Date |
Text |
2019-03-26 08:11:39 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18120436 |
| ADD: 2201 45TH ST. |
| CONT: DPR CONSTRUCTION |
| TEL: 954-991-6200 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. MARCH 18/THROUGH TUES. MARCH 26/ 2019 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE WITHIN THE DOCUMENT FOLDER THE PROJECT |
| MANUAL CONSISTING OF 179 PAGES WAS LOADED AS INDIVIDUAL |
| PAGES, THIS IS INCORRECT, IT SHOULD BE LOADED AS A |
| SINGLE DOCUMENT WITH THE FOLDER LABELED PROJECT MANUAL. |
| YOU WILL NEED TO SPEAK WITH CAROLINE PUELL PLAN REVIEW |
| LIBRARIAN (TELL: 561-805-6659) AS TO HOW TO CORRECT |
| THIS MATTER. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1 ADMINISTRATION 107.2.1.3 QUALITY OF |
| BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH |
| THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS |
| AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO |
| ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE |
| SUCH THINGS, CLARITY, OR OTHER ITEMS RELATED TO RECORDS |
| MANAGEMENT. ELECTRONIC MEDIA MUST BE COMPATIBLE WITH |
| THE ARCHIVE REQUIREMENTS OF FLORIDA STATUTES. |
| |
| 2) ART IN PUBLIC PLACES |
| THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| DEVELOPMENT. |
| (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected] |
| |
| 3) SHEET 014_G201 OVERALL PROPOSED FIRST FLOOR PLAN: |
| |
| 3A) PLEASE NOTE FOR THIS REVIEW THE NORTH BUILDING THE |
| CHILDREN?S BEHAVIOR UNIT WILL BE KNOWN AS BUILDING A, |
| THE BUILDING JUST TO THE SOUTH BUILDING B AND THE |
| BUILDING HOUSING THE ADULT BEHAVIOR UNIT AND ADDITION |
| AS BUILDING C. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE (IDENTIFY BUILDINGS)THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED. |
| |
| 3B) SINCE THE SCOPE OF WORK IS IN (2) BUILDINGS, IN (2) |
| LOCATIONS AND FOR TRACKING PURPOSES (INSPECTIONS) |
| THIS PERMIT SHOULD BE BROKEN DOWN INTO (2) SEPARATE |
| PERMITS WITH SEPARATE IDENTITIES,( EXAMPLE BUILDING A |
| OR BUILDING C), PLEASE ALSO SPLIT THE VALUE OF THE |
| PERMIT APPLICATION ACCORDINGLY. UNDER THE 16110246 |
| PERMIT THE BUILDINGS WERE IDENTIFIED AS PAVILIONS, |
| (EXAMPLE GYM: PAVILION 4). THE WHOLE CAMPUS IS LISTED |
| UNDER 2201 45TH ST. THE BUILDINGS HAVE NO IDENTIFIERS, |
| THIS WOULD BE A GREAT HELP FOR ADDRESSING OF THE |
| CAMPUS. |
| 2017 FBC-B 501.2 ADDRESS IDENTIFICATION. NEW AND |
| EXISTING BUILDINGS SHALL BE PROVIDED WITH APPROVED |
| ADDRESS IDENTIFICATION. |
| |
| CITY MUNI CODE SEC.78-6 (1-7) (2) LOCATION, BUILDINGS |
| CONTAINING MORE THAN ONE ADDRESS. ALL ADDRESSES SHALL |
| BE POSTED ON THAT PORTION OF THE STRUCTURE FRONTING OR |
| FACING UPON THE STREET OR PRINCIPAL VEHICULAR ACCESS TO |
| THE PREMISES, SO AS TO BE READILY VISIBLE TO |
| APPROACHING VEHICLES. |
| |
| 4A) THE SUBMITTED PLANS HAVE CIVIL PLANS, SITE PLANS |
