2018-12-25 11:05:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. RISER DIAGRAM PROVIDED SHOWS A NEW 50 AMP MAIN
 DISCONNECT ON THE LEFT SIDE OF METER. THIS INSTALLATION
 IS NOT PERMITTED PER FPL ELECTRICAL SERVICE STANDARDS,
 SECTION IV, PAGE 16. ADDITIONALLY, PROVIDE DETAIL OF
 TAPPING FROM METER CAN AS THEY TYPICALLY HAVE LUGS THAT
 PERMIT ONLY ONE WIRE ON EACH LUG. PROVIDE CORRECTIONS.
 WPB FBC 107.2.1; FBC RE E3605.3
 2. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3606.3
 3. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL.
 NEC 110.3, 110.9; FBC RE E3606.3
 4. RISER DIAGRAM SHOWS A SEPARATE GROUNDING ELECTRODE
 SYSTEM FOR THE 50 AMP SERVICE. ALL GROUNDING ELECTRODES
 PRESENT ARE REQUIRED TO BE BONDED TOGETHER AT THE
 SERVICE. THE PANEL LOCATED AT THE SEPARATE STRUCTURE
 SHOULD ALSO HAVE A GROUNDING ELECTRODE CONDUCTOR
 INSTALLED TO A GROUNDING ELECTRODE. PROVIDE
 CORRECTIONS. FBC RE E3608.1, E3607.3
 5. PANEL LOCATED AT SEPARATE STRUCTURE IS SHOWN AS A
 MAIN LUG ONLY PANEL. THIS SEPARATE STRUCTURE IS
 REQUIRED TO HAVE A MAIN THAT SHUTS OFF ALL POWER TO THE
 STRUCTURE. PROVIDE EITHER A MAIN BREAKER IN THIS PANEL.
 OR A DISCONNECT AHEAD OF THE MAIN LUG PANEL THAT IS
 LOCATED ON THE SEPARATE STRUCTURE. NEC 225.31, 225.32
 6. UNGROUNDED CONDUCTORS FOR OTHER THAN DWELLING UNITS
 SHALL HAVE AN AMPACITY OF NOT LESS THAN 60 AMPERES AND
 SHALL BE SIZED AS REQUIRED FOR FEEDERS. PROVIDE
 CORRECTION. FBC RE E3603.2
 7. ALL RECEPTACLE OUTLETS INSTALLED IN STORAGE AREAS
 SHALL HAVE GFCI PROTECTION. PROVIDE CORRECTION. FBC RE
 E3902.2
 8. PROVIDE ACCURATE LOAD CALCULATION DEMAND FACTORS ARE
 NOT PERMITTED TO BE APPLIED TO FEEDERS LESS THAN 100
 AMPS. ALSO, PROVIDE LOAD CALCULATION FOR MAIN SERVICE
 TO HOUSE TO CONFIRM THAT THE METER CAN IS OF SUFIICIENT
 SIZE FOR THE ADDITIONAL LOAD. FBC RE E3602.2, E3602.2.1
 9. BREAKER SIZE SHOWN FOR WATER HEATER IS 30 AMP, WHICH
 IS THE TYPICAL SIZE FOR A 4500 WATT WATER HEATER. BUT
 THE LOAD CALCULATION SHOWS AN 1800 WATT LOAD. PROVIDE
 CLARIFICATION AND/OR CORRECTION. WPB FBC 107.2.1; FBC
 RE E3602.2
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  