2019-01-23 12:57:551) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES
 DRYERS). 2ND REQUEST.
 2) WITH THE TANKLESS WATER HEATER AND DRYER, THE 3/4
 INCH GAS LINE IS UNDERSIZED BASED ON THE DISTANCE IN
 TABLE 402.4(2). THE LINE SHALL BE INCREASED TO 1 INCH
 OR THE GAS PRESSURE OF THE SYSTEM NEEDS TO BE INCREASED
 AND REGULATORS WILL BE REQUIRED AT THE APPLIANCES.2ND
 REQUEST.
 PROVISO:
 A SEPARATE PERMIT WILL BE REQUIRED FOR THE ASSOCIATED
 ELECTRIC WORK.
  