| AND ENGINEERING PLANS AS PART OF THE PACKAGE BUT THERE |
| IS NO SURVEY IN THIS SET OF PLANS. PLEASE SUBMIT A |
| SURVEY WITH THE AE FLOOD ZONE SHOWN ON THE SURVEY THE |
| EXISTING NORTH BUILDING. THE EXISTING BUILDING IS NOT |
| IN THE FLOOD ZONE BUT THE PROPOSED ADDITION IS IN THE |
| AE FLOOD ZONE. |
| |
| 4B) THE SUBMITTED PLANS HAVE CIVIL PLANS, SITE PLANS |
| AND ENGINEERING PLANS AS PART OF THE PACKAGE BUT THERE |
| IS NO SURVEY IN THIS SET OF PLANS. PLEASE SUBMIT A |
| SURVEY WITH THE AE FLOOD ZONE SHOWN ON THE SURVEY THE |
| EXISTING SOUTH BUILDING. THE EXISTING BUILDING IS NOT |
| IN THE FLOOD ZONE BUT THE PROPOSED ADDITION MAYBE IN |
| THE AE FLOOD ZONE. |
| |
| 4C) PLEASE NOTE SINCE THE CITY CANNOT DETERMINE WHEN |
| THESE BUILDINGS WERE BUILT, IF THE ORIGINAL BUILDINGS |
| BOTH A & C ARE PRE-FIRM OR POST-FIRM OR IF THE ADDITION |
| WILL MEET THE REQUIREMENTS FOR SUBSTANTIAL IMPROVEMENT |
| A CONCISE CODE ANALYSIS FOR THE FLOOD REQUIREMENTS |
| CANNOT BE DETERMINED. |
| |
| 4C)(1) IN BOTH CASES IF THE EXISTING BUILDINGS (A & |
| C)ARE EITHER PRE OR POST FIRM AND THE ADDITION |
| (STRUCTURALLY CONNECTED) ARE NOT A SUBSTANTIAL |
| IMPROVEMENT THEN THE ADDITION IS REQUIRED TO BE |
| ELEVATED TO AT LEAST THE ELEVATION OF THE EXISTING |
| FLOOR. TAKEN FROM SI/SD DESK REFERENCE. |
| |
| 4C)(2) UNDER THE 2017 EXIST. BUILDING CODE SECTION |
| 1103.5 APPLIES: |
| BS]1103.5 FLOOD HAZARD AREAS. ADDITIONS AND FOUNDATIONS |
| IN FLOOD HAZARD AREAS SHALL COMPLY WITH THE FOLLOWING |
| REQUIREMENTS: |
| 1.FOR HORIZONTAL ADDITIONS THAT ARE STRUCTURALLY |
| INTERCONNECTED TO THE EXISTING BUILDING: |
| |
| 1.1. (BUILDING C.) IF THE ADDITION AND ALL OTHER |
| PROPOSED WORK, WHEN COMBINED, CONSTITUTE SUBSTANTIAL |
| IMPROVEMENT, THE EXISTING BUILDING AND THE ADDITION |
| SHALL COMPLY WITH SECTION 1612 OF THE FLORIDA BUILDING |
| CODE, BUILDING. |
| |
| 1.2. (BUILDING A). IF THE ADDITION CONSTITUTES |
| SUBSTANTIAL IMPROVEMENT, THE EXISTING BUILDING AND THE |
| ADDITION SHALL COMPLY WITH SECTION 1612 OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| IF EITHER OF THE BUILDINGS (A OR C) MEET THE |
| REQUIREMENTS FOR SUBSTANTIAL IMPROVEMENTS THEN UNDER |
| THE 2017 FBC-B 1612 FLOOD LOADS TABLE 1612.1 SECTION |
| 449 HOSPITALS. |
| |
| 449.4.2.2.2 FOR ALL EXISTING FACILITIES, THE LOWEST |
| FLOOR ELEVATIONS OF ALL ADDITIONS, AND ALL PATIENT |
| SUPPORT AREAS INCLUDING FOOD SERVICE, AND ALL PATIENT |
| SUPPORT UTILITIES, INCLUDING MECHANICAL, AND ELECTRICAL |
| (EXCEPT FUEL STORAGE AS NOTED IN SECTION 449.4.2.9.3 OF |
| THIS CODE) FOR THE ADDITIONS SHALL BE AT OR ABOVE THE |
| ELEVATION OF THE EXISTING BUILDING, IF THE EXISTING |
| BUILDING WAS DESIGNED AND CONSTRUCTED TO COMPLY WITH |
| EITHER THE SITE STANDARDS OF SECTION 449.4 OF THIS CODE |
| OR LOCAL FLOOD-RESISTANT REQUIREMENTS, IN EFFECT AT THE |
| TIME OF CONSTRUCTION, WHICHEVER REQUIRES THE HIGHER |
