RISER DOES NOT THE REQUIRED | | SHUT OFF VALVES ON EACH TOP-DOWN FEED. EACH VALVE WILL | | REQUIRE A ACCESS PANEL TO THE SHUT OFF VALVE. FBC-PLB | | 606 #5, 606.3 | | #6- WHAT IS THE PURPOSE OF THE DOMESTIC WATER LINE IN | | THE MECH ROOM? FBC 107.2.1. PLEASE CLARIFY AS BACKFLOW | | PROTECTION BY RPZ DEVICE MAY BE REQUIRED. FBC 107.2.1. | | #7- ANSWERED | | #8-ANSWERED | | #9-ANSWERED | | #10-ANSWERED | | #11-ANSWERED | | NEW COMMENT | | #1-SHT. G176 ELEVATION B CALLS OUT FOR THE HANDHELD TO | | BE MOUNTED AT MAX 5? (60?). FBC-ACC 608.6, 309.4 | | REQUIRES THE MAX HEIGHT BE 48?. | | #2-G176 ELEVATION A AND C CALLS OUT FOR THE PAN PITCH | | TO BE MAX 2%. 2% IS THE MIN REQUIRED FOR BOTH PRE-PITCH | | AND TILE FINAL PITCH. FBC-PLB 417.5.2 | | | | TIM HUNT | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | [email protected] | | 561-248-2703 | | |
|