2019-03-26 08:11:392017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18120436
 ADD: 2201 45TH ST.
 CONT: DPR CONSTRUCTION
 TEL: 954-991-6200
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. MARCH 18/THROUGH TUES. MARCH 26/ 2019
 ACTION: DENIED
  
 1) PLEASE NOTE WITHIN THE DOCUMENT FOLDER THE PROJECT
 MANUAL CONSISTING OF 179 PAGES WAS LOADED AS INDIVIDUAL
 PAGES, THIS IS INCORRECT, IT SHOULD BE LOADED AS A
 SINGLE DOCUMENT WITH THE FOLDER LABELED PROJECT MANUAL.
 YOU WILL NEED TO SPEAK WITH CAROLINE PUELL PLAN REVIEW
 LIBRARIAN (TELL: 561-805-6659) AS TO HOW TO CORRECT
 THIS MATTER.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1 ADMINISTRATION 107.2.1.3 QUALITY OF
 BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH
 THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO
 ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE
 SUCH THINGS, CLARITY, OR OTHER ITEMS RELATED TO RECORDS
 MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH
 THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES.
  
 2) ART IN PUBLIC PLACES
 THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES
 ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR
 NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT
 APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL
 PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE
 DEVELOPMENT.
 (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND
 THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL
 PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE
 EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS
 WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED
 CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 3) SHEET 014_G201 OVERALL PROPOSED FIRST FLOOR PLAN:
  
 3A) PLEASE NOTE FOR THIS REVIEW THE NORTH BUILDING THE
 CHILDREN?S BEHAVIOR UNIT WILL BE KNOWN AS BUILDING A,
 THE BUILDING JUST TO THE SOUTH BUILDING B AND THE
 BUILDING HOUSING THE ADULT BEHAVIOR UNIT AND ADDITION
 AS BUILDING C.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE (IDENTIFY BUILDINGS)THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED.
  
 3B) SINCE THE SCOPE OF WORK IS IN (2) BUILDINGS, IN (2)
 LOCATIONS AND FOR TRACKING PURPOSES (INSPECTIONS)
 THIS PERMIT SHOULD BE BROKEN DOWN INTO (2) SEPARATE
 PERMITS WITH SEPARATE IDENTITIES,( EXAMPLE BUILDING A
 OR BUILDING C), PLEASE ALSO SPLIT THE VALUE OF THE
 PERMIT APPLICATION ACCORDINGLY. UNDER THE 16110246
 PERMIT THE BUILDINGS WERE IDENTIFIED AS PAVILIONS,
 (EXAMPLE GYM: PAVILION 4). THE WHOLE CAMPUS IS LISTED
 UNDER 2201 45TH ST. THE BUILDINGS HAVE NO IDENTIFIERS,
 THIS WOULD BE A GREAT HELP FOR ADDRESSING OF THE
 CAMPUS.
 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND
 EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED
 ADDRESS IDENTIFICATION.
  
 CITY MUNI CODE SEC.78-6 (1-7) (2) LOCATION, BUILDINGS
 CONTAINING MORE THAN ONE ADDRESS. ALL ADDRESSES SHALL
 BE POSTED ON THAT PORTION OF THE STRUCTURE FRONTING OR
 FACING UPON THE STREET OR PRINCIPAL VEHICULAR ACCESS TO
 THE PREMISES, SO AS TO BE READILY VISIBLE TO
 APPROACHING VEHICLES.
  
 4A) THE SUBMITTED PLANS HAVE CIVIL PLANS, SITE PLANS
 AND ENGINEERING PLANS AS PART OF THE PACKAGE BUT THERE
 IS NO SURVEY IN THIS SET OF PLANS. PLEASE SUBMIT A
 SURVEY WITH THE AE FLOOD ZONE SHOWN ON THE SURVEY THE
 EXISTING NORTH BUILDING. THE EXISTING BUILDING IS NOT
 IN THE FLOOD ZONE BUT THE PROPOSED ADDITION IS IN THE
 AE FLOOD ZONE.
  
 4B) THE SUBMITTED PLANS HAVE CIVIL PLANS, SITE PLANS
 AND ENGINEERING PLANS AS PART OF THE PACKAGE BUT THERE
 IS NO SURVEY IN THIS SET OF PLANS. PLEASE SUBMIT A
 SURVEY WITH THE AE FLOOD ZONE SHOWN ON THE SURVEY THE
 EXISTING SOUTH BUILDING. THE EXISTING BUILDING IS NOT
 IN THE FLOOD ZONE BUT THE PROPOSED ADDITION MAYBE IN
 THE AE FLOOD ZONE.
  
