Plan Review Notes
Plan Review Notes For Permit 18111103
Permit Number 18111103
Review Stop B
Sequence Number 1
Notes
Date Text
2019-01-03 13:34:462017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 18111103
 ADD: 901 NORTHWOOD PARKWAY, SUITE: 202-205
 CONT: TBD/ TO BE DETERMINED
 TEL: 561-373-3902
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JAN. 03/2019
 ACTION: DENIED
  
 1) THE COVERSHEET CS-1 AND LIFE SAFETY SHEET LS-1 BOTH
 INDICATE THIS BUILDING IS UNSPRINKLERED. THE LIFE
 SAFETY SHEET CHAPTER 10 SCHEDULE TYPICAL: INDICATES THE
 FIRE SPRINKLER SYSTEM 100%. PLEASE CORRECT THE
 DISCREPANCY BETWEEN THE BUILDING BEING FIRE SPRINKLERED
 AND UNSPRINKLERED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) THE LIFE SAFETY SHEET CHAPTER 10 SCHEDULE TYPICAL IS
 TAKING CREDIT FOR FIRE SPRINKLERS, IF THE BUILDING IS
 NOT FIRE SPRINKLERED THEN CORRECT THE FOLLOWING:
  
 2A) COMMON PATH OF TRAVEL IS TAKEN AT 100 FEET,
 ASSEMBLY & BUSINESS OCCUPANCY, OCCUPANT LOAD OF 97 AND
 UNSPRINKLERED THE COMMON PATH OF TRAVEL IS 75 FEET.
 2017 FBC-B TABLE 1006.2.1.
  
 2B) TRAVEL DISTANCE IS LISTED AT 300 FEET PER FBC-B
 TABLE 1017.2 FOR ASSEMBLY AND BUSINESS IS AGAIN FOR A
 FIRE SPRINKLERED BUILDING SEE TABLE 1017.2 OF THE
 FBC-B.
  
 2C) THE EXIT SEPARATION DISTANCE IS ALSO TAKEN AT 1/3RD
 THE OVERALL DIAGONAL DISTANCE OF THE BUILDING WHICH IS
 AN EXCEPTION FOR FIRE SPRINKLERED BUILDINGS. IF THE
 BUILDING IS NOT FIRE SPRINKLERED THEN THE FBC-B SECTION
 1007.1.1 WOULD REQUIRE THE DIAGONAL DISTANCE TO BE ? OF
 THE OVERALL DIAGONAL DISTANCE.
  
 3) SHEET A-1 THE FLOOR PLAN:
  
 3A) PLEASE NOTE THE PHASE I/ PHASE II LABELING ON THE
 LEFT SIDE OF THE PLAN, CENTER OF THE PLAN ARE THE SAME
 WITH THE LAB AS PART OF PHASE L. JUST TO THE RIGHT OF
 THE LAB AND MAINTENANCE EQUIPMENT STORAGE ROOM THE
 LABELING FOR THE PHASING IS REVERSED. PLEASE CORRECT
 THE DISCREPANCY IN THE LABELING FOR THE PHASING PLAN.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3B) PLEASE PROVIDE IS THE INTENT OF PHASING OCCUPYING
 THE LAB AND EQUIPMENT STORAGE ROOM BEFORE THE OFFICES
 ARE OCCUPIED? AS SHOWN THE RESTROOMS ARE IN THE PHASE
 LL PART OF THE PHASING PLAN, WILL THERE BE TEMPORARY
 WALLS FOR EMPLOYEES TO BE ABLE TO GO TO THE RESTROOMS
 WITHOUT GOING THROUGH A CONSTRUCTION.
  
 2017 FBC-B 3302.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 REQUIRED EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE
 PROTECTION DEVICES AND SANITARY SAFEGUARDS SHALL BE
 MAINTAINED AT ALL TIMES DURING ALTERATIONS, REPAIRS OR
 ADDITIONS TO ANY BUILDING OR STRUCTURE.
  
 3C) WALL TYPES: THE WALLS LABELED C-2 IN THE WALL
 SCHEDULE ARE LABELED 1 HOUR FIRE WALLS:
  
 3C)(1) THE WALLS THAT SURROUND THE LAB ARE WALLS
 SEPARATING WHAT MOST LIKELY WILL BE A CONTROL AREA FROM
 OTHER OCCUPANCIES AND ARE TO BE IDENTIFIED AS FIRE
 BARRIERS SEE 2017 FBC-B SECTION 707.3.8.
  
 3C)(2) THERE ARE ADDITIONAL WALLS IDENTIFIED AS C-2
 TYPE WALLS BETWEEN THE OPEN OFFICE AND THE OFFICES TO
 THE RIGHT OF THIS WALL AND CONFERENCE ROOM. THIS WALL
 DOES NOT NEED TO BE FIRE RATED. THE DESIGNER OF RECORD
 HAS LABELED THIS WALL AS AN 1 HOUR FIRE WALL. THE FBC-B
 TABLE 706.4 THERE IS NO 1 HOUR FIRE WALL RATING
 SEPARATING OCCUPANCIES.
  
 3D) IN THE CENTER OF THE PLAN THERE IS A ROOM LABELED A
 LAB. PLEASE NOTE DEFINING AN AREA AS A LAB IS A VERY
 BROAD IN DETERMINING CODE COMPLIANCE. THE QUESTION IS
 IT APPEARS THE DESIGNER OF RECORD IS TRYING TO ENCLOSE
 THE LAB AND EQUIPMENT STORAGE ROOM (HIGHER HAZARD
 OCCUPANCY) WITH 1 HOUR FIRE RATED WALLS. THE 4
 RESTROOMS ARE ALSO INCLUDED IN THE 1 HOUR FIRE RATED
 WALL ASSEMBLY. THIS MEANS THE ASSEMBLY AND BUSINESS
 OCCUPANCIES ARE GOING INTO A MORE HAZARDOUS OCCUPANCY
 TO USE THE RESTROOMS. IT WOULD APPEAR THE DESIGN
 PROFESSIONAL?S INTENT WAS TO HAVE THE 1 HOUR FIRE
 RATING BEHIND THE REAR RESTROOM WALLS TO ALLOW THE
 OCCUPANTS FROM THE ASSEMBLY AND BUSINESS OCCUPANCY TO
 USE THE 4 RESTROOMS. SEE 2017 FBC-B TABLE 508.4.
  
 3E) AT THIS TIME THE OCCUPANCY OF THE LAB, CANNOT BE
 DETERMINED THE USAGE WILL NEED TO BE BETTER DEFINED.
 WHAT TYPES OF HAZARDOUS MATERIALS ARE TO BE USED IN THE
 DAY TO DAY USAGE OF THE LAB. PLEASE PROVIDE AMOUNT OF
 HAZARDOUS MATERIALS, IF THEY ARE SOLIDS, LIQUIDS, AND
 OR GASEOUS MATERIALS( FC-B TABLE 307.1(1), IF THEY ARE
 GOING TO BE STORED IN 1 HOUR FIRE RATED CABINETS, AND
 IF THIS ROOM (LAB) IS TO BE CONSIDERED A 1 HOUR FIRE
 CONTROL AREA IN COMPLIANCE WITH 2017 FBC-B SECTION
 414.2 THROUGH 414.4. PLEASE ALSO SUBMIT THE MSDS SHEETS
 FOR ALL CHEMICALS TO BE USED IN THE DAILY PROCESS OF
 THE LAB. A NARRATIVE FROM THE TENANT MAYBE OF HELP OF
 WHAT WORK, OR PROCESS WILL OCCUR IN THE ROOM CONSIDERED
 A LAB.
  
 3F) AT THIS TIME IT IS UNCERTAIN IF THERE NEEDS TO BE
 OCCUPANCY SEPARATION BETWEEN THE LAB AND THE EQUIPMENT
 STORAGE ROOM. THE MAINTENANCE EQUIPMENT STORAGE ROOM IS
 284 SQUARE FEETLESS THAN 10% OF THE FLOOR AREA OF THE
 BUILDING. IF PART OF THE CONTROL AREA, ADDITIONAL
 COMMENTS MAY OCCUR UNDER THE MECHANICAL PLAN REVIEWER.
 107.2.1.2. ADDITIONAL INFORMATION IS REQUIRED.
  
 3G) THERE ARE 8 DOORS ON SHEET A2 THE DOOR SCHEDULE
 THAT ARE LABELED C LABELED DOORS. PLEASE NOTE THESE
 DOORS ARE 12, 13, 14, 18, 19, 20, 21, & 38. IN THE 2017
 FBC-B THE RATING OF FIRE RATED DOORS IS IN MINUTES AND
 IN HOURS, PLEASE SEE FBC-B TABLE 716.5 FOR THE FIRE
 RATING FOR FIRE BARRIERS AND FIRE PARTITIONS AND DOOR
 RATING.
 3H)(1) SHEET A2 THE DOOR SCHEDULE INDICATES THE
 OVERHEAD GARAGE DOOR IS BEING REPLACED, PLEASE PROVIDE
 THE
 PRODUCT APPROVAL FOR THIS DOOR. COMPONENTS & CLADDING.
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR OVERHEAD GARAGE DOORS ,
  
