Plan Review Notes For Permit 18120427
Permit Number 18120427
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-28 14:13:39****CORRECTIONS****
 W.P.B. PERMIT: 18120427
 REVIEWED: DECEMBER 28, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 [FBC 1017.3]MEASUREMENT. EXIT ACCESS TRAVEL DISTANCE
 SHALL BE MEASURED FROM THE MOST REMOTE POINT WITHIN A
 STORY ALONG THE NATURAL AND UNOBSTRUCTED PATH OF
 HORIZONTAL AND VERTICAL EGRESS TRAVEL TO THE ENTRANCE
 TO AN EXIT.
  
 1. [FBC AMENDED 107.3.5.1]
 A) STATE THE MAXIMUM TRAVEL DISTANCE
 B) ADJUST LIFE SAFETY PLAN TO SHOW EGRESS FOR OCCUPANTS
 TO THE EXIT STAIRWAY DOOR.
 C) ADJUST OCCUPANT LOAD TO 27 OCCUPANTS.
  
 2. [FBC EXISTING 501]STATE THE LEVEL OF ALTERATION FOR
 WORK BEING PERFORMED. THIS IS A LEVEL 2 ALTERATION.
 ALSO, STATE OCCUPANCY AS NO CHANGE FROM PREVIOUS. THIS
 WILL SATISFY THE IMPACT STOP THAT WAS INCLUDED WITH
 THIS PERMIT REVIEW.
  
 4. [FBC 806.4]ACCEPTANCE CRITERIA AND REPORTS. WHERE
 REQUIRED TO EXHIBIT IMPROVED FIRE PERFORMANCE,
 CURTAINS, DRAPERIES, FABRIC HANGINGS AND SIMILAR
 COMBUSTIBLE DECORATIVE MATERIALS SUSPENDED FROM WALLS
 OR CEILINGS SHALL BE TESTED BY AN APPROVED AGENCY AND
 MEET THE FLAME PROPAGATION PERFORMANCE CRITERIA OF TEST
 1 OR 2, AS APPROPRIATE, OF NFPA 701, OR EXHIBIT A
 MAXIMUM HEAT RELEASE RATE OF 100 KW WHEN TESTED IN
 ACCORDANCE WITH NFPA 289, USING THE 20 KW IGNITION
 SOURCE. REPORTS OF TEST RESULTS SHALL BE PREPARED IN
 ACCORDANCE WITH THE TEST METHOD USED AND FURNISHED TO
 THE BUILDING OFFICIAL UPON REQUEST.
 PROVIDE SUBMITTAL PRIOR TO INSTALLATION OF ROOM DIVIDER
 TO MEET CRITERIA IN 806.4.
  
 3. [FBC 305.1]GENERAL. CLEAR FLOOR OR GROUND SPACE
 SHALL COMPLY WITH 305.
 SHOW CLEAR FLOOR SPACE AT KITCHEN SINK FOR SIDE
 APPROACH, OR PROVIDE FOR FORWARD APPROACH (SEE BELOW)
 [FBC 606.2]CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE
 COMPLYING WITH 305, POSITIONED FOR A FORWARD APPROACH,
 AND KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  