2019-03-26 09:31:04PERMIT # 18111193
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SHEET ALS 1.3 ON REVIEW OF THE REVISION TO THE 3RD
 FLOOR TERRACE IT APPEARS THAT THE EGRESSING FOR THE
 TERRACE SPACE DOES NOT MEET THE MEANS OF EGRESS
 REQUIREMENTS FOR ASSEMBLY OCCUPANCIES.
 ASSEMBLY REQUIREMENTS SHALL HAVE A MINIMUM OF 2,
 PROPERLY SEPARATED, MEANS OF EGRESS. ALTHOUGH THERE ARE
 3 SEPARATE EXIT STAIRWELLS ON THE 3RD FLOOR, THE
 TERRACE AREA HAS ONLY ONE MEANS OF EGRESS LEADING
 OUT/OFF OF THE TERRACE AREA.
 NFPA 101, CHAPTER 7:
 7.4* NUMBER OF MEANS OF EGRESS.
 7.4.1 GENERAL.
 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY,
 MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS
 THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS:
 (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43.
 (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A
 MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL
 LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET.
  
 NFPA 101, CHAPTER 12:
 12.2.4* NUMBER OF MEANS OF EGRESS.
 12.2.4.1 THE NUMBER OF MEANS OF EGRESS SHALL BE IN
 ACCORDANCE WITH SECTION 7.4, OTHER THAN EXITS FOR
 FENCED OUTDOOR ASSEMBLY OCCUPANCIES IN ACCORDANCE WITH
 12.2.4.4.
  
 2) THE 3RD FLOOR AND TERRACE PLANS DO NOT MATCH THE
 APPROVED LAYOUTS/FLOOR PLANS AS PROVIDED ON MASTER
 PERMIT #17120610 AND REVISION 18040104. THIS NEW
 LOCATION OF THE "TERRACE" IS NOT COMPLIANCE OF THE FIRE
 CODE REQUIREMENTS FOR EGRESS.
  
 3) SHEET ALS 0.1: THE OCCUPANCY LOADS DO NOT FULLY
 MATCH THE OCCUPANT LOADS PROVIDED ON SHEETS ALS 1.1,
 ALS 1.2, AND ALS 1.3.
 SPECIFICALLY, THE CONFERENCE ROOM TOTALS, AND THE TENAN
 OCCUPANT LOADS ON THE 3RD FLOOR.
 ON ALS 0.1, THE TERRACE IS LABELED AS FLOOR 4, NOT
 FLOOR 3.
 PLEASE REVIEW AND ENSURE THAT ALL OCCUPANT LOAD
 CALCULATIONS AND TOTAL MATCH ON ALL APPLICABLE SHEETS.
  
 4) ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED
 DURING PLAN RESUBMISSION.
  
  