Plan Review Notes
Plan Review Notes For Permit 18120436
Permit Number 18120436
Review Stop P
Sequence Number 2
Notes
Date Text
2019-09-16 18:11:35PLUMBING 2ND REVIEW**DENIED** SOME OF THE UPLOADS
 APPEAR TO BE DUPLICATE.
 ALL OF THESE COMMENTS ARE 2ND REQUEST:
 #1- ANSWERED
 #2-PROVIDE ALL 3 GAS WATER HEATER INSTALLATION MANUALS.
 FBC 107.2.1
 #3-PROVIDE A COMPLETE ISOMETRIC OF THE STORM DRAIN
 SYSTEM. FBC 107.3.5
 #4-ANSWERED
 #5-SHT.301 DOMESTIC WATER RISER DOES NOT THE REQUIRED
 SHUT OFF VALVES ON EACH TOP-DOWN FEED. EACH VALVE WILL
 REQUIRE A ACCESS PANEL TO THE SHUT OFF VALVE. FBC-PLB
 606 #5, 606.3
 #6- WHAT IS THE PURPOSE OF THE DOMESTIC WATER LINE IN
 THE MECH ROOM? FBC 107.2.1. PLEASE CLARIFY AS BACKFLOW
 PROTECTION BY RPZ DEVICE MAY BE REQUIRED. FBC 107.2.1.
 #7- ANSWERED
 #8-ANSWERED
 #9-ANSWERED
 #10-ANSWERED
 #11-ANSWERED
 NEW COMMENT
 #1-SHT. G176 ELEVATION B CALLS OUT FOR THE HANDHELD TO
 BE MOUNTED AT MAX 5? (60?). FBC-ACC 608.6, 309.4
 REQUIRES THE MAX HEIGHT BE 48?.
 #2-G176 ELEVATION A AND C CALLS OUT FOR THE PAN PITCH
 TO BE MAX 2%. 2% IS THE MIN REQUIRED FOR BOTH PRE-PITCH
 AND TILE FINAL PITCH. FBC-PLB 417.5.2
  
 TIM HUNT
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH (CGA SOLUTIONS)
 [email protected]
 561-248-2703
  