| 1ST REVIEW: DENIED |
| GAS COMMENTS |
| GAS PLAN NOT SUPPLIED. IS GAS SERVICE AVAILABLE THAT |
| WILL SUPPORT THE REQUIREMENTS OF THE RESIDENCE? A |
| SEPERATE PERMIT WILL BE REQUIRED FOR THE GAS. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES |
| G2413.4.1, G2413.4.2. |
| 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL |
| PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE |
| CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR |
| EACH PIPE SIZE. WPB FBC 107.2.1. |
| 3. TYPE OF GAS (LP OR NATURAL). WPB FBC 107.2.1. IF |
| NATURAL, SHOW METER LOCATION ON THE PLAN. IF LP PROVIDE |
| THE FOLLOWING: |
| A. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2. |
| B. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE |
| GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED |
| PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA |
| 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED |
| PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK |
| SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT |
| WIND LOAD PER THE FLORIDA BUILDING CODE. |
| 4.LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU |
| LOAD ON THE SYSTEM. REFER TO THE FBC RES SEC. G2413.3, |
| G2413.4 AND TABLES G2413.4 (1) THROUGH G2413.4(21). |
| 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND / OR SYSTEM PER THE FBC RES |
| SEC. G 2413.4.1, G2413.4.2. |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| ON THE PLAN PER FBC RES SEC. G2413.2, G2413.4.3. |
| 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC RES |
| SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED AND |
| LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FBC RES SEC.G2408.1. |
| 8. SHOW THE LOCATION OF THE TANKLESS WATER HEATER AND |
| THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR |
| WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION |
| OF THE WATER HEATER SHALL COMPLY WITH THE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB FBC |
| 107.2.1 |
| 9. PROVIDE APPLICABLE SIZING TABLES USED TO SIZE THE |
| GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS |
| SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR |
| OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS |
| SYSTEM. REFER TO THE FBC RES SEC. G2413.3, G2412.8, |
| G2413.1, G2413.2, & G2413.3. |
| 10. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS WHEN APPLICABLE. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION. FBC RES SEC. |
| G2421.1. |
| 11. I HAVE NOTED THREE (3) TANKLESS WATER HEATERS ON |
| PLAN SHEET P.01; PLAN SHEET E.03 INDICATES A GAS RANGE, |
| A BBQ GRILL (GAS?). ADDITIONALLY A FUTURE GENERATOR IS |
| SHOWN ON PLAN SHEET A.02 AS WELL AS E.01 AND E.03. |
| INDICATE ALL GAS FIRED APPLIANCES AND EQUIPMENT, PIPING |
| DIAGRAMS, CALCULATIONS, ETC. IN AN ORDERLY WAY ON THE |
| PLANS. WPB FBC 107.2.1. |
| 12. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY |
| AHEAD OF EACH MP REGULATOR. FBC RES SEC. G 2420.4 |
| 13. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| G2421.1. |
| 14. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC |
| RES SEC. G 2407.1 AND G2439.4 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| |