 3H)(2) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE
 CODE RULE 61G20 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 3I) IN THE BREAK AREA/ COMMUNITY SPACE THERE IS A
 BARRIER FREE ELECTRIC WATER COOLER AND REFERENCES THE
 PLUMBING CODE SECTION 404.2. PLEASE NOTE THERE IS NO
 404.2 IN THE 2017 FBC-PLUMBING CODE. YOU DO HAVE TO
 COMPLY WITH THE 2017 FBC-ACCESSIBILITY CODE SECTION
 211.2 MINIMUM NUMBER. NO FEWER THAN TWO DRINKING
 FOUNTAINS SHALL BE PROVIDED. ONE DRINKING FOUNTAIN
 SHALL COMPLY WITH 602.1 THROUGH 602.6 AND ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.7.
  
 3J) SHEET A-1 IN THE BREAK ROOM THERE IS SHOWN 2
 MICROWAVES BUT IN THE DETAIL 2/ A-3 THEY ARE NOT SHOWN?
 THERE IS 2 OPEN SHELVES NOTE # 10. ON THE ELECTRIC
 SHEET E-1 IN THIS SAME AREA SHOWS 2 GFCI 20 AMP
 RECEPTACLES AT 64 INCHES OFF THE FLOOR. PLEASE NOTE IF
 THE MICROWAVES ARE LOCATED ON THE OPEN SHELVES THEY
 WILL NEED TO SHOW HOW THEY COMPLY WITH:
  
 3J)(1) 308 REACH RANGES. 308.2 FORWARD REACH./ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 3J)(2) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308.
 309.4 OPERATION. OPERABLE PARTS SHALL BE OPERABLE WITH
 ONE HAND AND SHALL NOT REQUIRE TIGHT GRASPING,
 PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED
 TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS (22.2 N)
 MAXIMUM.
  
 3K) THE LS-1 SHEET NOR THE A-1 SHEET SHOW ANY TABLES OR
 CHAIRS IN THE COMMUNITY SPACE WHEREAS THE E1, M1 AND P1
 SHEETS ALL SHOW TABLES AND CHAIRS. PLEASE SHOW
 COMPLIANCE WITH THE 2017 ACCESS. CODE:
  
 3K)(1) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 3K)(2) 226.2 DISPERSION. DINING SURFACES AND WORK
 SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 3K)(3) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, INCLUDING RAISED OR
 SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 3K)(4) 902.1 .DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS.
  
 3L) THE BOTTOM OF SHEET A-1 THERE IS A NOTE FOR
 ALTERNATE PRICING. THE WEST PALM BEACH CHAPTER 1
 ADMINISTRATION SECTION 107.2.1 DOES NOT ALLOW FOR
 ALTERNATES. 2017 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.
 W.P.B. ADMINISTRATIVE CODE/2017 DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR
 IN PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC INFORMATION".
  
 4A) BOTH THE M1 AND E1 BOTH SHOW NEW ROOF TOP UNITS
 PLEASE PROVIDE PRODUCT APPROVAL FOR THE NEW ROOF TOP
 CURB. 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(G) ROOF TOP CURBS
  
 4B) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 4C) 2017 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING.
 2017 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
  
 5) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY WIND
 DESIGN CRITERIA FOR THE REPLACEMENT OVERHEAD GARAGE
 DOOR NOR THE ROOF TOP A/C UNITS.
  
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 5.2. RISK CATEGORY.
  
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6) THE ARCHITECTURAL SHEETS DOES NOT PROVIDE ANY
 STRUCTURAL INFORMATION OF HOW THE ROOF TOP DECK IS TO
 BE CUT NOR ROOF FRAMING TO BE STRENGTHEN FOR THE
 ADDITIONAL WEIGHT AND POINT LOADING OF THE ROOF JOIST.
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED.
  
 7) 2017 FBC-B 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL
 BE PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF
 HATCH OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE
 ARE LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR
 OPEN SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN
 SIDE IS LOCATED MORE THAN 30 INCHES ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO PREVENT THE PASSAGE OF A SPHERE 21 INCHES IN
 DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES BEYOND EACH END OF SUCH APPLIANCE, EQUIPMENT,
 FAN OR COMPONENT.
  
 8) 2017 FBC-B 1013.7 ROOF ACCESS. GUARDS SHALL BE
 PROVIDED WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN
 10 FEET OF A ROOF EDGE OR OPEN SIDE OF A WALKING
 SURFACE AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN
 30 INCHES ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE
 GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE
 OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER