Plan Review Notes
Plan Review Notes For Permit 18120436
Permit Number 18120436
Review Stop B
Sequence Number 2
Notes
Date Text
2019-10-16 10:55:052017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120436
 ADD: 2201 45TH ST.
 CONT: DPR CONSTRUCTION
 TEL: 954-991-6200
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. OCT. 15- WED. OCT. 16/ 2019
 ACTION: DENIED
  
 1) COMPLIED, REMOVED MANUAL CONSISTING OF 179 PAGES
  
 2) PROVISO: ART IN PUBLIC PLACES. THE CITY OF WEST PALM
 BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT
 APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR
 WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER
 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY
 WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 3) SHEET 014_G201 OVERALL PROPOSED FIRST FLOOR PLAN:
  
 3A) COMPLETED.
 CHILDREN?S BEHAVIOR UNIT AND ADDITION WILL BE KNOWN AS:
 BUILDING A
 THE BUILDING JUST TO THE SOUTH: BUILDING B
 THE BUILDING HOUSING THE ADULT BEHAVIOR UNIT AND
 ADDITION AS: BUILDING C
  
 3B)(1) 2ND REQUEST. IT IS NECESSARY FOR OUR RECORDS AND
 TRACKING PURPOSES (2) SEPARATE PERMITS WILL BE
 REQUIRED. THIS IS NOT JUST A REQUEST, IT IS A MUST.
 SINCE THE SCOPE OF WORK IS IN (2) BUILDINGS, IN (2)
 LOCATIONS AND FOR TRACKING PURPOSES (INSPECTIONS)
 THIS PERMIT SHOULD BE BROKEN DOWN INTO (2) SEPARATE
 PERMITS WITH SEPARATE IDENTITIES, (EXAMPLE BUILDING A
 OR BUILDING C), PLEASE ALSO SPLIT THE VALUE OF THE
 PERMIT APPLICATION ACCORDINGLY. UNDER THE 16110246
 PERMIT THE BUILDINGS WERE IDENTIFIED AS PAVILIONS,
 (EXAMPLE GYM: PAVILION 4). THE WHOLE CAMPUS IS LISTED
 UNDER 2201 45TH ST. THE BUILDINGS HAVE NO IDENTIFIERS,
 THIS WOULD BE A GREAT HELP FOR ADDRESSING OF THE
 CAMPUS.
  
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 OF THE ADMINISTRATIVE CODE SECTION
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 3B)(2) 2ND REQUEST. 2017 FBC-B 501.2 ADDRESS
 IDENTIFICATION. NEW AND EXISTING BUILDINGS SHALL BE
 PROVIDED WITH APPROVED ADDRESS IDENTIFICATION.
  
 CITY MUNI CODE SEC.78-6 (1-7) (2) LOCATION, BUILDINGS
 CONTAINING MORE THAN ONE ADDRESS. ALL ADDRESSES SHALL
 BE POSTED ON THAT PORTION OF THE STRUCTURE FRONTING OR
 FACING UPON THE STREET OR PRINCIPAL VEHICULAR ACCESS TO
 THE PREMISES, SO AS TO BE READILY VISIBLE TO
 APPROACHING VEHICLES.
  
 4A) SEMI-COMPLIED. THE SUBMITTED PLANS HAVE CIVIL
 PLANS, SITE PLANS AND ENGINEERING PLANS AS PART OF THE
 PACKAGE. SUBMITTED WAS A SURVEY WITH THE AE FLOOD ZONE
 SHOWN ON THE SURVEY THE EXISTING NORTH BUILDING,
 BUILDING A. THE EXISTING BUILDING IS NOT IN THE FLOOD
 ZONE BUT THE PROPOSED ADDITION IS IN THE AE FLOOD ZONE.
 PLEASE PROVIDE THE SURVEY WITH THE PROPOSED ADDITION AS
 AN OVERLAY TO SHOW IF THE ADDITION IS OR IS NOT IN THE
 FLOOD ZONE. OUR MAPS IT WOULD APPEAR TO BE IN A FLOOD
 ZONE AE.
  
