2019-03-20 14:50:48 | PLUMBING 1ST REVIEW**DENIED** |
| |
| 1) SHT. G175 DETAIL #4 SHOWS THE TOILET @ 1' 5" (17") |
| TO THE CENTER. YOUR GRAB BAR IS SHOWING 6" FROM THE |
| SIDE WALL WHICH IF THE TOILET WAS CENTERED @ 18" WOULD |
| BE CORRECT AS THE GRAB BAR IS INSTALL 12" FROM THE |
| CENTER LINE OF THE TOILET MEANING THIS GRAB BAR WOULD |
| BE 5" FROM THE SIDE WALL. FBC-A 604.5.2 |
| |
| 2) PROVIDE ALL 3 WATER HEATER'S INSTALLATION MANUAL'S. |
| FBC 107.2.1 |
| |
| 3) PROVIDE A COMPLETE ISOMETRIC OF THE NEW STORM |
| SYSTEM. FBC 107.3.5 |
| |
| 4) SHT. A600 UNDER TOILET ACCESSORIES LEGEND DETAIL C |
| AND C1 THE GRAB BAR IS LISTING AS EITHER 24", 30", OR |
| 36". THE FLORIDA ACCESSIBILITY CODE REQUIRES THE REAR |
| GRAB BAR TO BE MIN 36". FBC-A 604.5.2 |
| |
| 5) SHT.301 DOMESTIC WATER RISER DOES NOT SHOW THE |
| REQUIRED SHUT OFF VALVE THAT SHOULD BE @ EVERY TOP-DOWN |
| FEED IN THE PIPING SYSTEM. FBC-P 606 #5. WOULD ALSO |
| NEED TO PROVIDE ACCESS FOR EACH VALVE. FBC-P 606.3 |
| |
| 6) WHAT IS THE PURPOSE OF THE DOMESTIC WATER IN THE |
| MECH ROOM? PLEASE CLAIRFY AND DOES IT NEED BACKFLOW |
| PROTECTION. FBC 107.2.1 |
| |
| 7) IT APPEARS ON THE FLAT DRAWING OF THE SANITARY |
| SYSTEM THE FOLLOWING ROOMS HAVE THE FLOOR DRAINS DRY |
| VENTED SO AS THE BASE OF STACK WOULD NEVER BE WASHED. |
| BH 157, 114, 225, 159, 157, 105, 209, 218. FBC-P 912.2 |
| |
| 8) THERE ARE MUILT SINK DISCHARGING INTO THE BATHROOM |
| GROUP WET VENT. ONLY THE FIXTURES OF THE BATHRROM GROUP |
| ARE PRMITTED TO BE IN THE BATHROOM GROUP WET VENT. |
| FBC-P 912.1. BH201, 120, 109, 107, 105, 113 |
| |
| 9) IT AOOEARS THE OVERALL DELELOPED LENGTH OF THE HOT |
| WATER PIPING WILL BE OVER 50' FROM THE WATER HEATER TO |
| THE BATHROOM GROUP BH159. |
| |
| 10) SHT. 100A NEAR RESTOOM BH157 HAS THE 4" SS FITTING |
| IN THE WRONG DIRECTION. ALL FITTING SHALL BE IN THE |
| DIRECTION OF FLOW. FBC-P 706.3 |
| |
| 11) A600 BATHROOM DETAIL 1-BH157PAT DOES NOT SHOW THE |
| CLEAR FLOOR SPACE FOR THE SHOWER. FBC-A 706.3 |
| |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| |