2019-03-08 11:39:51 | PROVISO: | | | | 1ST REVIEW: 18111103 | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. SHT. A-1 THE NOTE UNDER THE ELECTRIC WATER COOLER IS | | STATING CODE SECTION 404.2 FBC PLUMBING THIS SECTION | | DOES NOT EXIST WATER COOLERS SHALL COMPLY WITH FBC PL | | 410 AND FBC ACC 211, 602 PLEASE PROVIDE DETAILS SHOWING | | COMPLIANCE WITH FBC ACC 602.2, 602.4, 602.5, 602.7, 306 | | | | 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 694.6 FLUSH | | CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND | | OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. FLUSH | | CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE WATER | | CLOSET. | | | | 3. PROVIDE MSDS SHEETS ON ANY CHEMICALS THAT ARE BEING | | USED. PER WPB AMEND TO FBC 107.2.1 | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] |
|