2018-12-19 16:02:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18111109
 12/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A FLORIDA UNDERGROUND UTILITY AND EXCAVATION
 CONTRACTOR MAY NOT INSTALL PIPING THAT IS AN INTEGRAL
 PART OF A FIRE PROTECTION SYSTEM AS DEFINED IN FL.
 STATUTES 633.021 BEGINNING AT THE POINT WHERE THE
 PIPING IS USED EXCLUSIVELY FOR SUCH SYSTEM. FOR THIS
 TYPE OF INSTALLATION A FLORIDA FIRE PROTECTION V
 CONTRACTOR LICENSE IS REQUIRED INSTEAD.
  
 2) THE SUBMITTED SETS OF COPIED PLANS HAVE BEEN REDUCED
 IN SIZE AND ARE COMPLETELY ILLEGIBLE AND NOT ACCEPTABLE
 FOR REVIEW. PROVIDE CLEAR, LEGIBLE PLANS AT MINIMUM
 1/8" SCALE THAT ALSO BEAR THE ORIGINAL SIGNATURE AND
 SEAL OF THE ENGINEER OF RECORD- SECTION 107.2.1 WPB AND
 SECTION 61G15- 23.002 FAC.
  
 3) PROVIDE A PRODUCT SUBMITTAL PACKAGE THAT INCLUDES
 ALL COMPONENTS OF THE FIRE LINE ASSEMBLY INCLUDING THE
 PIPING, TEES, PLUGS, CAPS, REDUCERS, VALVES, AND ALL
 RESTRAINING DEVICES. PLEASE NOTE THAT MATERIAL DATA
 SHEETS WITH TORQUE WRENCH SETTINGS SHALL BE ONSITE AT
 TIME OF INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  