Plan Review Notes
Plan Review Notes For Permit 18111193
Permit Number 18111193
Review Stop E
Sequence Number 1
Notes
Date Text
2018-12-23 15:25:10CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PER NEC 240.6(B), THE ADJUSTABLE BREAKER FOR PANEL
 MDP-B SHALL BE RATED AT THE MAXIMUM POSSIBLE SETTING,
 WHICH IS 1000 AMPS. THE CONDUCTORS FEEDING THIS BREAKER
 SHALL HAVE AN AMPACITY EQUAL TO OR GREATER THAN THE
 RATRING OF THE BREAKER. PROVIDE CORRECTION. NEC
 240.4(C)
  
 END OF COMMENTS.
  