2019-06-11 09:06:20 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED. |
| 2. CORRECTED. |
| 3. CORRECTED. |
| 4. CORRECTED WITH NOTE ON PLAN. |
| 5. CORRECTED. |
| 6. CORRECTED. |
| 7. CORRECTED. |
| 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE |
| NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100 |
| AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE |
| TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT |
| SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1 |
| (NOT PROVIDED. RISER DIAGRAM SHOWS A CIRCUIT FEEDING |
| THE POOL, BUT THIS IS NOT INCLUDED IN THE PANEL |
| SCHEDULE OR THE LOAD CALCULATION. NO LOAD CALCULATION |
| HAS BEEN PROVIDED FOR MAIN HOUSE.) |
| 9. OK |
| |
| NEW COMMENTS: |
| |
| 10. PER NOTE BELOW THE COMMENTS, THE CORRECTED SHEETS |
| ARE REQUIRED TO BE INSERTED INTO THE PLAN WHEN |
| RESUBMITTING, AND THE OLD SHEETS SHOULD BE REMOVED. |
| PROVIDE CORRECTION. WPB FBC 107.2.1 |
| 11. LOAD CALCULATION STATES THAT A 100 AMP SERVICE WILL |
| BE PROVIDED TO GUEST HOUSE. RISER DIAGRAM SHOWS # 8 |
| WIRE FEEDING THIS PANEL. THIS WIRE SIZE IS NOT RATED |
| FOR 100 AMPS. PROVIDE CORRECTION. NEC 310.15(B)(16); |
| FBC RE E3705.1 |
| 12. PANEL SCHEDULE SHOWS CIRCUIT # 8 AS A 15 AMP |
| CIRCUIT AND 14 GAUGE WIRE FOR THE BATHROOM RECEPTACLE. |
| A MINIMUM OF ONE 20 AMPERE BRANCH CIRCUIT SHALL BE |
| PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). |
| PROVIDE CORRECTION. NEC 210.11(C)(3) , FBC RE E3703.4 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |