2018-12-25 11:05:04 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. RISER DIAGRAM PROVIDED SHOWS A NEW 50 AMP MAIN |
| DISCONNECT ON THE LEFT SIDE OF METER. THIS INSTALLATION |
| IS NOT PERMITTED PER FPL ELECTRICAL SERVICE STANDARDS, |
| SECTION IV, PAGE 16. ADDITIONALLY, PROVIDE DETAIL OF |
| TAPPING FROM METER CAN AS THEY TYPICALLY HAVE LUGS THAT |
| PERMIT ONLY ONE WIRE ON EACH LUG. PROVIDE CORRECTIONS. |
| WPB FBC 107.2.1; FBC RE E3605.3 |
| 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10; FBC RE E3606.3 |
| 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| NEC 110.3, 110.9; FBC RE E3606.3 |
| 4. RISER DIAGRAM SHOWS A SEPARATE GROUNDING ELECTRODE |
| SYSTEM FOR THE 50 AMP SERVICE. ALL GROUNDING ELECTRODES |
| PRESENT ARE REQUIRED TO BE BONDED TOGETHER AT THE |
| SERVICE. THE PANEL LOCATED AT THE SEPARATE STRUCTURE |
| SHOULD ALSO HAVE A GROUNDING ELECTRODE CONDUCTOR |
| INSTALLED TO A GROUNDING ELECTRODE. PROVIDE |
| CORRECTIONS. FBC RE E3608.1, E3607.3 |
| 5. PANEL LOCATED AT SEPARATE STRUCTURE IS SHOWN AS A |
| MAIN LUG ONLY PANEL. THIS SEPARATE STRUCTURE IS |
| REQUIRED TO HAVE A MAIN THAT SHUTS OFF ALL POWER TO THE |
| STRUCTURE. PROVIDE EITHER A MAIN BREAKER IN THIS PANEL. |
| OR A DISCONNECT AHEAD OF THE MAIN LUG PANEL THAT IS |
| LOCATED ON THE SEPARATE STRUCTURE. NEC 225.31, 225.32 |
| 6. UNGROUNDED CONDUCTORS FOR OTHER THAN DWELLING UNITS |
| SHALL HAVE AN AMPACITY OF NOT LESS THAN 60 AMPERES AND |
| SHALL BE SIZED AS REQUIRED FOR FEEDERS. PROVIDE |
| CORRECTION. FBC RE E3603.2 |
| 7. ALL RECEPTACLE OUTLETS INSTALLED IN STORAGE AREAS |
| SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. FBC RE |
| E3902.2 |
| 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE |
| NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100 |
| AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE |
| TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT |
| SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1 |
| 9. BREAKER SIZE SHOWN FOR WATER HEATER IS 30 AMP, WHICH |
| IS THE TYPICAL SIZE FOR A 4500 WATT WATER HEATER. BUT |
| THE LOAD CALCULATION SHOWS AN 1800 WATT LOAD. PROVIDE |
| CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1; FBC |
| RE E3602.2 |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |