2018-12-19 16:02:30 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18111109 |
| 12/18/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A FLORIDA UNDERGROUND UTILITY AND EXCAVATION |
| CONTRACTOR MAY NOT INSTALL PIPING THAT IS AN INTEGRAL |
| PART OF A FIRE PROTECTION SYSTEM AS DEFINED IN FL. |
| STATUTES 633.021 BEGINNING AT THE POINT WHERE THE |
| PIPING IS USED EXCLUSIVELY FOR SUCH SYSTEM. FOR THIS |
| TYPE OF INSTALLATION A FLORIDA FIRE PROTECTION V |
| CONTRACTOR LICENSE IS REQUIRED INSTEAD. |
| |
| 2) THE SUBMITTED SETS OF COPIED PLANS HAVE BEEN REDUCED |
| IN SIZE AND ARE COMPLETELY ILLEGIBLE AND NOT ACCEPTABLE |
| FOR REVIEW. PROVIDE CLEAR, LEGIBLE PLANS AT MINIMUM |
| 1/8" SCALE THAT ALSO BEAR THE ORIGINAL SIGNATURE AND |
| SEAL OF THE ENGINEER OF RECORD- SECTION 107.2.1 WPB AND |
| SECTION 61G15- 23.002 FAC. |
| |
| 3) PROVIDE A PRODUCT SUBMITTAL PACKAGE THAT INCLUDES |
| ALL COMPONENTS OF THE FIRE LINE ASSEMBLY INCLUDING THE |
| PIPING, TEES, PLUGS, CAPS, REDUCERS, VALVES, AND ALL |
| RESTRAINING DEVICES. PLEASE NOTE THAT MATERIAL DATA |
| SHEETS WITH TORQUE WRENCH SETTINGS SHALL BE ONSITE AT |
| TIME OF INSPECTION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |