2019-01-15 07:29:53 | 1ST REVIEW: 18111103 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. A-1 THE NOTE UNDER THE ELECTRIC WATER COOLER IS |
| STATING CODE SECTION 404.2 FBC PLUMBING THIS SECTION |
| DOES NOT EXIST WATER COOLERS SHALL COMPLY WITH FBC PL |
| 410 AND FBC ACC 211, 602 PLEASE PROVIDE DETAILS SHOWING |
| COMPLIANCE WITH FBC ACC 602.2, 602.4, 602.5, 602.7, 306 |
| |
| 2. PLEASE SHOW COMPLIANCE WITH FBC ACC 694.6 FLUSH |
| CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC. HAND |
| OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309. FLUSH |
| CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE WATER |
| CLOSET. |
| |
| 3.PLEASE PROVIDE A DESCRIPTION OF THE FOLLOWING. PER |
| WPB AMEND TO FBC 107.2.1 |
| A) TYPE OF TESTING BEING DONE IN THE LAB. |
| B) THE TYPE OF CHEMICALS BEING USED. |
| C) THE AMOUNTS OF THE CHEMICALS THAT ARE BEING STORED. |
| D) HOW THE CHEMICALS ARE BEING STORED. |
| E) THE AMOUNT AND TYPE THAT IS BEING DISCHARGED TO THE |
| SANITARY. |
| |
| 4. PROVIDE MSDS SHEETS ON ANY CHEMICALS THAT ARE BEING |
| USED. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. PLEASE SHOW THE DIMENSIONS ON THE CLEAR FLOOR SPACES |
| FOR THE TOILET LAVATORY AND WATER FOUNTAIN. PER FBC ACC |
| 604.3.1, 602.2, 606.2 |
| |
| 6. SHT P-2 UNDER THE THE NOTES AT THE BOTTOM OF THE |
| PLAN SHEET #2 IS REFERENCING CODE SECTION FBC 2318.15 |
| AND 2510.5.11 THAT DO NOT EXIST OR DO NOT APPLY TO |
| PLUMBING FIXTURE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 7. SHT P-2 UNDER THE THE NOTES AT THE BOTTOM OF THE |
| PLAN SHEET #3 IS REFERENCING CODE SECTION FBC PL 424.4 |
| THAT APPLIES TO GANG SHOWERS THERE ARE NO SHOWERS SHOWN |
| ON PLAN PLEASE CLARIFY . PER WPB AMEND TO FBC 107.2.1 |
| |
| 8. SHT. P-2 THE PLUMBING FIXTURE SCHEDULE IS LISTING A |
| DROP IN LAVATORY SINK THE PLANS SHOW A WALL HUNG IF THE |
| DROP IN IS BEING USED PROVIDE DETAIL OF VANITY TOP |
| COMPILING WITH FBC ACC 606.2 AND 606.3 |
| OR REVISE PLUMBING SCHEDULE TO LIST WALL HUNG LAVATORY. |
| |
| 9. THE FLOOR DRAIN IN THE LAB ARE NOT VENTED ON THE |
| SANITARY ISOMETRIC SHALL COMPLY WITH FBC PL 901.2, 919 |
| |
| 10. A BACKFLOW DEVISE IS REQUIRED FOR THE REFRIGERATOR |
| ICE MAKER A NOTE ON THE PLAN WILL SUFFICE. PER FBC PL |
| 608.3 |
| |
| 11. PLEASE INDICATE ON THE PLAN THE LEVEL OF ALTERATION |
| PER FBC EXISTING CH5 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |