 SHALL COMPLY WITH NFPA 24
 2013 EDITION
  
 4.1.3 WORKING PLANS SHALL BE DRAWN TO AN INDICATED
 SCALE ON
 SHEETS OF UNIFORM SIZE, WITH A PLAN OF EACH FLOOR AS
 APPLICABLE,
 AND SHALL INCLUDE THE FOLLOWING ITEMS THAT PERTAIN TO
 THE DESIGN
 OF THE SYSTEM:
 (1) NAME OF OWNER
 (2) LOCATION, INCLUDING STREET ADDRESS
 (3) POINT OF COMPASS
 (4) A GRAPHIC REPRESENTATION OF THE SCALE USED ON ALL
 PLANS
 (5) NAME AND ADDRESS OF CONTRACTOR
 (6) SIZE AND LOCATION OF ALL WATER SUPPLIES
 (7) SIZE AND LOCATION OF STANDPIPE RISERS, HOSE
 OUTLETS, HAND
 HOSE, MONITOR NOZZLES, AND RELATED EQUIPMENT
 (8) THE FOLLOWING ITEMS THAT PERTAIN TO PRIVATE FIRE
 SERVICE
 MAINS:
 (A) SIZE
 (B) LENGTH
 (C) LOCATION
 (D) WEIGHT
 (E) MATERIAL
 (F) POINT OF CONNECTION TO CITY MAIN
 (G) SIZES, TYPES, AND LOCATIONS OF VALVES, VALVE
 INDICATORS,
 REGULATORS, METERS, AND VALVE PITS
 (H) DEPTH AT WHICH THE TOP OF THE PIPE IS LAID BELOW
 GRADE
 (I) METHOD OF RESTRAINT
 (9) THE FOLLOWING ITEMS THAT PERTAIN TO HYDRANTS:
 (A) SIZE AND LOCATION, INCLUDING SIZE AND NUMBER OF
 OUTLETS
 AND WHETHER OUTLETS ARE TO BE EQUIPPED WITH INDEPENDENT
 GATE VALVES
 (B) THREAD SIZE AND COUPLING ADAPTER SPECIFICATIONS IF
 DIFFERENT FROM NFPA 1963
 (C) WHETHER HOSE HOUSES AND EQUIPMENT ARE TO BE
 PROVIDED,
 AND BY WHOM
 (D) STATIC AND RESIDUAL HYDRANTS USED IN FLOW
 (E) METHOD OF RESTRAINT
 (10) SIZE, LOCATION, AND PIPING ARRANGEMENT OF FIRE
 DEPARTMENT
 CONNECTIONS
 4.1.4 THE WORKING PLAN SUBMITTAL SHALL INCLUDE THE
 MANUFACTURER?S
 INSTALLATION INSTRUCTIONS FOR ANY SPECIALLY LISTED
 EQUIPMENT,
 INCLUDING DESCRIPTIONS, APPLICATIONS, AND LIMITATIONS
 FOR
 ANY DEVICES, PIPING, OR FITTINGS.