2019-01-04 07:09:43 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE ONE-LINE DIAGRAM WITH WIRE SIZES |
| AND CONDUIT SIZES TO METER-CAN, NEW ATS, GENERATOR, AND |
| FROM ATS TO EXISTING 125AMP PANEL AND GENERATOR OCP. |
| FBC 107.2.1 |
| |
| 2. PROVIDE LOAD CALCULATION SHOWING LOAD SHEDDING. NEC |
| 220 |
| |
| 3. VALUE IS LOW, RAISE VALUE. VALUE TO INCLUDE ALL |
| MATERIALS (GENERATOR INCLUDED) AND LABOR. FBC 109.3 |
| BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES, |
| VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC, |
| PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE |
| WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| 4. PLAN SHOWS 20KW GENERATOR BUT SPEC SHEETS SHOW 22KW |
| GENERATOR. PROVIDE CLARIFICATION OF WHAT IS ACTUALLY |
| BEING INSTALLED. FBC 107.2.1 |
| |
| 5. LICENSE # 13004086 IS ASSOCIATED WITH BRUCE KEMP AND |
| DBA "DOUG'S INDUSTRIAL REFRIDGERATION INC". PLAN IS |
| SIGNED BY LIGHTHOUSE ENERGY. ELECTRICAL PLAN MUST BE |
| SIGNED BY ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE |
| CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |