Plan Review Notes For Permit 18120436 |
Permit Number |
18120436 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-09-16 18:12:09 | GAS 2ND REVIEW**DENIED**NO GAS PLAN PROVIDED 2ND | | REQUEST** | | 1) A COMPLETE GAS ISOMETRIC IS REQUIRED. IT SHALL SHOW | | THE EXISTING BTU LOAD ON THE SYSTEM AND THE ADDITIONAL | | LOAD FOR THE NEW EQUIPMENT, THE CUT SECTIONS AND | | MATERIAL BEING USED ALONG WITH SIZING TABLES BEING | | USED. RESPONSE LETTER CALLS OUT NEW SHT. P304 WAS | | ADDED. NO SHT. P304 CAN BE FOUND. FBC 107.3.5 | | 2) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / | | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY | | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 | | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED | | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS | | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF | | INSPECTION. FGC SEC.305.1 | | 3) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE | | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR | | INSTALLATION. 2017 FGC SEC.410.1 | | NOTE: A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED NEXT REVIEW OF SUBMITTED. | | | | TIM HUNT | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH (CGA SOLUTIONS) | | [email protected] | | 561-248-2703 | | | | |
|