2019-01-16 16:47:06 | ELECTRICAL PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| PERMITTED. PROVIDE DETAILS OF SERVICE FOR MAIN HOUSE. |
| PROVIDE CORRECTION AND/OR CLARIFICATION. FBC 107.2.1; |
| NEC 230.2; FBC RE E3601.2 |
| |
| 2. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF |
| SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, |
| WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY |
| SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW |
| INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, |
| 250.50, 250.94, 408.30; FBC RE E3706.1, E3608.1, |
| E3609.3; FBC 107.2.1 |
| |
| 3. PROVIDE GROUNDING ELECTRODE SYSTEM AS REQUIRED FOR A |
| BUILDING OR STRUCTURE SUPPLIED BY A FEEDER OR BRANCH |
| CIRCUIT. NEC 250.32; FBC RE3607.3 |
| |
| 4. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| MAIN BREAKER AT THE PANEL FOR THE SUB-PANELS IN THE |
| CARRIAGE HOUSE. NEC 225.31, 225.32 |
| |
| 5. BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| 15- AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY |
| ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, |
| DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS, |
| HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS |
| SHALL BE AFCI PROTECTED. PROVIDE COMPLIANCE. NEC |
| 210.12; FBC RE E3902.16 |
| |
| 6. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE |
| LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF |
| THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL |
| CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE. |
| FBC EC R404.1 |
| |
| 7. LOAD CALC'S PROVIDED SHOW A 20 AMP OVERCURRENT |
| DEVICE FOR DRYER. TYPICALLY A DRYER REQUIRES A 30 AMP |
| OVERCURRENT PROTECTION DEVICE. IS THIS A GAS DRYER? IF |
| YES, PROVIDE GAS RISER DIAGRAHM. |
| |
| 8. BATHROOM REQUIRES DEDICATED 20 AMP GFCI CIRCUT. |
| |
| 9. PROVIDE LOAD CALCULATION FOR ENTIRE SERVICE, INCLUDE |
| EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE |
| IS ADEQUATE. INCLUDE ALL LOADS, CURRENTLY THE WASHERS |
| AND DRYERS ARE NOT INCLUDED. NEC 215.2, 220, 408.30; |
| FBC RE E3602.2 |
| |
| 10. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR |
| ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE |
| CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE |
| TO COMPLY WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; |
| FBC RE E3706.2, E3902 |
| |
| 11. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| SERVICE. SHOW ON PLAN. NEC 250.94; FBC RE E3609.3 |
| |
| 12. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A |
| NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |
| |
| |
| |
| |
| |