2019-03-07 12:31:38 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 18111103 |
| ADD: 901 NORTHWOOD PARKWAY, SUITE: 202-205 |
| CONT: TBD/ TO BE DETERMINED |
| TEL: 561-373-3902 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: 03/06/19 |
| ACTION: DENIED |
| |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| |
| |
| 1) OK. |
| |
| ORIGINAL COMMENT: |
| 2) THE LIFE SAFETY SHEET CHAPTER 10 SCHEDULE TYPICAL IS |
| TAKING CREDIT FOR FIRE SPRINKLERS, IF THE BUILDING IS |
| NOT FIRE SPRINKLERED THEN CORRECT THE FOLLOWING: |
| |
| 2A) OK. |
| 2B) OK. |
| 2C) OK. |
| |
| NEW COMMENT: |
| 2D) DEAD END CORRIDOR FOR UNSPRINKLERED BUILDING IS 20 |
| FEET NOT 25 FEET. REVISE AS REQUIRED. SEC. 1020.4 FBC. |
| ALSO, THERE IS NOT SEC. 1024.2 AS REFERENCED IN THE |
| LIFE SAFETY TABLE ON SHEET LS-1. |
| |
| ORIGINAL COMMENT: |
| 3) SHEET A-1 THE FLOOR PLAN: |
| |
| 3A) OK. |
| |
| 3B) OK. LAB EQUIPMENT INSTALLATION TO BE COORDINATED |
| WITH CHIEF BUILDING INSPECTOR. |
| |
| 2017 FBC-B 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE |
| PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE |
| MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR |
| ADDITIONS TO ANY BUILDING OR STRUCTURE. |
| |
| ORIGINAL COMMENT: |
| 3C) WALL TYPES: THE WALLS LABELED C-2 IN THE WALL |
| SCHEDULE ARE LABELED 1 HOUR FIRE WALLS: |
| |
| 3C)(1) OK. |
| 3C)(2) OK. |
| 3D) OK. |
| |
| ORIGINAL COMMENT: |
| 3E) AT THIS TIME THE OCCUPANCY OF THE LAB, CANNOT BE |
| DETERMINED THE USAGE WILL NEED TO BE BETTER DEFINED. |
| WHAT TYPES OF HAZARDOUS MATERIALS ARE TO BE USED IN THE |
| DAY TO DAY USAGE OF THE LAB. PLEASE PROVIDE AMOUNT OF |
| HAZARDOUS MATERIALS, IF THEY ARE SOLIDS, LIQUIDS, AND |
| OR GASEOUS MATERIALS( FC-B TABLE 307.1(1), IF THEY ARE |
| GOING TO BE STORED IN 1 HOUR FIRE RATED CABINETS, AND |
| IF THIS ROOM (LAB) IS TO BE CONSIDERED A 1 HOUR FIRE |
| CONTROL AREA IN COMPLIANCE WITH 2017 FBC-B SECTION |
| 414.2 THROUGH 414.4. PLEASE ALSO SUBMIT THE MSDS SHEETS |
| FOR ALL CHEMICALS TO BE USED IN THE DAILY PROCESS OF |
| THE LAB. A NARRATIVE FROM THE TENANT MAYBE OF HELP OF |
| WHAT WORK, OR PROCESS WILL OCCUR IN THE ROOM CONSIDERED |
| A LAB. |
| |
| RESPONSE: |
| PARTIALLY COMPLIED. TO AVOID CONFUSION AND TO BE CLEAR |
| THAT CONTROL AREAS ARE NOT REQUIRED. ARCHITECT TO |
| CLEARLY SPECIFY ON PLANS THE TYPE OF TESTING TO BE |
| PERFORMED IN THIS LAB . AND, ACKNOWLEDGE THAT HAZARDOUS |
| MATERIALS ARE NOT STORED OR HANDLED IN THIS LAB. ALSO, |
| NARRATIVE FROM THE DIRECTOR OF THE LAB NEEDS TO HAVE |
| THE SIGNATURE OF THE DIRECTOR. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| |
| 3F) AT THIS TIME IT IS UNCERTAIN IF THERE NEEDS TO BE |
| OCCUPANCY SEPARATION BETWEEN THE LAB AND THE EQUIPMENT |
| STORAGE ROOM. THE MAINTENANCE EQUIPMENT STORAGE ROOM IS |
| 284 SQUARE FEETLESS THAN 10% OF THE FLOOR AREA OF THE |
| BUILDING. IF PART OF THE CONTROL AREA, ADDITIONAL |
| COMMENTS MAY OCCUR UNDER THE MECHANICAL PLAN REVIEWER. |
| 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED. |
| |
| |
| 3G) OK. |
| |
| ORIGINAL COMMENT: |
| 3H)(1) SHEET A2 THE DOOR SCHEDULE INDICATES THE |
| OVERHEAD GARAGE DOOR IS BEING REPLACED, PLEASE PROVIDE |
| THE PRODUCT APPROVAL FOR THIS DOOR. COMPONENTS & |
| CLADDING. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| |
| (31)(A) EXTERIOR OVERHEAD GARAGE DOORS , |
| |
| RESPONSE: |
| PRODUCT APPROVAL NOT SUBMITTED AT THIS TIME. |
| THIS CAN BE A DEFERRED SUBMITTAL. |
| |
| |
| ORIGINAL COMMENT: |
| 3H)(2) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE |
| CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC. |
| |
| RESPONSE: |
| TO BE DONE AT TIME OF PRODUCT APPROVAL SUBMITTAL. |
| |
| |
| ORIGINAL COMMENT: |
| 3I) IN THE BREAK AREA/ COMMUNITY SPACE THERE IS A |
| BARRIER FREE ELECTRIC WATER COOLER AND REFERENCES THE |
| PLUMBING CODE SECTION 404.2. PLEASE NOTE THERE IS NO |
| 404.2 IN THE 2017 FBC-PLUMBING CODE. YOU DO HAVE TO |
| COMPLY WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION |
| 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING |
| FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN |
| SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING |
| FOUNTAIN SHALL COMPLY WITH 602.7. |
| |
| RESPONSE: |
| PLANS ARE NOT SHOWING DETAILS AND SPECIFICATIONS |
| SHOWING COMPLIANCE. PLANS ARE ONLY CITING SECTIONS OF |
| THE FBC- ACCESSIBILITY CODE. PROVIDE COMPLETE DETAILS |
| SHOWING COMPLIANCE. DON'T JUST CITE CODE SECTIONS. SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| |
| 3J) OK. |
| 3J)(1) OK. |
| 3J)(2) OK. |
| 3K) OK |
| 3K)(1) OK |
| 3K)(2)OK |
| 3K)(3) OK |
| 3K)(4)OK |
| 3L) OK |
| |
| ORIGINAL COMMENT: |
| 4A) BOTH THE M1 AND E1 BOTH SHOW NEW ROOF TOP UNITS |
| PLEASE PROVIDE PRODUCT APPROVAL FOR THE NEW ROOF TOP |
| CURB. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(G) ROOF TOP CURBS |
| |
| RESPONSE: |
| DEFERRED SUBMITTAL |
| |
| 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| RESPONSE: |
| DEFERRED SUBMITTAL |
| |
| |
| 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| BUILDING CODE, BUILDING. |
| 2017 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND |
| PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO |
| BE DESIGNED FOR WIND PRESSURES COMPONENTS AND |
| ATTACHMENTS. |
| |
| RESPONSE: |
| DEFERRED SUBMITTAL |
| |
| ORIGINAL COMMENT: |
| 5) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY WIND |
| DESIGN CRITERIA FOR THE REPLACEMENT OVERHEAD GARAGE |
| DOOR NOR THE ROOF TOP A/C UNITS. |
| |
| RESPONSE: |
| REVISE WIND DESIGN DATA ON SHEET A-2. ACCORDING TO SEC. |
| 1609.4 THIS BUILDING IS LOCATED IN EXPOSURE "C" NO |
| EXPOSURE "B". REVISE AS REQUIRED AND REVISE DESIGN |
| PRESSURES ACCORDINGLY. ALSO, PROVIDE THE SIZE OF THE |
| OVERHEAD GARAGE DOOR TO BE REPLACED TO VERIFY DESIGN |
| PRESSURES. |
| |
| 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 5.1. OK. |
| 5.2. OK. |
| 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. |
| RESPONSE: |
| REVISE WIND EXPOSURE |
| |
| 5.4. OK. |
| 5.5. OK. |
| |
| ORIGINAL COMMENT: |
| 6) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY |
| STRUCTURAL INFORMATION OF HOW THE ROOF TOP DECK IS TO |
| BE CUT NOR ROOF FRAMING TO BE STRENGTHEN FOR THE |
| ADDITIONAL WEIGHT AND POINT LOADING OF THE ROOF JOIST. |
| 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. |
| |
| RESPONSE: |
| PLANS STILL DON'T SHOW ANY STRUCTURAL INFORMATION ABOUT |
| THE ROOF TOP DECK PREPARATION TO RECEIVE THE NEW |
| ADDITIONAL LOAD OF THE A/C CONDENSER UNIT. IT DOESN'T |
| SPECIFY THE STRUCTURAL SUPPORTS. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 7) 2017 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL |
| BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF |
| HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE |
| ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR |
| OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN |
| SIDE IS LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR, |
| ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO |
| AS TO PREVENT THE PASSAGE OF A SPHERE 21 INCHES IN |
| DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30 |
| INCHES BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT, |
| FAN OR COMPONENT. |
| |
| RESPONSE: |
| PROVIDE EXACT LOCATION OF ROOF TOP UNIT. COORDINATE |
| WITH ITEM #6 ABOVE. |
| |
| 8) OK. |
| |
| |
| 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| |
| NEW COMMENT: |
| 10-THIS BUILDING IS NOT SPRINKLERED. ACCORDING TO |
| EXCEPTION #4 OF SEC. 1020.1 FBC THE CORRIDORS NEED TO |
| BE FIRE RATED IN ACCORDANCE WITH TABLE 1020.1. REVISE |
| PLANS AS REQUIRED TO COMPLY. |
| |
| |
| |