2018-12-19 08:19:38 | RESIDENTIAL (R3) FOUNDATION ONLY PERMIT, BUILDING |
| REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- FOUNDATION PLAN WAS NOT SUBMITTED. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 2- FLOOD ZONE AE WITH BASE FLOOD ELEVATION OF 7'-0" |
| (NAVD OF 1988). POWDER ROOM LOCATED IN THE GARAGE NEEDS |
| TO BE ELEVATED TO 9'-0". |
| CITY ORDINANCE 4729-17 SEC. 18-34 THE FINISH FLOOR |
| ELEVATION NEEDS TO BE TWO FEET FREEBOARD ABOVE THE BASE |
| FLOOD ELEVATION. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| NOTE: MAIN HOUSE AND FOUNDATION PERMITS WERE |
| SIMULTANEOUSLY REVIEWED. MAIN HOUSE PERMIT WAS APPROVED |
| WITH PROVISO. CONTRACTOR TO COORDINATE THIS TWO PERMITS |
| TO AVOID CONFLICTS/DELAYS. SEE PROVISO BELOW: |
| |
| BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-SHOW ATTIC ACCESS SIZE/LOCATION IN ALL ROOF AREAS IN |
| THE 1ST & 2ND FLOOR. |
| 2-PROVIDE PRODUCT APPROVAL FOR: A)WINDOW MULLIONS AND |
| SPECIFY MULLION SIZE. B)DOORS PRODUCT APPROVAL |
| FL10765-R6 IS FOR NON-IMPACT DOORS. PROVIDE SHUTTERS |
| PRODUCT APPROVAL AND COMPLETE INSTALLATION SCHEDULE. |
| C)POLYGLASS ROOF UNDERLAYMENT FL5259-R28: CLEARLY MARK |
| WHICH ASSEMBLY L IS GOING TO BE USED. D) SHUTTERS SHOWN |
| ON EXTERIOR ELEVATIONS AND PROVIDE COMPLETE |
| INSTALLATION SCHEDULE. E) WATER PROOFING AT TERRACE. |
| PROVIDE PRODUCT APPROVAL THAT IS DESIGNED TO RECEIVE |
| MATERIAL SPECIFIED BY THE DESIGNER OF RECORD. F) |
| DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT |
| APPROVALS. |
| 3-ALUMINUM TRELLIS UNDER SEPARATE PERMIT PER |
| ARCHITECT'S RESPONSE LETTER. |
| 4-REVISE ENTRY FOYER FINISH ELEVATION IN ALL PLANS. PER |
| JOHN MELHORN, THE ELEVATION WILL BE 9'-0" (NAVD OF |
| 1988) NOT 8'-6". |
| 5-PER JOHN MELHORN, GARAGE WILL HAVE FLOOD VENTS. |
| PROVIDE PRODUCT APPROVAL AND REVISE PLANS SHOWING |
| LOCATION. ALSO, POWDER ROOM LOCATED IN THE GARAGE NEEDS |
| TO BE ELEVATED TO 9'-0". |
| |