2019-03-08 11:39:51PROVISO:
  
 1ST REVIEW: 18111103
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-1 THE NOTE UNDER THE ELECTRIC WATER COOLER IS
 STATING CODE SECTION 404.2 FBC PLUMBING THIS SECTION
 DOES NOT EXIST WATER COOLERS SHALL COMPLY WITH FBC PL
 410 AND FBC ACC 211, 602 PLEASE PROVIDE DETAILS SHOWING
 COMPLIANCE WITH FBC ACC 602.2, 602.4, 602.5, 602.7, 306
  
 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 694.6 FLUSH
 CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND
 OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. FLUSH
 CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE WATER
 CLOSET.
  
 3. PROVIDE MSDS SHEETS ON ANY CHEMICALS THAT ARE BEING
 USED. PER WPB AMEND TO FBC 107.2.1
  
  