Plan Review Notes
Plan Review Notes For Permit 18120436
Permit Number 18120436
Review Stop M
Sequence Number 1
Notes
Date Text
2019-03-21 08:22:081ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18120436
 3/21/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN COMPLIANCE WITH SECTION C403.2.1 FBC EC.
  
 2) PROVIDE AN ENERGY COMPLIANCE REPORT FOR THE NEW
 ADDITIONS- SEE SECTIONS C502.1 AND C101.5.1 FBC EC
  
 3) COMMISSIONING OF THE MECHANICAL SYSTEMS AND
 ELECTRICAL LIGHTING AND POWER SYSTEMS IS REQUIRED PER
 SECTION C408.2 FBC-14 ENERGY CONSERVATION. SUBMIT A
 COMMISSIONING PLAN AS OUTLINED IN SECTION C408.2.1 AND
 DESCRIBED IN SECTIONS C403.2.2- C408.2.3.3. PLEASE NOTE
 THAT A COPY OF THE COMMISSIONING REPORT SHALL BE
 SUBMITTED FOR REVIEW AT FINAL INSPECTION.
  
 4) SHEET M001: PLEASE ADD THE PRESSURE RELATIONSHIPS-
 POSITIVE OR NEGATIVE- FOR THE ROOMS LISTED IN THE AIR
 BALANCE SCHEDULES- REFER TO TABLE 7-1 DESIGN
 PARAMETERS, ASHRAE 170-2008.
  
 5) M001: SOILED WORKROOMS AND SOILED HOLDING ROOMS
 REQUIRE A MINIMUM OF 2 OUTDOOR AIR CHANGES PER TABLE
 7-1. THE SCHEDULES SHOW 0 TO BE PROVIDED.
  
 6) M101B: FIRE DAMPERS MISSING FOR DUCTS PENETRATING
 THE FIRE-RATED EQUIP. STOR. RM WALLS- SECTION 607.5.2
 FBC M.
  
 7) M101A & M101B: PROVIDE EQUIPMENT SCHEDULES FOR THE
 APPLIANCES IN THE DINING ROOMS, AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS- SECTION 304.1 FBC M.
  
 8) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS
 OF ALL THE ROOF TOP EQUIPM,ENT AND REQUIRED CLEARANCE
 DISTANCE MEASURES FOR AIR INTAKES AND ROOF EDGES-
 SECTION 107.2.1 WPB.
  
 9) SUBMIT SITE SPECIFIC WIND LOAD ENGINEERING FOR TIE
 DOWN OF ALL ROOF MOUNTED MECHANICAL EQUIPMENT AND
 APPLIANCES- SECTIO N 301.15 FBC M.
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATERS AND THE DRYER- SECTIONS 304.1 AND 504.1 FBC M
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  