2018-12-26 05:26:16 | 1) THERE IS AN APPLICATION IN THE PERMIT PACKAGE FOR A |
| GAS DRYER BUT IT IS NOT SHOWN ON THE GAS RISER DIAGRAM. |
| SHOW THE GAS DRYER ON THE GAS RISER AND SHOW THE BTU |
| LOAD OF THE DRYER ON THE PLAN. REFER TO THE 2017 |
| FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) |
| THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 |
| AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). |
| 2) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| 2017 FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE 2017 |
| FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 FBC-RES. |
| SEC. G 2413.4.1, G2413.4.2. |
| 4) WITH THE ADDED DRYER, IT APPEARS THAT THE 3/4 INCH |
| GAS LINE MAY BE UNDERSIZED BASED ON THE DISTANCE IN |
| TABLE 402.4(2). |
| 5) SHOW THE LOCATION OF THE DRYER ON THE PLANS. WPB |
| AMEND. TO FBC SEC. 107.2.1. |
| 6) SUBMIT AN ADDITIONAL APPLICATION FOR THE PLUMBING |
| CONNECTIONS FOR THE TANKLESS WATER HEATER. |
| 7) A SEPARATE PERMIT WILL BE REQUIRED FOR THE |
| ASSOCIATED ELECTRIC WORK. |
| 8) SHOW THE LOCATION OF THE GAS METER ON THE HOUSE |
| PLAN. WPB AMEND. TO FBC SEC. 107.2.1. |
| |