2019-02-22 18:24:03 | NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| NOTES: |
| ***(1) BUILDING WILL BE APPROVED WITH PROVISO ONCE THE |
| STRUCTURAL ENGINEER UPDATES THE ENGINEERING FIRM |
| CERTIFICATE OF AUTHORIZATION. ACCORDING TO DBPR WEBSITE |
| THE CERTIFICATE OF AUTHORIZATION #8495 IS NULL AND |
| VOID. THE ENGINEER REMOVED THE ENGINERING FIRM NAME BUT |
| THE FIRM CERTIFICATE OF AUTHORIZATION #8495 IS SHOWN ON |
| THE TITLE BLOCK. REVISE AS REQUIRED. |
| CHAPTER 471 F.S. |
| |
| ***(2) DIGITAL SIGNATURE ON DRAWING S-1.0 IS INVALID. |
| THERE IS AN ERROR ON THE SIGNATURE VERIFICATION. PLEASE |
| REVISE. |
| |
| |
| |
| |
| 1- OK |
| |
| 2- |
| |
| 3- OK |
| |
| 4- OK |
| |
| 5- ENERGY CALCULATIONS: NEED TO PROVIDE THE ENERGY |
| CALCULATIONS FOR THE MAIN HOUSE. ONLY THE ENERGY |
| CALCULATIONS FOR THE GUEST SUITE WERE SUBMITTED. SEC. |
| R101.5.1 FBC-ENERGY CONSERVATION. |
| RESPONSE: |
| ONLY THE COVER PAGE SIGNED BY THE OWNER/AGENT WAS |
| PROVIDED. MISSING THE REST OF THE REPORT. UNABLE TO |
| REVIEW. |
| |
| NOTE: |
| LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS |
| ARE NOT USING THE DEFAULT FACTOR. |
| |
| 6- OK |
| |
| 7- OK |
| |
| 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| |
| A) INSWING ARCHED ENTRY DOOR SIZE AS SHOWN ON PLANS. |
| RESPONSE: |
| FLORIDA PRODUCT APPROVAL FL15001.2 SUBMITTED IS NOT FOR |
| INSWING DOOR AND SIZE DOESN'T MATCH SPECIFIED SIZE. |
| |
| B) OK. |
| |
| C) OK |
| |
| D) OK. |
| |
| E) OK. . |
| |
| F)POLYSTICK TU-PLUS FLORIDA PRODUCT APPROVAL FL5259-R10 |
| SUBMITTED IS TOO OLD. PROVIDE CURRENT FLORIDA PRODUCT |
| APPROVAL OR MIAMI -DADE NOA. AND CLEARLY IDENTIFY WHICH |
| ASSEMBLY IS GOING TO BE USED TO VERIFY DESIGN PRESSURES |
| LIMITATIONS. . |
| |
| G) OK. |
| |
| H)OK |
| |
| 9- OK |
| |
| 10- OK |
| |
| 11-OK |
| |
| 12- OK |
| |
| 13- OK. |
| |
| 14- OK |
| |
| 15- OK |
| |
| 16-OK |
| |
| 17- STRUCTURAL ENGINEER NEEDS TO HAVE A CURRENT |
| ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION. SEC. |
| 61G15-23.002 AND CHAPTER 471 F.S. COORDINATE WITH DBPR. |
| |
| RESPONSE: |
| REPEAT COMMENT: ACCORDING TO DBPR CERTIFICATE OF |
| AUTHORIZATION #8495 FOR THE ENGINEERING COMPANY IS NOT |
| VALID. ENGINEER TO UPDATE INFORMATION WITH DBPR. |
| OTHERWISE, IT WILL BE REPORTED TO THE BOARD OF |
| ENGINEERS AND DBPR. |
| |
| 18- SHEET A-14: PROVIDE COMPLETE DETAILS AND |
| SPECIFICATIONS FOR THE CONSTRUCTION OF THE PRIVACY |
| WALLS AND GATES. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| NEED TO PROVIDE ADDITIONAL FOOTING DETAIL WHEN THE WALL |
| IS LOCATED AT THE PROPERTY LINE. FOOTING CAN NOT |
| ENCROACH BEYOND THE PROPERTY LINE. |
| |
| 19- OK |
| |
| 20- OK |
| |
| *** NEED SOIL TEST REPORT DIGITAL SIGNATURE OR HARD |
| COPY WITH ORIGINAL SIGNATURE |
| |
| |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| |