Plan Review Notes For Permit 18120357 |
Permit Number |
18120357 |
|
Review Stop |
G |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-02-07 12:42:54 | 1) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE NEW | | DRYER.2ND REQUEST. 2017 FBC- RES. SEC.G2407.1, G2439.4. | | 2) YOU HAVE SHOWN THE LOCATION OF THE DRYER ON THE | | PLAN. IS THIS IN A SEPARATE ROOM WITH A DOOR? NO DOOR? | | CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|