2019-04-09 07:49:27MECANICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE LIST
 THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL
 STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN
 PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE
 WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT
 INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE
 CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS
 FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN
 AND SCOPE OF WORK FOR 2ND UNIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. MECHANICAL SCOPE OF WORK INCLUDES EXHAUST FANS,
 MINI-SPLIT AND DRYER EXHAUST. EXHAUST FANS MISSING FROM
 PLAN. NO DRYER SHOWN ON PLAN.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. PROVIDE ENERGY CALCULATIONS (MANUAL J), INCLUDE
 EQUIPMENT SIZING PER ACCA MANUAL S. M1401.3 EQUIPMENT
 AND APPLIANCE SIZING.
  
 4. TWO SEPERATE 20 AMP CIRCUTS ARE PROPOSED FOR NEW
 MINI-SPLIT SYSTEM. PROVIDE MANUFACTURERS SPCIFICATIONS
 TO VERIFY POWER REQUIREMENTS. M1401.1 INSTALLATION
  
 5. PROVIDE SURVEY. SHOW LOCATION OF NEW CONDENSING
 UNIT. PROVIDE DISTANCE TO PROPERTY LINE. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 6. PROVIDE NOTE ON PLAN TO PROVIDE LOCKING ACCESS
 PORTS. M1411.8 LOCKING ACCESS PORT CAPS.
  
 7. PROVIDE DETAIL OF CONDENSATE DISPOSAL PIPING ROUTING
 THROUGH BUILDING. M1411.3 CONDENSATE DISPOSAL.
  
 8. PROVIDE A 125-VOLT, SINGLE PHASE, 15 OR 20 AMP
 RECEPTACLE OUTLET FOR THE SERVICING OF THE NEW
 MECHANICAL EQUIPMENT. E3901.12 HVAC OUTLET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  