2019-01-11 09:40:471ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 SHOW COMPLIANCE WITH THE FOLLOWING: SHEET A9-5-2
  
 1. THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES MINIMUM AND 19 INCHES MAXIMUM
 MEASURED TO THE TOP OF THE SEAT.PER FBC ACC 604.4
  
 2. THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG
 MINIMUM, LOCATED 12 INCHES MAXIMUM FROM THE REAR WALL
 AND EXTENDING 54 INCHES MINIMUM FROM THE REAR WALL. PER
 FBC ACC 604.5.1
  
 3. THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM)
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND
 24 INCHES (610 MM) MINIMUM ON THE OTHER SIDE. PER FBC
 ACC 604.5.2
  
 4. MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND. PER FBC ACC 603.3
  
 5. TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR. PER FBC ACC 604.7
  
 6. LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE
 FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND. PER
 FBC ACC 606.3
  
 7. CLEAR FLOOR SPACE FOR THE TOILET AND LAVATORY WITH
 DIMENSIONS. PER FBC ACC 604.3.1, 606.2
  
 8. AT LEAST ONE OF THE LAVATORY'S OUTSIDE OF THE
 ACCESSIBLE STALL SHALL COMPLY WITH . FBC ACC 213.3.4,
 606.2, 606.3
  
 9. PLEASE REVISE SHEETS P5.1 + P6.1 SHOW THE NEW MOP
 SINK IN THE BASEMENT , SINK ON 2ND FLOOR AND
 RECONFIGURED BATHROOM ON 3RD FLOOR. PER WPB AMEND TO
 FBC 107.3.5.1.3(13)
  
 10. THE NEW SINK ON THE 2ND FLOOR NEXT TO BATHROON 208
 SHALL COMPLY WITH FBC ACC 212.3, 606.2, 606.3
  
 11. SHEET P2.3 THE WC IN THE OFFICE BATHROOM 202 IS NOT
 VENT IT SHOULD CONNECT TO THE WET VENT WITH TH E
 LAVATORY AND SHOWER. PER FBC PL 913.1
  
 12. SHEET P2.3 THE NEW SINK NEXT TO BATHROOM 208 ON 2ND
 FLOOR SHALL NOT CONNECT BETWEEN THE SHOWER AND WC IT
 SHALL CONNECT DOWN STREAM OF THE BATHROOM GROUP. PER
 FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]