 4C) PLEASE NOTE SINCE THE CITY CANNOT DETERMINE WHEN
 THESE BUILDINGS WERE BUILT, IF THE ORIGINAL BUILDINGS
 BOTH A & C ARE PRE-FIRM OR POST-FIRM OR IF THE ADDITION
 WILL MEET THE REQUIREMENTS FOR SUBSTANTIAL IMPROVEMENT
 A CONCISE CODE ANALYSIS FOR THE FLOOD REQUIREMENTS
 CANNOT BE DETERMINED.
  
 4C)(1) IN BOTH CASES IF THE EXISTING BUILDINGS (A &
 C)ARE EITHER PRE OR POST FIRM AND THE ADDITION
 (STRUCTURALLY CONNECTED) ARE NOT A SUBSTANTIAL
 IMPROVEMENT THEN THE ADDITION IS REQUIRED TO BE
 ELEVATED TO AT LEAST THE ELEVATION OF THE EXISTING
 FLOOR. TAKEN FROM SI/SD DESK REFERENCE.
  
 4C)(2) UNDER THE 2017 EXIST. BUILDING CODE SECTION
 1103.5 APPLIES:
 BS]1103.5 FLOOD HAZARD AREAS. ADDITIONS AND FOUNDATIONS
 IN FLOOD HAZARD AREAS SHALL COMPLY WITH THE FOLLOWING
 REQUIREMENTS:
 1.FOR HORIZONTAL ADDITIONS THAT ARE STRUCTURALLY
 INTERCONNECTED TO THE EXISTING BUILDING:
  
 1.1. (BUILDING C.) IF THE ADDITION AND ALL OTHER
 PROPOSED WORK, WHEN COMBINED, CONSTITUTE SUBSTANTIAL
 IMPROVEMENT, THE EXISTING BUILDING AND THE ADDITION
 SHALL COMPLY WITH SECTION 1612 OF THE FLORIDA BUILDING
 CODE, BUILDING.
  
 1.2. (BUILDING A). IF THE ADDITION CONSTITUTES
 SUBSTANTIAL IMPROVEMENT, THE EXISTING BUILDING AND THE
 ADDITION SHALL COMPLY WITH SECTION 1612 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 IF EITHER OF THE BUILDINGS (A OR C) MEET THE
 REQUIREMENTS FOR SUBSTANTIAL IMPROVEMENTS THEN UNDER
 THE 2017 FBC-B 1612 FLOOD LOADS TABLE 1612.1 SECTION
 449 HOSPITALS.
  
 449.4.2.2.2 FOR ALL EXISTING FACILITIES, THE LOWEST
 FLOOR ELEVATIONS OF ALL ADDITIONS, AND ALL PATIENT
 SUPPORT AREAS INCLUDING FOOD SERVICE, AND ALL PATIENT
 SUPPORT UTILITIES, INCLUDING MECHANICAL, AND ELECTRICAL
 (EXCEPT FUEL STORAGE AS NOTED IN SECTION 449.4.2.9.3 OF
 THIS CODE) FOR THE ADDITIONS SHALL BE AT OR ABOVE THE
 ELEVATION OF THE EXISTING BUILDING, IF THE EXISTING
 BUILDING WAS DESIGNED AND CONSTRUCTED TO COMPLY WITH
 EITHER THE SITE STANDARDS OF SECTION 449.4 OF THIS CODE
 OR LOCAL FLOOD-RESISTANT REQUIREMENTS, IN EFFECT AT THE
 TIME OF CONSTRUCTION, WHICHEVER REQUIRES THE HIGHER
 ELEVATION, UNLESS OTHERWISE PERMITTED BY SECTION 1612
 OF THIS CODE. IF THE EXISTING BUILDING WAS CONSTRUCTED
 PRIOR TO THE ADOPTION OF EITHER THE SITE STANDARDS OF
 SECTION 449.4 OF THIS CODE OR LOCAL FLOOD-RESISTANT
 REQUIREMENTS, THEN THE ADDITION AND ALL PATIENT SUPPORT
 AREAS AND UTILITIES FOR THE ADDITION AS DESCRIBED IN
 THIS SECTION SHALL EITHER BE DESIGNED AND CONSTRUCTED
 TO MEET THE REQUIREMENTS OF SECTION 449.4.2.2.1 OF THIS
 CODE OR BE DESIGNED AND CONSTRUCTED TO MEET THE DRY
 FLOOD PROOFING REQUIREMENTS OF SECTION 1612 OF THIS
 CODE.
 449.4.2.2.3 SUBSTANTIAL IMPROVEMENT, AS DEFINED BY
 SECTION 1612 OF THIS CODE, TO ALL EXISTING FACILITIES
 LOCATED WITHIN FLOOD AREAS AS DEFINED IN SECTION 1612
 OF THIS CODE OR WITHIN A CATEGORY 3 SURGE INUNDATION
 ZONE AS DESCRIBED IN SECTION 449.4.2.2.1 OF THIS CODE,
 SHALL BE DESIGNED AND CONSTRUCTED IN COMPLIANCE WITH
 SECTION 1612 OF THIS CODE.
 PLEASE PROVIDE A COST ANALYSIS TO SEE IF THE
 SUBSTANTIAL REQUIREMENT IS OR IS NOT MET, AN EXAMPLE IS
 UNDER PERMIT 16110246.
  
 4D) HAVE YOU RECEIVED A LOMAR REMOVING THESE AREAS FROM
 THE FLOOD ZONE?
  
 5) SHEET 002_G100:
  
 5A) UNDER THE CONSTRUCTION TYPE THE BUILDING IS LISTED
 AS OCCUPANCY I-2 INSTITUTIONAL FULLY SPRINKLERED, TYPE
 II-B CONSTRUCTION. UNDER THE ALLOWABLE HEIGHT THE PLANS
 STATE 5 AND AREA UNLIMITED. PROPOSED AREA, EXISTING
 AREA THE PLANS DO NOT STATE THE AREA FOR EITHER
 BUILDING A OR BUILDING C? NOR DOES THE PLAN STATE THE
 AREA FOR EACH ADDITION INDIVIDUALLY FOR EACH BUILDING.
 IT WOULD APPEAR THAT THE VALUES FOR HEIGHT AND AREA
 WERE TAKEN AS FOR TYPE I-B CONSTRUCTION TYPE. SEE THE
 2017 FBC-B TABLES 504.4 & 506.2.
  
 5B) THE PLANS DO NOT STATE IF THE SQUARE FOOTAGE IS FOR
 BUILDINGS A & C OR IF THE SQUARE FOOTAGE IS FOR
 BUILDINGS A, B, C, AND PAVILION 4? BUILDING B IS
 BETWEEN A & C?
  
 FBC-B SECTION 503.1.2 BUILDINGS ON SAME LOT. TWO OR
 MORE BUILDINGS ON THE SAME LOT SHALL BE REGULATED AS
 SEPARATE BUILDINGS OR SHALL BE CONSIDERED AS PORTIONS
 OF ONE BUILDING WHERE THE BUILDING HEIGHT, NUMBER OF
 STORIES OF EACH BUILDING AND THE AGGREGATE BUILDING
 AREA OF THE BUILDINGS ARE WITHIN THE LIMITATIONS
 SPECIFIED IN SECTIONS 504 AND 506. THE PROVISIONS OF
 THIS CODE APPLICABLE TO THE AGGREGATE BUILDING SHALL BE
 APPLICABLE TO EACH BUILDING.
  
 5C) WITH THE NEW ADDITION TO BUILDING A, THE PLANS ARE
 SILENT AS TO INDIVIDUAL BUILDINGS NOT CONSIDERED AS
 ONE, THEN THERE SHOULD BE A PROPOSED IMAGINARY PROPERTY
 LINE BETWEEN BUILDINGS A & C AND DISTANCE BETWEEN THIS
 IMAGINARY PROPERTY LINE FOR WALL RATINGS AND ALLOWABLE
 SQ. FT. OF WALL OPENINGS. SEE TABLE 602 AND 705.8. NONE
 OF THESE THINGS APPEAR TO BE CONSIDERED, ONLY TABLE
 601. THERE IS A FOOTNOTE A NOTING A REDUCTION OF 1 HOUR
 FOR STRUCTURAL FRAME, BEARING WALLS AND REDUCTION OF
 ROOF WHERE ONLY SUPPORTING ROOF THIS IS FOUND ONLY IN
 TYPE I-A AND I-B CONSTRUCTION NOT II-B. THE OTHER ISSUE
 IS UNDER 603.1.1 WHERE FIRE RETARDANT TREATED WOOD CAN
 BE USED.
  
 6) SHEET 076_S001 IN THE STRUCTURAL NOTES IN THE WIND
 DESIGN DATA THE EXPOSURE IS GIVEN AS A B EXPOSURE. IT
 WOULD APPEAR THAT TO THE NORTHEAST AND NORTHWEST THERE
 ARE C EXPOSURES SINCE MOST OF THESE AREAS HAVE LITTLE
 OR NO BUILDINGS, THEY ARE GRASSLANDS, OPEN LAKES,
 CANALS, PARKING LOTS AND HIGHWAYS.
 2017 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES. A
 GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE SECTOR
 SHALL BE DETERMINED FOR A DISTANCE UPWIND OF THE SITE
 AS DEFINED IN SECTION 1609.4.3 FROM THE CATEGORIES
 DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING AN EXPOSURE
 CATEGORY AS DEFINED IN SECTION 1609.4.3.
 SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED
 OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30
 FEET. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, AND
 GRASSLANDS.
  
 7) SINCE THE EXPOSURE WOULD BE A C EXPOSURE FOR 179
 VASD THE PRESSURES WILL INCREASE FOR THE MULTIPLIER FOR
 THE HEIGHT OF THE BUILDING FOR THE EXPOSURE C. SEE
 TABLE 1609.7(2).
  
 8) PLEASE ALSO NOTE ON SHEET 076_S001 UNDER THE HEADING
 2.4.1 EXTERIOR COMPONENTS & CLADDING
 THE COLUMN OF PRESSURES FOR CORNERS WALL ZONE 5 THE
 NEGATIVE PRESSURES FOR 20 SQ. FT. AND 100 SQ. FT. ARE
 THE SAME AND THE PRESSURES FOR 50 SQ. FT. ARE HIGHER
 THAN FOR THE 20 SQ. FT. IT WOULD APPEAR THIS IS A TYPO,
 PLEASE PROVIDE ADDITIONAL INFORMATION, PLEASE.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 9A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT
 CONCRETE INSULATION, ROOF TOP VENTILATORS & CURBS
  
 9B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 10) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 11) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES
 FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL
 LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF
 ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR
 BOTH INSULATION & THE BASE SHEET AS CALCULATED IN
 COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117.
 CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 12) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL
 FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE
 MANUFACTURERS INSTALLATION BROCHURE PROVIDING
 COMPLIANCE WITH 2014 FBC-B SECTIONS;
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.2 PERFORMANCE CHARACTERISTICS.
 1408.3 STRUCTURAL DESIGN.
 1408.4 WEATHER RESISTANCE.
 1408.4.1 EIFS WITH DRAINAGE.
 408.4.1.1 WATER-RESISTIVE BARRIER.
 1408.5 INSTALLATION
  
 13) IF EITHER THE CONTRACTOR OR DESIGN PROFESSIONAL
 WOULD LIKE TO SUBMIT THE PRODUCT APPROVALS AFTER PERMIT
 ISSUANCE PLEASE NOTE SO ON THE PLANS AS A DEFERRED
 SUBMITTAL.
  
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) SHEET 076_S001 UNDER THE HEADING OF FOUNDATION AND
 THE GEOTECHNICAL REPORT IT DOES NOT INDICATE A REPORT
 NUMBER NOR UNDER THE SOIL BEARING CAPACITY FOR ISOLATED
 FOOTING OR CONTINUOUS FOOTING THE PSF IS LEFT BLANK.
 PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION:
  
 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION,
 STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR
 WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED
 IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE
 PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION
 BE CONDUCTED.
  
 15) SHEET055_A475 SHOWS A GABLE ROOF STEEL BEAM STEEL
 FRAMING MEMBERS, RAFTERS STEEL DECKING AND EXTERIOR
 GRADE PLYWOOD DECKING. THERE IS NO MENTION OF THE
 PLYWOOD DECKING BEING REQUIRED TO BE FIRE RETARDANT
 TREATED WOOD, SEE 2017 FBC-B SECTION 603.1.1.3 ROOF
 CONSTRUCTION.
  
 16) SHEET055_A475 SHOWS STEEL BEAM WITH SPRAY APPLIED
 FIRE PROOFING TO THE HORIZONTAL STEEL BEAM BUT THERE IS
 NO NOTE TO THE STEEL ROOF FRAMING MEMBERS NOR THE
 UNDERSIDE OF THE STEEL ROOF DECKING. DEPENDING ON IF
 THIS IS TO BE CONSIDERED CONSTRUCTION I-B OR II-B IF
 THIS IS A CODE REQUIREMENT? 107.2.1.2 ADDITIONAL
 INFORMATION IS REQUIRED. WHAT TYPE OF CONSTRUCTION ARE
 THE 2 ORIGINAL BUILDINGS BUILT AS? WOULD A FIREWALL BE
 REQUIRED TO SEPARATE THE DIFFERENT BUILDING TYPES?
  
 17) SHEET055_A475 SHOWS A DETAIL 3/ A351. PLEASE NOTE
 THERE IS AREAS OF SUB-SHEATHING THAT ARE NOT IDENTIFIED
 AS TO THE MATERIAL, THERE ARE OTHER AREAS THAT INDICATE
 THE USE OF ? INCH EXTERIOR GRADE PLYWOOD. SEE 2017
 FBC-B SECTION 603.1.1.3 ROOF CONSTRUCTION. PLEASE NOTE
 THERE ARE OTHER SHEETS THAT EITHER STATE THE USE OF
 PLYWOOD OR NOT MENTIONING THE SUB-STRATE, THIS NOTE
 COUNTS FOR ALL.
  
 18) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR ON
 THE PROJECT AS LONG AS THERE IS STRUCTURAL STEEL BOLTED
 OR WELDED CONNECTIONS BAR JOIST AND THE STEEL ROOF DECK
 ANCHORING BY WELDS OR BOLTED CONNECTIONS.
 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 110.3.9. OTHER
 INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE,
 OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED
 BY SECTION 109 110. HE/SHE MAY ACCEPT REPORTS OF
 INSPECTORS OF RECOGNIZED INSPECTION SERVICES, PROVIDED
 THAT AFTER INVESTIGATION HE/SHE IS SATISFIED AS TO
 THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE
 CALLED FOR BY ANY PROVISION OF THE TECHNICAL CODES
 SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE SAME ARE
 IN WRITING AND CERTIFIED BY A RESPONSIBLE OFFICER OF
 SUCH SERVICE. THE BUILDING OFFICIAL MAY REQUIRE THE
 OWNER TO EMPLOY AN INSPECTION SERVICE IN THE FOLLOWING
 INSTANCES:
 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS
 3) WELDING AND BOLTED CONNECTIONS
 FORMS ARE TO BE E-MAILED TO: [email protected] SENT
 AT3/26/2019 @ 06:25 AM.
  
 19A) NEITHER SHEET 083_S201 NOR 084_S202 SHOW
 COMPLIANCE WITH UNDERGROUND TERMITE PROTECTION 1816.1
 OF THE 2017 FBC-B FOR THE NEW WORK OR TRENCHES CUT
 THROUGH THE SLAB.
  
 19B) NEITHER SHEET 083_S201 NOR 084_S202 SHOW
 COMPLIANCE WITH 1805.2.1 DAMP-PROOFING OF SLABS. WHERE
 INSTALLED BENEATH THE SLAB, DAMP-PROOFING SHALL CONSIST
 OF NOT LESS THAN 6-MIL (0.006 INCH) POLYETHYLENE WITH
 JOINTS LAPPED NOT LESS THAN 6 INCHES (152 MM), OR OTHER
 APPROVED METHODS OR MATERIALS.
  
 20) SHEET 065_A800 IN THE UPPER LEFT HAND CORNER OF THE
 SHEET DETAIL NOT LABELED BUT IT APPEARS TO BE A BREAK
 AREA WITH A MICROWAVE ON A SHELF IN THE UPPER CABINETS
 THE BOTTOM OF THE SHELF THE MICROWAVE SITS ON IS AT AN
 ELEVATION OF 4 FOOT 8 INCHES ABOVE THE FLOOR OUT OF
 REACH RANGES AND OPERABLE PARTS OF THE ACCESSIBILITY
 CODE.
  
 20A) 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 20B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS.
  
 21) SHEET 062_A610 DETAILS 4 & 6 BOTH SHOW DOORS IN
 SERIES BUT NOT THE 4 FOOT CLEAR BETWEEN DOORS REQUIRED
 BY THE 2017 FBC-ACCESSIBILITY CODE SECTION 404.2.6. THE
 CODE DOES NOT GIVE ANY EXCEPTIONS, ARE YOU APPLYING TO
 THE STATE FOR A WAIVER?
  
 22) IMPACT FEES - DIGITAL SUBMITTALS:
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
 PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300
 N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL.
  
 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  