| ELEVATION, UNLESS OTHERWISE PERMITTED BY SECTION 1612 |
| OF THIS CODE. IF THE EXISTING BUILDING WAS CONSTRUCTED |
| PRIOR TO THE ADOPTION OF EITHER THE SITE STANDARDS OF |
| SECTION 449.4 OF THIS CODE OR LOCAL FLOOD-RESISTANT |
| REQUIREMENTS, THEN THE ADDITION AND ALL PATIENT SUPPORT |
| AREAS AND UTILITIES FOR THE ADDITION AS DESCRIBED IN |
| THIS SECTION SHALL EITHER BE DESIGNED AND CONSTRUCTED |
| TO MEET THE REQUIREMENTS OF SECTION 449.4.2.2.1 OF THIS |
| CODE OR BE DESIGNED AND CONSTRUCTED TO MEET THE DRY |
| FLOOD PROOFING REQUIREMENTS OF SECTION 1612 OF THIS |
| CODE. |
| 449.4.2.2.3 SUBSTANTIAL IMPROVEMENT, AS DEFINED BY |
| SECTION 1612 OF THIS CODE, TO ALL EXISTING FACILITIES |
| LOCATED WITHIN FLOOD AREAS AS DEFINED IN SECTION 1612 |
| OF THIS CODE OR WITHIN A CATEGORY 3 SURGE INUNDATION |
| ZONE AS DESCRIBED IN SECTION 449.4.2.2.1 OF THIS CODE, |
| SHALL BE DESIGNED AND CONSTRUCTED IN COMPLIANCE WITH |
| SECTION 1612 OF THIS CODE. |
| PLEASE PROVIDE A COST ANALYSIS TO SEE IF THE |
| SUBSTANTIAL REQUIREMENT IS OR IS NOT MET, AN EXAMPLE IS |
| UNDER PERMIT 16110246. |
| |
| 4D) HAVE YOU RECEIVED A LOMAR REMOVING THESE AREAS FROM |
| THE FLOOD ZONE? |
| |
| 5) SHEET 002_G100: |
| |
| 5A) UNDER THE CONSTRUCTION TYPE THE BUILDING IS LISTED |
| AS OCCUPANCY I-2 INSTITUTIONAL FULLY SPRINKLERED, TYPE |
| II-B CONSTRUCTION. UNDER THE ALLOWABLE HEIGHT THE PLANS |
| STATE 5 AND AREA UNLIMITED. PROPOSED AREA, EXISTING |
| AREA THE PLANS DO NOT STATE THE AREA FOR EITHER |
| BUILDING A OR BUILDING C? NOR DOES THE PLAN STATE THE |
| AREA FOR EACH ADDITION INDIVIDUALLY FOR EACH BUILDING. |
| IT WOULD APPEAR THAT THE VALUES FOR HEIGHT AND AREA |
| WERE TAKEN AS FOR TYPE I-B CONSTRUCTION TYPE. SEE THE |
| 2017 FBC-B TABLES 504.4 & 506.2. |
| |
| 5B) THE PLANS DO NOT STATE IF THE SQUARE FOOTAGE IS FOR |
| BUILDINGS A & C OR IF THE SQUARE FOOTAGE IS FOR |
| BUILDINGS A, B, C, AND PAVILION 4? BUILDING B IS |
| BETWEEN A & C? |
| |
| FBC-B SECTION 503.1.2 BUILDINGS ON SAME LOT. TWO OR |
| MORE BUILDINGS ON THE SAME LOT SHALL BE REGULATED AS |
| SEPARATE BUILDINGS OR SHALL BE CONSIDERED AS PORTIONS |
| OF ONE BUILDING WHERE THE BUILDING HEIGHT, NUMBER OF |
| STORIES OF EACH BUILDING AND THE AGGREGATE BUILDING |
| AREA OF THE BUILDINGS ARE WITHIN THE LIMITATIONS |
| SPECIFIED IN SECTIONS 504 AND 506. THE PROVISIONS OF |
| THIS CODE APPLICABLE TO THE AGGREGATE BUILDING SHALL BE |
| APPLICABLE TO EACH BUILDING. |
| |
| 5C) WITH THE NEW ADDITION TO BUILDING A, THE PLANS ARE |
| SILENT AS TO INDIVIDUAL BUILDINGS NOT CONSIDERED AS |
| ONE, THEN THERE SHOULD BE A PROPOSED IMAGINARY PROPERTY |
| LINE BETWEEN BUILDINGS A & C AND DISTANCE BETWEEN THIS |
| IMAGINARY PROPERTY LINE FOR WALL RATINGS AND ALLOWABLE |
| SQ. FT. OF WALL OPENINGS. SEE TABLE 602 AND 705.8. NONE |
| OF THESE THINGS APPEAR TO BE CONSIDERED, ONLY TABLE |
