2019-04-08 17:37:26ELECTRICAL PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. THE PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE
 LIST THIS BLDG. AS A 2 STORY MULTI-FAMILY RESIDENTIAL
 STRUCTURE WITH 2 UNITS. BUILDING DATA INFO. ON PLAN
 PAGE A-1 STATES THIS STRUCTURE IS A 2 STORY STRUCTURE
 WITH ONLY 1 UNIT. NO RECORDS ARE AVAILABLE THAT
 INDICATES THESE 2 UNITS HAVE BEEN COMBINED. PLEASE
 CLARIFY. IDENTIFY UNIT THIS PROPOSED SCOPE OF WORK IS
 FOR. IF BOTH UNITS ARE TO RECIEVE WORK, PROVIDE PLAN
 AND SCOPE OF WORK FOR 2ND UNIT.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 2. NEW CHANGE IN SERVICE -
 2A. STATE CONDUCTOR SIZE OF EXISTING SERVICE DROP.
 E3602.1 AMPACITY OF UNGROUNDED CONDUCTORS.
 2B. IDENTIFY LOCATION OF SERVICE DISCONNECT. E3601.6.2
 SERVICE DISCONNECT LOCATION.
 2C. PROVIDE LOAD CALCULATIONS FOR BOTH NEW PANELS.
 UTILIZE RESIDENTIAL FORMULA TABLE E3602.2
 2D. PROVIDE AIC CALCULATIONS FOR BOTH NEW SERVICES.
 E3602.2 SERVICE LOAD.
  
 3. ELECTRICAL NOTE #6 IS INCORRECT. AFCI PROTECTION IS
 REQUIRED PER THE FOLLOWING: E3902.16 ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION.
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE PROTECTED BY ANY OF THE FOLLOWING: [210.12(A)]
  
 4. ELECTRICAL PLAN SHOWS BOTH KITCHEN COUNTER TOP
 RECEPTACLES ARE SUPPLIED FROM A SINGLE 20AMP CIRCUT-
 #2. PLEASE SEE FBC R3703.2 AND CORRECT.
 E3703.2 KITCHEN AND DINING AREA RECEPTACLES.
 A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL
 BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA,
 DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN
 COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF
 TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF
 WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER
 RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY,
 BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS
 FOR REFRIGERATION APPLIANCES. [210.11(C)(1) AND
 210.52(B)(1) AND (B)(2)].
  
 5. CIRCUT #10 OVERCURRENT PROTECTION AND CONDUCTOR SIZE
 IS INCORRECT. E3703.4 BATHROOM BRANCH CIRCUITS AND
 TABLE E3702.14.
 A MINIMUM OF ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. [210.11(C)(3)].
  
 6. PANEL SCHEDULE ON PLAN PAGE A-1 IS LABELED WINDOW
 AND DOOR SCHEDULE. PLEASE CORRECT. 107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 7. OVERCURRENT PROTECTION FOR THE INDOOR AND OUTDOOR
 MINI-SPLIT A/C SYSTEM PROPOSES TWO SEPERATE SINGLE POLE
 20AMP CIRCUTS. PROVIDE MANUFACTURERS SPCIFICATIONS TO
 VERIFY. E3702.11 BRANCH CIRCUITS FOR AIR-CONDITIONING
 AND HEAT PUMP EQUIPMENT.
  
 8. PROVIDE A 125-VOLT, SINGLE PHASE, 15 OR 20 AMP
 RECEPTACLE OUTLET FOR THE SERVICING OF THE NEW
 MECHANICAL EQUIPMENT. E3901.12 HVAC OUTLET.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED.
  
  
  
  
  