Plan Review Notes
Plan Review Notes For Permit 18111079
Permit Number 18111079
Review Stop G
Sequence Number 1
Notes
Date Text
2019-01-03 13:01:53FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW: DENIED
 GAS COMMENTS
 GAS PLAN NOT SUPPLIED. IS GAS SERVICE AVAILABLE THAT
 WILL SUPPORT THE REQUIREMENTS OF THE RESIDENCE? A
 SEPERATE PERMIT WILL BE REQUIRED FOR THE GAS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER FBC RES
 G2413.4.1, G2413.4.2.
 2. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING (IF APPLICABLE) FOR
 EACH PIPE SIZE. WPB FBC 107.2.1.
 3. TYPE OF GAS (LP OR NATURAL). WPB FBC 107.2.1. IF
 NATURAL, SHOW METER LOCATION ON THE PLAN. IF LP PROVIDE
 THE FOLLOWING:
 A. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER NFPA 58, TABLE 3-2.2.2.
 B. CLEARLY INDICATE ON THE PLAN IF THE LP TANK IS ABOVE
 GROUND OR BELOW GROUND, AND SHOW THE METHOD OF REQUIRED
 PROTECTION FOR THE LP TANK AND APPURTENANCES PER NFPA
 58. IF THE TANK IS BELOW GROUND IT SHALL BE ANCHORED
 PER NFPA 58 SEC.3-2.2.7 (H). IF ABOVE GROUND, THE TANK
 SHALL BE SECURELY ANCHORED TO WITHSTAND 170 MPH ULT
 WIND LOAD PER THE FLORIDA BUILDING CODE.
 4.LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU
 LOAD ON THE SYSTEM. REFER TO THE FBC RES SEC. G2413.3,
 G2413.4 AND TABLES G2413.4 (1) THROUGH G2413.4(21).
 5. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND / OR SYSTEM PER THE FBC RES
 SEC. G 2413.4.1, G2413.4.2.
 6. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER FBC RES SEC. G2413.2, G2413.4.3.
 7. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND FBC RES
 SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC RES SEC.G2408.1.
 8. SHOW THE LOCATION OF THE TANKLESS WATER HEATER AND
 THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS OR
 WINDOWS IN RELATION TO THE WATER HEATER. THE LOCATION
 OF THE WATER HEATER SHALL COMPLY WITH THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS. WPB FBC
 107.2.1
 9. PROVIDE APPLICABLE SIZING TABLES USED TO SIZE THE
 GAS SYSTEM OR PLACE A NOTE ON THE PLANS/DRAWINGS
 SPECIFYING WHICH SIZING TABLE(S) FROM THE GAS CODE OR
 OTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS GAS
 SYSTEM. REFER TO THE FBC RES SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 10. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS WHEN APPLICABLE. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION. FBC RES SEC.
 G2421.1.
 11. I HAVE NOTED THREE (3) TANKLESS WATER HEATERS ON
 PLAN SHEET P.01; PLAN SHEET E.03 INDICATES A GAS RANGE,
 A BBQ GRILL (GAS?). ADDITIONALLY A FUTURE GENERATOR IS
 SHOWN ON PLAN SHEET A.02 AS WELL AS E.01 AND E.03.
 INDICATE ALL GAS FIRED APPLIANCES AND EQUIPMENT, PIPING
 DIAGRAMS, CALCULATIONS, ETC. IN AN ORDERLY WAY ON THE
 PLANS. WPB FBC 107.2.1.
 12. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS.
 A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY
 AHEAD OF EACH MP REGULATOR. FBC RES SEC. G 2420.4
 13. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
 14. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE FBC
 RES SEC. G 2407.1 AND G2439.4
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  