| 601. THERE IS A FOOTNOTE A NOTING A REDUCTION OF 1 HOUR |
| FOR STRUCTURAL FRAME, BEARING WALLS AND REDUCTION OF |
| ROOF WHERE ONLY SUPPORTING ROOF THIS IS FOUND ONLY IN |
| TYPE I-A AND I-B CONSTRUCTION NOT II-B. THE OTHER ISSUE |
| IS UNDER 603.1.1 WHERE FIRE RETARDANT TREATED WOOD CAN |
| BE USED. |
| |
| 6) SHEET 076_S001 IN THE STRUCTURAL NOTES IN THE WIND |
| DESIGN DATA THE EXPOSURE IS GIVEN AS A B EXPOSURE. IT |
| WOULD APPEAR THAT TO THE NORTHEAST AND NORTHWEST THERE |
| ARE C EXPOSURES SINCE MOST OF THESE AREAS HAVE LITTLE |
| OR NO BUILDINGS, THEY ARE GRASSLANDS, OPEN LAKES, |
| CANALS, PARKING LOTS AND HIGHWAYS. |
| 2017 FBC-B 1609.4.2 SURFACE ROUGHNESS CATEGORIES. A |
| GROUND SURFACE ROUGHNESS WITHIN EACH 45-DEGREE SECTOR |
| SHALL BE DETERMINED FOR A DISTANCE UPWIND OF THE SITE |
| AS DEFINED IN SECTION 1609.4.3 FROM THE CATEGORIES |
| DEFINED BELOW, FOR THE PURPOSE OF ASSIGNING AN EXPOSURE |
| CATEGORY AS DEFINED IN SECTION 1609.4.3. |
| SURFACE ROUGHNESS C. OPEN TERRAIN WITH SCATTERED |
| OBSTRUCTIONS HAVING HEIGHTS GENERALLY LESS THAN 30 |
| FEET. THIS CATEGORY INCLUDES FLAT OPEN COUNTRY, AND |
| GRASSLANDS. |
| |
| 7) SINCE THE EXPOSURE WOULD BE A C EXPOSURE FOR 179 |
| VASD THE PRESSURES WILL INCREASE FOR THE MULTIPLIER FOR |
| THE HEIGHT OF THE BUILDING FOR THE EXPOSURE C. SEE |
| TABLE 1609.7(2). |
| |
| 8) PLEASE ALSO NOTE ON SHEET 076_S001 UNDER THE HEADING |
| 2.4.1 EXTERIOR COMPONENTS & CLADDING |
| THE COLUMN OF PRESSURES FOR CORNERS WALL ZONE 5 THE |
| NEGATIVE PRESSURES FOR 20 SQ. FT. AND 100 SQ. FT. ARE |
| THE SAME AND THE PRESSURES FOR 50 SQ. FT. ARE HIGHER |
| THAN FOR THE 20 SQ. FT. IT WOULD APPEAR THIS IS A TYPO, |
| PLEASE PROVIDE ADDITIONAL INFORMATION, PLEASE. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| 9A) 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES. |
| (B) WINDOWS & MULLIONS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, EFIS SYSTEMS, |
| (D) ROOFING PRODUCTS AND ASSEMBLIES, LIGHTWEIGHT |
| CONCRETE INSULATION, ROOF TOP VENTILATORS & CURBS |
| |
| 9B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 10) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 11) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY |
| ALL ROOFING SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES |
| FOR ROOF ZONE # 1. REVIEW THE PRODUCT APPROVAL |
| LIMITATIONS, IF ENHANCED FASTENING IS ALLOWED FOR ROOF |
| ZONES 2 & 3. FASTENER DENSITIES SHALL BE INCREASED FOR |
| BOTH INSULATION & THE BASE SHEET AS CALCULATED IN |
| COMPLIANCE WITH ROOFING APPLICATION STANDARDS RAS 117. |
| CALCULATION PREPARED, SIGNED AND |
| SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR |
| REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS & |
| CLADDING. |
| |
| 12) EFIS SYSTEMS: PLEASE PROVIDE THE PRODUCT APPROVAL |
| FOR THE SYSTEM TO BE INSTALLED. PLEASE ALSO PROVIDE THE |
| MANUFACTURERS INSTALLATION BROCHURE PROVIDING |
| COMPLIANCE WITH 2014 FBC-B SECTIONS; |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.2 PERFORMANCE CHARACTERISTICS. |
| 1408.3 STRUCTURAL DESIGN. |
| 1408.4 WEATHER RESISTANCE. |
| 1408.4.1 EIFS WITH DRAINAGE. |
| 408.4.1.1 WATER-RESISTIVE BARRIER. |
| 1408.5 INSTALLATION |
| |
| 13) IF EITHER THE CONTRACTOR OR DESIGN PROFESSIONAL |
| WOULD LIKE TO SUBMIT THE PRODUCT APPROVALS AFTER PERMIT |
| ISSUANCE PLEASE NOTE SO ON THE PLANS AS A DEFERRED |
| SUBMITTAL. |
| |
| 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 14) SHEET 076_S001 UNDER THE HEADING OF FOUNDATION AND |
| THE GEOTECHNICAL REPORT IT DOES NOT INDICATE A REPORT |
| NUMBER NOR UNDER THE SOIL BEARING CAPACITY FOR ISOLATED |
| FOOTING OR CONTINUOUS FOOTING THE PSF IS LEFT BLANK. |
| PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B SECTION: |
| |
| 1803.5.2 QUESTIONABLE SOIL. WHERE THE CLASSIFICATION, |
| STRENGTH OR COMPRESSIBILITY OF THE SOIL IS IN DOUBT OR |
| WHERE A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED |
| IN THIS CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL BE |
| PERMITTED TO REQUIRE THAT A GEOTECHNICAL INVESTIGATION |
| BE CONDUCTED. |
| |
| 15) SHEET055_A475 SHOWS A GABLE ROOF STEEL BEAM STEEL |
| FRAMING MEMBERS, RAFTERS STEEL DECKING AND EXTERIOR |
| GRADE PLYWOOD DECKING. THERE IS NO MENTION OF THE |
| PLYWOOD DECKING BEING REQUIRED TO BE FIRE RETARDANT |
| TREATED WOOD, SEE 2017 FBC-B SECTION 603.1.1.3 ROOF |
| CONSTRUCTION. |
| |
| 16) SHEET055_A475 SHOWS STEEL BEAM WITH SPRAY APPLIED |
| FIRE PROOFING TO THE HORIZONTAL STEEL BEAM BUT THERE IS |
| NO NOTE TO THE STEEL ROOF FRAMING MEMBERS NOR THE |
| UNDERSIDE OF THE STEEL ROOF DECKING. DEPENDING ON IF |
| THIS IS TO BE CONSIDERED CONSTRUCTION I-B OR II-B IF |
| THIS IS A CODE REQUIREMENT? 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. WHAT TYPE OF CONSTRUCTION ARE |
| THE 2 ORIGINAL BUILDINGS BUILT AS? WOULD A FIREWALL BE |
| REQUIRED TO SEPARATE THE DIFFERENT BUILDING TYPES? |
| |
| 17) SHEET055_A475 SHOWS A DETAIL 3/ A351. PLEASE NOTE |
| THERE IS AREAS OF SUB-SHEATHING THAT ARE NOT IDENTIFIED |
| AS TO THE MATERIAL, THERE ARE OTHER AREAS THAT INDICATE |
| THE USE OF ? INCH EXTERIOR GRADE PLYWOOD. SEE 2017 |
| FBC-B SECTION 603.1.1.3 ROOF CONSTRUCTION. PLEASE NOTE |
| THERE ARE OTHER SHEETS THAT EITHER STATE THE USE OF |
| PLYWOOD OR NOT MENTIONING THE SUB-STRATE, THIS NOTE |
| COUNTS FOR ALL. |
| |
| 18) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR ON |
| THE PROJECT AS LONG AS THERE IS STRUCTURAL STEEL BOLTED |
| OR WELDED CONNECTIONS BAR JOIST AND THE STEEL ROOF DECK |
| ANCHORING BY WELDS OR BOLTED CONNECTIONS. |
| 2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION 110.3.9. OTHER |
| INSPECTIONS SERVICES. THE BUILDING OFFICIAL MAY MAKE, |
| OR CAUSE TO BE MADE BY OTHERS, THE INSPECTIONS REQUIRED |
| BY SECTION 109 110. HE/SHE MAY ACCEPT REPORTS OF |
| INSPECTORS OF RECOGNIZED INSPECTION SERVICES, PROVIDED |
| THAT AFTER INVESTIGATION HE/SHE IS SATISFIED AS TO |
| THEIR QUALIFICATIONS AND RELIABILITY. A CERTIFICATE |
| CALLED FOR BY ANY PROVISION OF THE TECHNICAL CODES |
| SHALL NOT BE BASED ON SUCH REPORTS UNLESS THE SAME ARE |
| IN WRITING AND CERTIFIED BY A RESPONSIBLE OFFICER OF |
| SUCH SERVICE. THE BUILDING OFFICIAL MAY REQUIRE THE |
| OWNER TO EMPLOY AN INSPECTION SERVICE IN THE FOLLOWING |
| INSTANCES: |
| 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| CONSTRUCTION |
| 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| 3) WELDING AND BOLTED CONNECTIONS |
| FORMS ARE TO BE E-MAILED TO: [email protected] SENT |
| AT3/26/2019 @ 06:25 AM. |
| |
| 19A) NEITHER SHEET 083_S201 NOR 084_S202 SHOW |
| COMPLIANCE WITH UNDERGROUND TERMITE PROTECTION 1816.1 |
| OF THE 2017 FBC-B FOR THE NEW WORK OR TRENCHES CUT |
| THROUGH THE SLAB. |
| |
| 19B) NEITHER SHEET 083_S201 NOR 084_S202 SHOW |
| COMPLIANCE WITH 1805.2.1 DAMP-PROOFING OF SLABS. WHERE |
| INSTALLED BENEATH THE SLAB, DAMP-PROOFING SHALL CONSIST |
| OF NOT LESS THAN 6-MIL (0.006 INCH) POLYETHYLENE WITH |
| JOINTS LAPPED NOT LESS THAN 6 INCHES (152 MM), OR OTHER |
| APPROVED METHODS OR MATERIALS. |
| |
| 20) SHEET 065_A800 IN THE UPPER LEFT HAND CORNER OF THE |
| SHEET DETAIL NOT LABELED BUT IT APPEARS TO BE A BREAK |
| AREA WITH A MICROWAVE ON A SHELF IN THE UPPER CABINETS |
| THE BOTTOM OF THE SHELF THE MICROWAVE SITS ON IS AT AN |
| ELEVATION OF 4 FOOT 8 INCHES ABOVE THE FLOOR OUT OF |
| REACH RANGES AND OPERABLE PARTS OF THE ACCESSIBILITY |
| CODE. |
| |
| 20A) 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1 |
| UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH. |
| 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 |
| OBSTRUCTED HIGH REACH. |
| |
| 20B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS |
| SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES |
| SPECIFIED IN 308.309.4 OPERATION. OPERABLE PARTS SHALL |
| BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT |
| GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE |
| REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS. |
| |
| 21) SHEET 062_A610 DETAILS 4 & 6 BOTH SHOW DOORS IN |
| SERIES BUT NOT THE 4 FOOT CLEAR BETWEEN DOORS REQUIRED |
| BY THE 2017 FBC-ACCESSIBILITY CODE SECTION 404.2.6. THE |
| CODE DOES NOT GIVE ANY EXCEPTIONS, ARE YOU APPLYING TO |
| THE STATE FOR A WAIVER? |
| |
| 22) IMPACT FEES - DIGITAL SUBMITTALS: |
| PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS |
| OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] . |
| PALM BEACH COUNTY IMPACT FEE OFFICE IS LOCATED AT 2300 |
| N. JOG RD. ROOM?S 2W01-2W14 WEST PALM BEACH, FL. |
| |
| 23) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER BN, PX, SFP, CBO |