 4B) SEMI-COMPLIED. THE SUBMITTED PLANS HAVE CIVIL
 PLANS, SITE PLANS AND ENGINEERING PLANS AS PART OF THE
 PACKAGE. SUBMITTED WAS A SURVEY WITH THE AE FLOOD ZONE
 SHOWN ON THE SURVEY THE EXISTING ADULT BEHAVIOR UNIT
 BUILDING C. THE EXISTING BUILDING C IS NOT IN THE FLOOD
 ZONE BUT THE PROPOSED ADDITION IT MAYBE LOCATED IN THE
 AE FLOOD ZONE. PLEASE PROVIDE THE SURVEY WITH THE
 PROPOSED ADDITION AS AN OVERLAY TO SHOW IF THE ADDITION
 IS OR IS NOT IN THE FLOOD ZONE AE. OUR MAPS IT WOULD
 APPEAR TO BE IN A FLOOD ZONE AE.
  
 4C) 2ND REQUEST. THE RESPONSE LETTER INDICATES SURVEY
 DOCUMENTS HAVE BEEN PROVIDED AS PART OF THIS SUBMITTAL.
 THIS QUESTION HAS NOTHING TO DO WITH THE SURVEY. PLEASE
 NOTE SINCE THE CITY CANNOT DETERMINE WHEN THESE
 BUILDINGS WERE BUILT, SINCE THEY WERE UNDER ONE
 ADDRESS. IF THE ORIGINAL BUILDINGS BOTH A & C ARE
 PRE-FIRM OR POST-FIRM OR IF THE ADDITION WILL MEET THE
 REQUIREMENTS FOR SUBSTANTIAL IMPROVEMENT A CONCISE CODE
 ANALYSIS FOR THE FLOOD REQUIREMENTS CANNOT BE
 DETERMINED EVEN FOR THE 2ND REVIEW, THIS QUESTION NOT
 ANSWERED.
  
  
  
 4C)(1) 2ND REQUEST. IN BOTH CASES IF THE EXISTING
 BUILDINGS (A & C)ARE EITHER PRE OR POST FIRM AND THE
 ADDITION (STRUCTURALLY CONNECTED) ARE NOT A SUBSTANTIAL
 IMPROVEMENT THEN THE ADDITION IS REQUIRED TO BE
 ELEVATED TO AT LEAST THE ELEVATION OF THE EXISTING
 FLOOR. TAKEN FROM SI/SD DESK REFERENCE.
  
 4C)(2) 2ND REQUEST. UNDER THE 2017 EXIST. BUILDING CODE
 SECTION 1103.5 APPLIES:
 BS]1103.5 FLOOD HAZARD AREAS. ADDITIONS AND FOUNDATIONS
 IN FLOOD HAZARD AREAS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1.FOR HORIZONTAL ADDITIONS THAT ARE STRUCTURALLY
 INTERCONNECTED TO THE EXISTING BUILDING:
  
 1.1. (BUILDING C.) IF THE ADDITION AND ALL OTHER
 PROPOSED WORK, WHEN COMBINED, CONSTITUTE SUBSTANTIAL
 IMPROVEMENT, THE EXISTING BUILDING AND THE ADDITION
 SHALL COMPLY WITH SECTION 1612 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 1.2. (BUILDING A). IF THE ADDITION CONSTITUTES
 SUBSTANTIAL IMPROVEMENT, THE EXISTING BUILDING AND THE
 ADDITION SHALL COMPLY WITH SECTION 1612 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 IF EITHER OF THE BUILDINGS (A OR C) MEET THE
 REQUIREMENTS FOR SUBSTANTIAL IMPROVEMENTS THEN UNDER
 THE 2017 FBC-B 1612 FLOOD LOADS TABLE 1612.1 SECTION
 449 HOSPITALS.
  
