2018-12-06 15:11:38 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE SUBMITTED PLAN SHEET SHOWS VERY GENERAL |
| INFOMATION WITH A LARGE CLOUD AREA. |
| |
| THE PREVIOUS PLANS SHOWED A DOMESTIC PUMP AREA. |
| |
| WHAT HAPPENED TO THE THAT PUMP? |
| |
| |
| |
| 2) THERE ARE INDICATIONS WHERE THE NEW PIPING HAS |
| BREACHED A FIRE RATED WALL. |
| |
| PLEASE PROVIDE THE LISTED FIRE WALL PENETRATIONS USED |
| TO MAINTAIN THIS RATING? |
| |
| |
| |
| 3) THERE IS AN INDICATION "DOOR TO BE REMOVED" AND A |
| NEW DOOR ADDED. |
| |
| THE PUMP ROOM IS REQUIRED TO BE RATED. IS THIS NEW DOOR |
| RATED? |
| |
| HOW IS IT ASCESSED? |
| |
| WAS AN EXIT LIGHT MOVED OR PROVIDED? |
| |
| HOW WAS THE DOOR VOID SPACE INFILLED? |
| |
| PLEASE CORRECT OR PROVIDE SPECIFIC DETAILES AND FIRE |
| CODE REFERENCES. |
| |
| |
| |
| 4) THERE IS TWO NEW PIPES ENTERING ANOTHER ROOM AND |
| BREACHING ANOTHER WALL. |
| |
| THIS NEW ROOM IS NOT INDICATED AND HOW IT IS BEING |
| USED. |
| |
| PLEASE PROVIDE THE ROOM DETAIL AND HOW IT IS USED.. |
| |
| |
| |
| 5) THE FDC CONFIGURATION IS DIFFERENT THAN PREVIOUSLY |
| SUBMITTED. |
| |
| IT APPEARS THE FDC IS FEEDING THE INCORRECT END |
| (DISCHARGE) OF THE PUMP. |
| |
| PLEASE REVIEW AND CORRECT OR EXPLAIN WITH DETAILS. |
| |
| |
| |
| 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| |
| 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |