2019-06-11 09:06:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED WITH NOTE ON PLAN.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE
 NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100
 AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE
 TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT
 SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1
 (NOT PROVIDED. RISER DIAGRAM SHOWS A CIRCUIT FEEDING
 THE POOL, BUT THIS IS NOT INCLUDED IN THE PANEL
 SCHEDULE OR THE LOAD CALCULATION. NO LOAD CALCULATION
 HAS BEEN PROVIDED FOR MAIN HOUSE.)
 9. OK
  
 NEW COMMENTS:
  
 10. PER NOTE BELOW THE COMMENTS, THE CORRECTED SHEETS
 ARE REQUIRED TO BE INSERTED INTO THE PLAN WHEN
 RESUBMITTING, AND THE OLD SHEETS SHOULD BE REMOVED.
 PROVIDE CORRECTION. WPB FBC 107.2.1
 11. LOAD CALCULATION STATES THAT A 100 AMP SERVICE WILL
 BE PROVIDED TO GUEST HOUSE. RISER DIAGRAM SHOWS # 8
 WIRE FEEDING THIS PANEL. THIS WIRE SIZE IS NOT RATED
 FOR 100 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16);
 FBC RE E3705.1
 12. PANEL SCHEDULE SHOWS CIRCUIT # 8 AS A 15 AMP
 CIRCUIT AND 14 GAUGE WIRE FOR THE BATHROOM RECEPTACLE.
 A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S).
 PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  