 449.4.2.2.2 FOR ALL EXISTING FACILITIES, THE LOWEST
 FLOOR ELEVATIONS OF ALL ADDITIONS, AND ALL PATIENT
 SUPPORT AREAS INCLUDING FOOD SERVICE, AND ALL PATIENT
 SUPPORT UTILITIES, INCLUDING MECHANICAL, AND ELECTRICAL
 (EXCEPT FUEL STORAGE AS NOTED IN SECTION 449.4.2.9.3 OF
 THIS CODE) FOR THE ADDITIONS SHALL BE AT OR ABOVE THE
 ELEVATION OF THE EXISTING BUILDING, IF THE EXISTING
 BUILDING WAS DESIGNED AND CONSTRUCTED TO COMPLY WITH
 EITHER THE SITE STANDARDS OF SECTION 449.4 OF THIS CODE
 OR LOCAL FLOOD-RESISTANT REQUIREMENTS, IN EFFECT AT THE
 TIME OF CONSTRUCTION, WHICHEVER REQUIRES THE HIGHER
 ELEVATION, UNLESS OTHERWISE PERMITTED BY SECTION 1612
 OF THIS CODE. IF THE EXISTING BUILDING WAS CONSTRUCTED
 PRIOR TO THE ADOPTION OF EITHER THE SITE STANDARDS OF
 SECTION 449.4 OF THIS CODE OR LOCAL FLOOD-RESISTANT
 REQUIREMENTS, THEN THE ADDITION AND ALL PATIENT SUPPORT
 AREAS AND UTILITIES FOR THE ADDITION AS DESCRIBED IN
 THIS SECTION SHALL EITHER BE DESIGNED AND CONSTRUCTED
 TO MEET THE REQUIREMENTS OF SECTION 449.4.2.2.1 OF THIS
 CODE OR BE DESIGNED AND CONSTRUCTED TO MEET THE DRY
 FLOOD PROOFING REQUIREMENTS OF SECTION 1612 OF THIS
 CODE.
 449.4.2.2.3 SUBSTANTIAL IMPROVEMENT, AS DEFINED BY
 SECTION 1612 OF THIS CODE, TO ALL EXISTING FACILITIES
 LOCATED WITHIN FLOOD AREAS AS DEFINED IN SECTION 1612
 OF THIS CODE OR WITHIN A CATEGORY 3 SURGE INUNDATION
 ZONE AS DESCRIBED IN SECTION 449.4.2.2.1 OF THIS CODE,
 SHALL BE DESIGNED AND CONSTRUCTED IN COMPLIANCE WITH
 SECTION 1612 OF THIS CODE.
 PLEASE PROVIDE A COST ANALYSIS TO SEE IF THE
 SUBSTANTIAL REQUIREMENT IS OR IS NOT MET, AN EXAMPLE IS
 UNDER PERMIT 16110246.
  
 UNDER THE 2ND REVIEW WE HAVE RECEIVED A VALUE OF 25
 MILLION IN IMPROVEMENTS, USING THE PALM BEACH COUNTY
 PROPERTY APPRAISER?S OFFICE THE VALUE FOR IMPROVEMENTS
 IS $16,434,316.00. THERE VALUE IS USUALLY LOW. EVEN
 WITH A INCREASED VALUE OF 1.25% OR $20,542,895.00
 DOLLARS THE WHOLE CAMPUS WOULD BE SUBSTANTIAL
 IMPROVEMENTS. EVEN IF WE GO AS FAR AS FIGURING THE
 WHOLE CAMPUS 124,817 SQUARE FEET AT NEW CONSTRUCTION
 COST OF $308.81 DOLLARS A SQUARE FOOT OR A COST OF $38,
 544,737.00 THE $25 MILLION WOULD BE CONSIDERED
 SUBSTANTIAL IMPROVEMENTS. I EXPLAINED THIS TO MS. HILL
 (PLAN REVIEW SUPERVISOR) YESTERDAY, SO SHE HAS SENT OUT
 AN E-MAIL EXPLAINING WHAT SHOULD BE USED PERMIT WISE TO
 DETERMINE WHAT PERMITS SHOULD BE USED FOR THE LAST 5
 YEARS TO DETERMINE IF SUBSTANTIAL IMPROVEMENTS HAVE
 BEEN MET FOR BUILDINGS A & C
  
