2018-12-14 19:31:58 | 12/14/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. GAS RISER DIAGRAM REQUIRED WPB AMENDMENTS TO THE FBC |
| SEC. 107.3.5.3 (12) RESIDENTIAL GAS |
| 2. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON |
| PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION |
| ON CONSTRUCTION DOCUMENTS. |
| 3. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER 2017 FBC FUEL |
| GAS RES SECS. G2413.4.1, G2413.4.2. |
| 4. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER 2017 FBC FUEL GAS RES. SEC. G2413.2. |
| 5. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC FUEL GAS |
| RES. SEC. G2413. |
| 6. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 7. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE |
| FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 8. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2017 FBC |
| FUEL GAS RES. SEC. G2413.4.1. |
| 9. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. 2017 FBC FUEL GAS RES. SEC. |
| G2420.4. |
| 10. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS RES. |
| SECS. G2426 THRU G2429.1 |
| 11. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL. |
| FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| 12. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| THE GAS CODE OR ANOTHER STANDARD THAT WAS USED IN THE |
| DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC FUEL |
| GAS RES. SEC. G2412.4, G2412.8, G2413.1, G2413.2, & |
| G2413.3. |
| 13. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS RES. SEC. G2421.1. |
| 14. SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| DRAWN. WPB AMENDMENTS TO THE FBC SEC. 107.2.1. |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 15. TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE |
| THE COST OF ALL EQUIPMENT INCLUDING TANKLESS AND STOVE. |
| WPB AMENDMENTS TO THE FBC 109.3 |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| LUIS A. CRESPO |
| PLUMBING INSPECTOR / |
| PLUMBING PLAN REVIEW |
| AVAILABLE FROM 1:00 PM TO 4:00 PM |
| [email protected] |
| 561-805-6720 |
| |