Plan Review Notes
Plan Review Notes For Permit 18111193
Permit Number 18111193
Review Stop M
Sequence Number 1
Notes
Date Text
2018-12-28 16:25:261ST REVIEW FBC-2017 MECHANICAL
 MASTER PERMIT #18040104
 REVISION #18111193
 12/28/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.2: THE 6X4 DUCT IS NOT PERMITTED TO
 PENETRATE INTO THE INTERIOR EXIT STAIRWAY B- SECTION
 1023.5 FBC B.
  
 2) M2.2: A FIRE DAMPER IS REQUIRED AT THE PENETRATION
 OF THE 12X12 DUCT THROUGH THE FLOOR INTO THE BASEMENT-
 SECTION 607.6.1 FBC M.
  
 3) M2.4A: REVISE THE O/A CALCULATIONS AND THE AC
 EQUIPMENT SCHEDULE ON THE MAIN PLAN TO INCLUDE THE NEW
 THIRD FLOOR AC SYSTEMS- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  