2019-01-05 11:22:01 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. STRUCTURE IS MIS-CLASSIFIED AS A STORAGE BUILDING. |
| STRUCTURE IS DESIGNED AS A HABITABLE STRUCTURE AND WILL |
| REQUIRE PALM BEACH COUNTY IMPACT FEES. CHANGE BUILDING |
| DESCRIPTION ON PLANS. STATE WHAT STRUCTURE WILL BE USED |
| FOR. |
| PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL |
| (561) 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE |
| PLAN SET AND TAKE TO THAT OFFICE FOR REVIEW. PLEASE |
| RETURNED STAMPED AND WITH A COPY OF THE RECEIPT AS |
| APPLICABLE. PLEASE PROVIDE THE MUNICIPAL IMPACT FEE |
| QUESTIONNAIRE FORM TO THE PBC IMPACT FEE OFFICE. THE |
| FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/AD |
| MINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| 2. PROVIDE ENERGY SUBMITTAL. |
| FBCE-103.2.1.1 RESIDENTIAL LESS THAN OR EQUAL TO 3 |
| STORIES. ENERGY |
| FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402 |
| SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO |
| DEMONSTRATE CODE COMPLIANCE BY THIS METHOD. |
| _ OR _ |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| R401.3 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD |
| (MANDATORY). |
| |
| 3. SHOW FINISHED FLOOR ELEVATION ON SITE PLAN. |
| R403.1.7.3 FOUNDATION ELEVATION. |
| ON GRADED SITES, THE TOP OF ANY EXTERIOR FOUNDATION |
| SHALL EXTEND ABOVE THE ELEVATION OF THE STREET GUTTER |
| AT POINT OF DISCHARGE OR THE INLET OF AN APPROVED |
| DRAINAGE DEVICE A MINIMUM OF 12 INCHES (305 MM) PLUS 2 |
| PERCENT. ALTERNATE ELEVATIONS ARE PERMITTED SUBJECT TO |
| THE APPROVAL OF THE BUILDING OFFICIAL, PROVIDED IT CAN |
| BE DEMONSTRATED THAT REQUIRED DRAINAGE TO THE POINT OF |
| DISCHARGE AND AWAY FROM THE STRUCTURE IS PROVIDED AT |
| ALL LOCATIONS ON THE SITE. |
| |
| 4. PROVIDE SITE DRAINAGE PLAN. |
| FBC R401.3 SITE DRAINAGE |
| PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING |
| COMPLIANCE WITH FBC R401.3 DRAINAGE. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| LOTS SHALL BE GRADED TO DRAIN SURFACE WATER AWAY FROM |
| FOUNDATION WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 |
| INCHES WITHIN THE FIRST 10 FEET. |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES OF FALL WITHIN 10 |
| FEET, DRAINS OR SWALES SHALL BE CONSTRUCTED TO ENSURE |
| DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET OF THE BUILDING |
| FOUNDATION SHALL BE SLOPED A MINIMUM OF |
| 2 PERCENT AWAY FROM THE BUILDING. |
| FBC R 401.3 (DRAINAGE) |
| FBC 107.2.5 (SITE PLAN) |
| FBC 110.9 (IMPACT OF CONSTRUCTION) |
| |
| 5. ROOFING PERMIT REQUIRED. |
| |
| 6. PROVIDE FRAMING DETAIL FOR PARAPIT WALLS. PROVIDE |
| CONNECTOR SCHEDULE. |
| R301.1 |
| STRUCTURAL CONNECTORS. |
| BUILDINGS AND STRUCTURES, AND PARTS THEREOF, SHALL BE |
| CONSTRUCTED TO SAFELY SUPPORT ALL LOADS, INCLUDING DEAD |
| LOADS, LIVE LOADS, ROOF LOADS, FLOOD LOADS, SNOW LOADS, |
| WIND LOADS AND SEISMIC LOADS AS PRESCRIBED BY THIS |
| CODE. THE CONSTRUCTION OF BUILDINGS AND STRUCTURES IN |
| ACCORDANCE WITH THE PROVISIONS OF THIS CODE SHALL |
| RESULT IN A SYSTEM THAT PROVIDES A COMPLETE LOAD PATH |
| THAT MEETS THE REQUIREMENTS FOR THE TRANSFER OF LOADS |
| FROM THEIR POINT OF ORIGIN THROUGH THE LOAD-RESISTING |
| ELEMENTS TO THE FOUNDATION. BUILDINGS AND STRUCTURES |
| CONSTRUCTED AS PRESCRIBED BY THIS CODE ARE DEEMED TO |
| COMPLY WITH THE REQUIREMENTS OF THIS SECTION. |
| |
| 7. DESIGNER TO REVIEW ALL PRODUCT APPROVALS AND REVIEW |
| IN WRITING. (NOT SIGN AND SEAL) |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR |
| SUBMITTALS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |