2019-09-26 16:26:33 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18120436 |
| 9/26/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| RESPONSES TO COMMENTS NOT PROVIDED. COMMENTS #1, 2,9, |
| AND 10 FROM THE 1ST REVIEW PRINTED BELOW STILL EXIST- |
| PLEASE COMPLY. |
| |
| 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW SYSTEMS IN COMPLIANCE WITH SECTION C403.2.1 FBC EC. |
| |
| 2) PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE NEW |
| ADDITIONS- SEE SECTIONS C502.1 AND C101.5.1 FBC EC |
| |
| 9) SUBMIT SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE |
| DOWN OF ALL ROOF MOUNTED MECHANICAL EQUIPMENT AND |
| APPLIANCES- SECTION 301.15 FBC M. |
| |
| 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| HEATERS AND THE DRYER- SECTIONS 304.1 AND 504.1 FBC M |
| |
| NEW COMMENTS: |
| |
| 1) SHEETS M102B & A351: THE NEW SCREENING FOR RTU-1 MAY |
| ALSO HAVE TO BE CONSTRUCTED AS A GUARD IF THE UNIT IS |
| WITHIN 10' OF THE ROOF EDGE AND THERE IN NO MINIMUM 42" |
| PARAPET. PLEASE REVIEW SECTION 304.11 FBC M AND IF |
| NECESSARY REVISE THE SCREEN WALL TO MEET COMPLIANCE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |