Date |
Text |
2019-03-05 14:57:55 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| JOSEAN A. DUPREY E.I., BN, PX |
| BUILDING PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6716 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 2ND REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. ANSWERED |
| |
| 2. NOTED |
| |
| ADDITIONAL COMMENTS: |
| |
| 3. BUILDING CODE DATA PAGE ALS.0.1 REFERED TO THE 2014 |
| 5TH EDITION FBC. PLEASE SEE BELOW THE CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC M = FLORIDA BUILDING CODE MECHANICAL 2017 6TH |
| EDITION |
| FBC P = FLORIDA BUILDING CODE PLUMBING 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| 4. SOME PAGES ARE MAKING REFRENCE TO THE THE STRUCTURAL |
| DRAWINGS, HOWEVER NO STRUCTURAL DRAWINGS WERE |
| SUBMITTED. PLEASE SUBMIT THE APPLICABLE STRUCTURAL |
| DRAWINGS. FBC 107 |
| |
| 5. PAGE A7.0.1 REFERS SECTIONS 8/A7.0.2 FOR DOOR JAMS, |
| HOWEVER THE DRAWING SHEET 8/A7.0.2 WAS NOT SUBMITTED. |
| PLEASE SUBMIT THE APPLICABLE DETAILS. FBC 107 |
| |
| 6. FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE ROOFING, WINDOW AND DOOR |
| SUBMITTALS OR INDICATE IF THIS PRODUCT APPROVALS WILL |
| BE DEFERRED. |
| |
| 107.3.4.1 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| APPROVED BY THE BUILDING OFFICIAL. |
| |
| |
| |
| |
| |