 4D) 2ND REVIEW. HAVE YOU RECEIVED A LOMAR REMOVING
 THESE AREAS FROM THE FLOOD ZONE? RESPONSE INDICATES
 REFER TO ENCLOSED RESPONSE LETTER ISSUED BY
 KIMLEY-HORN. THE LETTER FROM KIMLEY HORN STATES THE
 PROPOSED BEHAVIORAL ADDITIONS AND ALTERATIONS DOES NOT
 QUALIFY AS A SUBSTANTIAL IMPROVEMENT. THE DOCUMENTS
 SUBMITTED AT THIS TIME STATING 25 MILLION IN
 IMPROVEMENTS, EVEN IF THIS VALUE IS FOR THE WHOLE
 CAMPUS QUALIFIES AS SUBSTANTIAL IMPROVEMENTS WHEN TAKEN
 AT NEW CONSTRUCTION COST OF $38 MILLION FOR THE WHOLE
 CAMPUS.
  
 5) SHEET 002_G100:
  
 5A-B) SEMI-COMPLIED. THE COMMENT SHEET RESPONSE 5C
 ANSWERS COMMENT 5A & & 5B. THE BUILDINGS A & B ARE TO
 BE CONSIDERED ONE BUILDING. SHEET G100 UNDER THE
 HEADING (5) IT IS NOT CLEAR AS TO WHAT BUILDINGS ARE
 BEING GROUPED TOGETHER SINCE THE NOMENCLATURE INCLUDES
 BUILDINGS 1,2,3 AS WELL AS A,B & C. THE RESPONSE TO
 COMMENT 5C MAKES IT CLEAR, BUT THE COMMENT SHEET WILL
 NOT FOLLOW THE PLANS TO SCANNING AND RECORD RETENTION.
 PLEASE REVISE AND STATE THAT BUILDINGS A & B ARE TO BE
 CONSIDERED 1 BUILDING ON THE SAME LOT. PLEASE ALSO NOTE
 FOR AREA OF A BUILDING THE DIMENSIONS ARE TAKEN FROM
 THE INSIDE OF THE EXTERIOR WALL, JUST AS THE SMOKE
 COMPARTMENTS. FLOOR AREA, GROSS. THE FLOOR AREA WITHIN
 THE INSIDE PERIMETER OF THE EXTERIOR WALLS OF THE
 BUILDING UNDER CONSIDERATION.
  
 5C) SEMI-COMPLIED. THE RESPONSE TO COMMENT 5C DOES
 INDICATE BUILDING C AND ADDITION IS TO BE CONSIDERED A
 STAND-ALONE BUILDING. WHAT I CAN NOT FIND IS AN ASSUMED
 PROPERTY LINE BETWEEN BUILDING B AND BUILDING C NOR
 COMPLIANCE WITH FBC-B TABLE 602 FIRE RESISTANCE RATINGS
 FOR EXTERIOR WALLS BASED ON FIRE SEPARATION DISTANCE
 NOR THE MAXIMUM AREA OF EXTERIOR WALL OPENINGS BASED ON
 FIRE SEPARATION DISTANCE & DEGREE OF OPENING PROTECTION
 FBC-B TABLE 705.8.
  
 1ST ROUND COMMENTS. WITH THE NEW ADDITION TO BUILDING
 A, THE PLANS ARE SILENT AS TO INDIVIDUAL BUILDINGS NOT
 CONSIDERED AS ONE, THEN THERE SHOULD BE A PROPOSED
 IMAGINARY PROPERTY LINE BETWEEN BUILDINGS A & C AND
 DISTANCE BETWEEN THIS IMAGINARY PROPERTY LINE FOR WALL
 RATINGS AND ALLOWABLE SQ. FT. OF WALL OPENINGS. SEE
 TABLE 602 AND 705.8. NONE OF THESE THINGS APPEAR TO BE
 CONSIDERED, ONLY TABLE 601. THERE IS A FOOTNOTE A
 NOTING A REDUCTION OF 1 HOUR FOR STRUCTURAL FRAME,
 BEARING WALLS AND REDUCTION OF ROOF WHERE ONLY
 SUPPORTING ROOF THIS IS FOUND ONLY IN TYPE I-A AND I-B
 CONSTRUCTION NOT II-B. THE OTHER ISSUE IS UNDER 603.1.1
 WHERE FIRE RETARDANT TREATED WOOD CAN BE USED.
  
 6 & 7) 2ND REQUEST. WE HAVE MULTIPLE PERMITS FOR THIS
 SITE AND THE QUESTION OF EXPOSURE HAS COME UP IN ALL OF
 THE PLAN REVIEWS. WE HAVE TAKEN THIS QUESTION TO THE
 BUILDING OFFICIAL ROBERT BROWN FOR AN INTERPRETATION
 FOR THE CITY OF WEST PALM BEACH. MR. BROWN HAS
 DETERMINED THAT THIS SITE DOES QUALIFY AS AN C EXPOSURE
 SINCE IT DOES QUALIFY AS AN C SURFACE ROUGHNESS
 CATEGORY.
  
 1ST ROUND OF COMMENTS. SHEET 076_S001 IN THE STRUCTURAL
 NOTES IN THE WIND DESIGN DATA THE EXPOSURE IS GIVEN AS
 A B EXPOSURE. IT WOULD APPEAR THAT TO THE NORTHEAST AND
 NORTHWEST THERE ARE C EXPOSURES SINCE MOST OF THESE
 AREAS HAVE LITTLE OR NO BUILDINGS, THEY ARE GRASSLANDS,
 OPEN LAKES, CANALS, PARKING LOTS AND HIGHWAYS.
 2017 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES. A
 GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE SECTOR
 SHALL BE DETERMINED FOR A DISTANCE UPWIND OF THE SITE
 AS DEFINED IN SECTION 1609.4.3 FROM THE CATEGORIES
 DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING AN EXPOSURE
 CATEGORY AS DEFINED IN SECTION 1609.4.3.
 SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30
 FEET. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, AND
 GRASSLANDS.
  
 7)2ND REQUEST SEE COMMENT # 6. SINCE THE EXPOSURE WOULD
 BE A C EXPOSURE FOR 179 VASD THE PRESSURES WILL
 INCREASE FOR THE MULTIPLIER FOR THE HEIGHT OF THE
 BUILDING FOR THE EXPOSURE C. SEE TABLE 1609.7(2).
  
 8) 2ND REQUEST. SINCE THE BUILDING OFFICIAL HAS DEEMED
 THIS AN EXPOSURE C THE PRESSURES SHOWN ON THE PLANS
 WILL BE INCREASED.
 1ST ROUND COMMENT. PLEASE ALSO NOTE ON SHEET 076_S001
 UNDER THE HEADING 2.4.1 EXTERIOR COMPONENTS & CLADDING
 THE COLUMN OF PRESSURES FOR CORNERS WALL ZONE 5 THE
 NEGATIVE PRESSURES FOR 20 SQ. FT. AND 100 SQ. FT. ARE
 THE SAME AND THE PRESSURES FOR 50 SQ. FT. ARE HIGHER
 THAN FOR THE 20 SQ. FT. IT WOULD APPEAR THIS IS A TYPO,
 PLEASE PROVIDE ADDITIONAL INFORMATION, PLEASE.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 9A) BUILDING PROVISO/ DEFERRED SUBMITTAL. 2017 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS & CURBS
  
