Plan Review Notes
Plan Review Notes For Permit 18111103
Permit Number 18111103
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-12-03 14:57:02THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
  
 1) SHEET A 1 - THERE IS AN INDICATION OF A LAB;
 HOWEVER, THERE IS NO INDICATION OF WHAT THIS LAB IS
 BEING USED FOR.
  
 PLEASE PROVIDE DETAIL INFORMATION OF THE TYPE OF WORK
 PERFORMED WITHIN THIS LAB..
  
  
  
  
 2) SHEET CS 1 - THERE ARE INDICATIONS OF SEPARATE
 OCCUPANCY LOADS; HOWEVER, THERE IS NO OCCUPANCY
 CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE.
  
 PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION AND WHETHER
 IT IS MIXED OR SEPARATED. (IT APPEARS TO BE SPEPARATED
 ON SHEET A 1, NEED FOR CLARIFICATION PURPOSES)
  
  
  
  
 3) SHEET A 1 - THERE IS AN INDICATION OF OVEN WITHIN
 THE LAB ROOM. THERE IS NO INDICATION OF WHAT THIS OVEN
 IS USED FOR AND OR ANY VENTING REQUIREMENTS.
  
 PLEASE PROVIDE DETAILS.
  
 ANY PROPOSED VENTING SHALL BE PER NFPA 96 AND UNDER
 SEPARATE SHOP DRAWINGS. PROVIDE AN APPLICABLE NOTE.
  
  
  
  
 4) SHEET A 1 - 1 HOUR FIRE WALLS ARE INDICATED AROUND
 THE LAB ROOM. PER # 2 ABOVE WHAT IS THE REQUIRED RATING
 OF THE SEPARATION OF OCCUPANCIES. IT MAY BE 2 HOURS.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH APPLICABLE
 FIRE CODE REFERNECES.
  
  
  
  
 5) SHEET A 1 - C2 RATED WALLS ARE INDICATED AROUND THE
 LAB, HOWEVER, AT THE BATHROOM AREA THE RATING STOPS AT
 THE DOOR EXPOSING THE INTERIOR OF THE BATHROOMS TO THE
 HAZARD.
  
 THE BATHROOM WALLS ARE REQUIRED TO BE HAVE THIS RATING.
 FOR DISSCUSSION PURPOSES, THE OUTSIDE BATHROOM WALLS
 INCLUDING THE DOORS WOULD NOT BE REQUIRED TO BE RATED.
 THE RATING WOULD STOP AT THE WALLS DIRECTLY IN CONTACT
 WITH THE LAB.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 6) SHEET A 1 - THERE IS AN INDICATION OF B2 WALLS (BY
 DOOR 21) THAT APPEAR TO REQUIRE C2 RATINGS.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH FIRE CODE
 REFERENCES.
  
  
  
  
 7) SHEET A 1 - THERE ARE INDICATIONS OF B WALLS AROUND
 THE ELECTRIC ROOM. THERE IS NO CALL OUT FOR B WALLS. IN
 ADDITION, THERE WALLS APPEAR TO REQUIRE C2 RATINGS.
  
 PLEASE REIVEW AND CORRECT OR JUSTIFY WILL FIRE CODE
 REFERENCES.
  
  
  
  
 8) SHEET A 2 - THE DOOR SCHEDULE HAS INDICATIONS OF C
 LABELS.
  
 FOR CLARIFICATION PURPOSES PLEASE PROVIDE FIRE RATING
 TIME FOR THESE DOORS PER THE FFPC AND ENSURE THE ARE IN
 COMPLIANCE WITH ANY CHANGES TO # 2 & 4.
  
  
  
  
 9) SHEET E 2 - THERE ARE TWO (2) EXITS INDICATED FOR
 THE LAB AREA. BASED ON THE CLASSIFICATION OF THIS
 OCCUPANCY AND BEING SEPARATED FOR THE OTHER
 OCCUOPANCIES, THESE TWO (2) EXITS MAY BE REQUIRED PER
 THE FFPC TO BE SEPARATED BY 1/2 THE DIAGONAL OF THE
 SPACE SERVED.
  
 THESE EXITS APPEAR TO TOO CLOSE TO EACH OTHER TO MEET
 THIS REQUIREMENT.
  
 PER NFPA 101, CHAPTER 7,
  
 7.5.1.3.2* WHERE TWO EXITS, EXIT ACCESSES, OR EXIT
 DISCHARGES ARE
 REQUIRED, THEY SHALL BE LOCATED AT A DISTANCE FROM ONE
 ANOTHER NOT
 LESS THAN ONE-HALF THE LENGTH OF THE MAXIMUM OVERALL
 DIAGONAL
 DIMENSION OF THE BUILDING OR AREA TO BE SERVED,
 MEASURED IN A
 STRAIGHT LINE BETWEEN THE NEAREST EDGE OF THE EXITS,
 EXIT ACCESSES, OR
 EXIT DISCHARGES, UNLESS OTHERWISE PROVIDED IN 7.5.1.3.3
 THROUGH
 7.5.1.3.5..
  
  
  
 PLEASE REVIEW THE OCCUPANCY OF THE LAS PER THE FFPC AND
 THE REQUIRED EIXTING AND CORRECT IF APPLICABLE.
  
  
  
 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 11) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  