2019-04-10 11:29:18 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. OK |
| 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3606.3 |
| 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| NEC 110.3, 110.9; FBC RE E3606.3 |
| 4. RISER DIAGRAM SHOWS A SEPARATE GROUNDING ELECTRODE |
| SYSTEM FOR THE 50 AMP SERVICE. ALL GROUNDING ELECTRODES |
| PRESENT ARE REQUIRED TO BE BONDED TOGETHER AT THE |
| SERVICE. THE PANEL LOCATED AT THE SEPARATE STRUCTURE |
| SHOULD ALSO HAVE A GROUNDING ELECTRODE CONDUCTOR |
| INSTALLED TO A GROUNDING ELECTRODE. PROVIDE |
| CORRECTIONS. FBC RE E3608.1, E3607.3 |
| 5. THIS SEPARATE STRUCTURE IS REQUIRED TO HAVE A MAIN |
| THAT SHUTS OFF ALL POWER TO THE STRUCTURE. PROVIDE |
| EITHER A MAIN BREAKER IN THIS PANEL. OR A DISCONNECT |
| AHEAD OF THE MAIN LUG PANEL THAT IS LOCATED ON THE |
| SEPARATE STRUCTURE. NEC 225.31, 225.32 |
| 6. UNGROUNDED CONDUCTORS FOR OTHER THAN DWELLING UNITS |
| SHALL HAVE AN AMPACITY OF NOT LESS THAN 60 AMPERES AND |
| SHALL BE SIZED AS REQUIRED FOR FEEDERS. PROVIDE |
| CORRECTION. FBC RE E3603.2 |
| 7. OK |
| 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE |
| NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100 |
| AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE |
| TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT |
| SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1 |
| 9. OK |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |