Plan Review Notes
Plan Review Notes For Permit 18120436
Permit Number 18120436
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2019-09-06 14:57:26THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET FP 001 - THERE ARE INDICATIONS OF FIRE
 SPRINKLER WORK. THERE ARE NO INDICATIONS THAT THE WORK
 SHALL BE DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS
 BY CERTIFIED FIRE SPRINKLER CONTRACTORS.
  
 ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
  
  
 2) SHEET FP 101 A - THERE ARE INDICATIONS OF FIRE
 SPRINKLER WORK IN THE SOUTH, ADULT SECTION. THERE ARE
 NO INDICATIONS OF WORK IN THE NORTH, CHILD SECTION.
  
 ALL FIRE SPRINKLER WORK SHALL BE DONE UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
  
  
 3) SHEET E 001 - THERE ARE NO INDICATIONS OF FIRE ALARM
 DEVICES, EQUIPMENT, OR WORK OF THE FIRE ALARM SYSTEM.
  
 ANY WORK ON THE FIRE ALARM, DEMO AND/OR NEW
 INSTALLTIONS SHALL BE DONE UNDER SEPARATE PERMIT AND
 SHOP DRAWING BY CERTIFIED FIRE ALARM CONTRACTORS.
  
  
 4) SHEET A 575 - THERE ARE INDICATIONS OF CARD READERS
 AND CONTROLLED EGRESS WITHIN THE DOOR SCHEDULE.
  
 ALL INSTALL INVOLVING EGRESS SHALL COMPLY WITH NFPA
 101, CHAPTER 7, MEANS OF EGRESS AS APPLICABLE.
  
 ANY WORK OF CARD READERS AND/OR CONTROLLED EGRESS SHALL
 BE DONE UNDER PERMIT AND SEPARATE SHOP DRAWINGS.
  
  
  
 5) SHEET G 100 - THERE ARE NO INDICATIONS UNDER DEMO
 AND/OR OTHER APPLICABLE AREAS REGARDING THE LIFE SAFETY
 SYSTEM BEING MAINTAINED.
  
 COMPLIED - NOTE ADDED
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]