 9B) BUILDING PROVISO/ DEFERRED SUBMITTAL. W. P. B.
 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE 61G20
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) BUILDING PROVISO/ DEFERRED SUBMITTAL. IDENTIFY
 GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE PRODUCT
 APPROVAL BEFORE SUBMITTING TO DESIGNER OF RECORD AND
 BEFORE SUBMISSION TO THE BUILDING DEPARTMENT. FOR ALL
 PRODUCTS WITH GLAZING, PLEASE IDENTIFY THE OPENING
 WIDTH & HEIGHT, TYPE OF GLAZING, MULLION SIZE, LENGTH
 IF UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 11) BUILDING PROVISO/ DEFERRED SUBMITTAL. ROOFING: FOR
 ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 12) BUILDING PROVISO/ DEFERRED SUBMITTAL. EFIS SYSTEMS:
 PLEASE PROVIDE THE PRODUCT APPROVAL FOR THE SYSTEM TO
 BE INSTALLED. PLEASE ALSO PROVIDE THE MANUFACTURERS
 INSTALLATION BROCHURE PROVIDING COMPLIANCE WITH 2014
 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION
  
 13) BUILDING PROVISO/ DEFERRED SUBMITTAL, BY DESIGNER
 OF RECORD FOR COMPONENTS AND CLADDING. 107.3.4.2
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14A) SEMI-COMPLIED. THIS REVIEW SHEET 076_ S001
 INDICATES THERE IS A GEOTECHNICAL REPORT BY
 PROFESSIONAL SERVICE INDUSTRIES, INC, PLEASE SUBMIT
 EITHER A PAPER REPORT SIGNED AND SEALED OR AN
 ELECTRONIC REPORT WITH ELECTRONIC SIGNATURE AND SEAL,
 TO SATISFY COMPLIANCE WITH 1803.5.2 OF THE 2017 FBC-B.
  
 1ST ROUND OF COMMENTS. SHEET 076_S001 UNDER THE HEADING
 OF FOUNDATION AND THE GEOTECHNICAL REPORT IT DOES NOT
 INDICATE A REPORT NUMBER NOR UNDER THE SOIL BEARING
 CAPACITY FOR ISOLATED FOOTING OR CONTINUOUS FOOTING THE
 PSF IS LEFT BLANK. PLEASE SHOW COMPLIANCE WITH THE 2017
 FBC-B SECTION:
  
 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION,
 STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 14B) NEW COMMENT. SHEET 076_S001 UNDER THE HEADING
 FOUNDATION 2.1 DOES INDICATE MUCK LAYER TO BE REMOVED.
 NOT HAVING THE REPORT YET WE WILL NEED TO SEE WHAT THE
 GEOTECHNICS ENGINEER WILL REQUIRE FOR BACKFILLING OF
 THE MUCK AREA, SOILS TYPE, COMPACTING TO WHAT
 PERCENTAGE AND AT WHAT MAXIMUM LIFTS. THE PLANS STATE
 WHAT THE STRUCTURAL ENGINEER WILL REQUIRE, DOES THE
 GEOTECHNICAL REPORT REQUIRE THE SAME.107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 14C) NEW COMMENT. SINCE THERE IS MUCK FOUND AND A
 DEMUCKING PROCESS IS TO TAKE PLACE AND MAXIMUM LIFTS OF
 EVERY 8 INCHES, WHO WILL BE THE GEOTECHNICAL ENGINEER
 WHO WILL BE PRESENT TO MONITOR THE FILL PROCESS IN
 COMPLIANCE WITH THE STRUCTURAL ENGINEER AND SOILS
 ENGINEER?S REQUIREMENTS? SEE 2017 FBC-B 1803.5.8.
  
  
  
 15) SEMI- COMPLIED. THE NOTE FOUND DETAIL # 4/ SHEET
 A475 DOES INDICATE FIRE RETARDANT TREATED PLYWOOD AND B
 STEEL DECKING. THE QUESTION WILL ARISE WITH THE
 STANDING SEAM METAL ROOFING PRODUCT APPROVAL AS TO THE
 TYPE OF DECKING AND ANCHOR AS TO THE PSF THE ANCHOR CAN
 HOLD, WILL IT BE REQUIRED TO GO THROUGH THE PLYWOOD
 (THICKNESS NOT GIVEN) OR THROUGH THE STEEL DECKING?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 16) COMPLIED.
  
 17) SEMI-COMPLIED. SHEET055_A475 SHOWS A DETAIL4.
 THICKNESS OF THE PLYWOOD NOT GIVEN. SHEET A351. DETAIL
 # 3 DOES GIVE THE THICKNESS. PLEASE NOTE THERE ARE
 OTHER SHEETS THAT EITHER STATE THE USE OF PLYWOOD OR
 NOT MENTIONING THE SUB-STRATE, THIS NOTE COUNTS FOR
 ALL.
  
 18) 2ND REQUEST. RESIDENT INSPECTOR FORMS WERE SENT TO:
 [email protected] SENT AT3/26/2019 @ 06:25 AM.
 FORMS NOT RETURNED FILED OUT.
 1ST ROUND OF COMMENTS. THIS PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR ON THE PROJECT AS LONG AS THERE IS
 STRUCTURAL STEEL BOLTED OR WELDED CONNECTIONS BAR JOIST
 AND THE STEEL ROOF DECK ANCHORING BY WELDS OR BOLTED
 CONNECTIONS.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 110.3.9. OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109 110. HE/SHE MAY ACCEPT REPORTS OF
 INSPECTORS OF RECOGNIZED INSPECTION SERVICES, PROVIDED
 THAT AFTER INVESTIGATION HE/SHE IS SATISFIED AS TO
 THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE
 CALLED FOR BY ANY PROVISION OF THE TECHNICAL CODES
 SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE SAME ARE
 IN WRITING AND CERTIFIED BY A RESPONSIBLE OFFICER OF
 SUCH SERVICE. THE BUILDING OFFICIAL MAY REQUIRE THE
 OWNER TO EMPLOY AN INSPECTION SERVICE IN THE FOLLOWING
 INSTANCES:
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3) WELDING AND BOLTED CONNECTIONS
 FORMS ARE TO BE E-MAILED TO: [email protected] SENT
 AT3/26/2019 @ 06:25 AM.
  
 19A) 2ND REQUEST. THE RESPONSE INDICATES COMPLIANCE
 WITH UNDERGROUND TERMITE PROTECTION CAN BE FOUND ON
 SHEETS S001 NOR S002. PLEASE CIRCLE WHERE THIS
 REQUIREMENT CAN BE FOUND, I DIDN?T SEE WHERE THIS NOTE
 IS LOCATED. THANK YOU. AS FAR AS SPECIFICATIONS WE DO
 NOT REVIEW SPECIFICATIONS.
  
 1ST ROUND OF COMMENTS. NEITHER SHEET 083_S201 NOR
 084_S202 SHOW COMPLIANCE WITH UNDERGROUND TERMITE
 PROTECTION 1816.1 OF THE 2017 FBC-B FOR THE NEW WORK OR
 TRENCHES CUT THROUGH THE SLAB.
  
 19B) 2ND REQUEST. THE RESPONSE INDICATES DAMP-PROOFING
 OF THE SLAB ON GRADE CAN BE FOUND ON IN NOTES ON SHEETS
 S001 AND S002. PLEASE CIRCLE I DIDN?T SEE WHERE THIS
 NOTE IS LOCATED. THANK YOU. AS FAR AS SPECIFICATIONS WE
 DO NOT REVIEW SPECIFICATIONS.
 1ST ROUND OF COMMENTS. NEITHER SHEET 083_S201 NOR
 084_S202 SHOW COMPLIANCE WITH 1805.2.1 DAMP-PROOFING OF
 SLABS. WHERE INSTALLED BENEATH THE SLAB, DAMP-PROOFING
 SHALL CONSIST OF NOT LESS THAN 6-MIL (0.006 INCH)
 POLYETHYLENE WITH JOINTS LAPPED NOT LESS THAN 6 INCHES
 (152 MM), OR OTHER APPROVED METHODS OR MATERIALS.
  
 20-21) COMPLIED
  
 22) UNDERSTOOD THE IMPACT FEES WILL NOT BE PAID UNTIL
 PLANS ARE READY FOR ISSUANCE.
 IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  