Plan Review Notes
Plan Review Notes For Permit 18120436
Permit Number 18120436
Review Stop P
Sequence Number 1
Notes
Date Text
2019-03-20 14:50:48PLUMBING 1ST REVIEW**DENIED**
  
 1) SHT. G175 DETAIL #4 SHOWS THE TOILET @ 1' 5" (17")
 TO THE CENTER. YOUR GRAB BAR IS SHOWING 6" FROM THE
 SIDE WALL WHICH IF THE TOILET WAS CENTERED @ 18" WOULD
 BE CORRECT AS THE GRAB BAR IS INSTALL 12" FROM THE
 CENTER LINE OF THE TOILET MEANING THIS GRAB BAR WOULD
 BE 5" FROM THE SIDE WALL. FBC-A 604.5.2
  
 2) PROVIDE ALL 3 WATER HEATER'S INSTALLATION MANUAL'S.
 FBC 107.2.1
  
 3) PROVIDE A COMPLETE ISOMETRIC OF THE NEW STORM
 SYSTEM. FBC 107.3.5
  
 4) SHT. A600 UNDER TOILET ACCESSORIES LEGEND DETAIL C
 AND C1 THE GRAB BAR IS LISTING AS EITHER 24", 30", OR
 36". THE FLORIDA ACCESSIBILITY CODE REQUIRES THE REAR
 GRAB BAR TO BE MIN 36". FBC-A 604.5.2
  
 5) SHT.301 DOMESTIC WATER RISER DOES NOT SHOW THE
 REQUIRED SHUT OFF VALVE THAT SHOULD BE @ EVERY TOP-DOWN
 FEED IN THE PIPING SYSTEM. FBC-P 606 #5. WOULD ALSO
 NEED TO PROVIDE ACCESS FOR EACH VALVE. FBC-P 606.3
  
 6) WHAT IS THE PURPOSE OF THE DOMESTIC WATER IN THE
 MECH ROOM? PLEASE CLAIRFY AND DOES IT NEED BACKFLOW
 PROTECTION. FBC 107.2.1
  
 7) IT APPEARS ON THE FLAT DRAWING OF THE SANITARY
 SYSTEM THE FOLLOWING ROOMS HAVE THE FLOOR DRAINS DRY
 VENTED SO AS THE BASE OF STACK WOULD NEVER BE WASHED.
 BH 157, 114, 225, 159, 157, 105, 209, 218. FBC-P 912.2
  
 8) THERE ARE MUILT SINK DISCHARGING INTO THE BATHROOM
 GROUP WET VENT. ONLY THE FIXTURES OF THE BATHRROM GROUP
 ARE PRMITTED TO BE IN THE BATHROOM GROUP WET VENT.
 FBC-P 912.1. BH201, 120, 109, 107, 105, 113
  
 9) IT AOOEARS THE OVERALL DELELOPED LENGTH OF THE HOT
 WATER PIPING WILL BE OVER 50' FROM THE WATER HEATER TO
 THE BATHROOM GROUP BH159.
  
 10) SHT. 100A NEAR RESTOOM BH157 HAS THE 4" SS FITTING
 IN THE WRONG DIRECTION. ALL FITTING SHALL BE IN THE
 DIRECTION OF FLOW. FBC-P 706.3
  
 11) A600 BATHROOM DETAIL 1-BH157PAT DOES NOT SHOW THE
 CLEAR FLOOR SPACE FOR THE SHOWER. FBC-A 706.3
  
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
  
 TIM HUNT
 PLUMBING INSPECTOR/PLUMBING PLAN EXAMINER
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]