2019-03-08 08:24:28 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18111103 |
| 3/8/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) IN REFERENCE TO COMMENT #1 FROM THE 1ST REVIEW, THE |
| REQUESTED MSDS SHEETS FOR THE MATERIALS BEING TESTED |
| WERE NOT SUBMITTED. |
| |
| 2) IN REFERENCE TO COMMENT #5 FROM THE 1ST REVIEW, |
| PLEASE SUBMNIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| SLOW COOKER. |
| |
| 3) NEW COMMENT, SHEET M-1: SMOKE DETECTORS ARE REQUIRED |
| IN THE SUPPLY AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER |
| SECTION 606.2.1 FBC M. PLEASE NOTE THAT AN EXEMPTION |
| CAN BE APPLIED IF THE MANUFACTURER'S SPECIFICATIONS |
| INDICATE THE SYSTEMS ARE NOT CAPABLE OF PRODUCING OVER |
| 2000 CFMS OF SUPPLY AIR. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |