2018-12-26 10:26:59 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #18120427 | | 12/26/18 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEET M2.1: SHOW THE LOCATIONS OF THE REQUIRED SMOKE | | DETECTORS, AND PROVIDE A SEQUENCE OF OPERATION FOR FAN | | SHUTDOWN- SECTIONS 606.2.2, 606.4 & 606.4.1 FBC M. | | | | 2) THE $89,000 VALUE ON THE PERMIT APPLICATION APPEARS | | LOW FOR THE 2650 SF. REMODEL. PLEASE PROVIDE A CONTRACT | | AND/OR DETAILED ESTIMATES FOR ALL PHASES OF THE PROJECT | | THAT INCLUDES LABOR, MATERIAL, EQUIPMENT, APPLIANCES, | | FIXTURES, DESIGN FEES, AND OVERHEAD AND PROFIT- SECTION | | 109.3 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|