2018-12-20 17:49:15NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 FBC R 401.3 (DRAINAGE)
 FBC 107.2.5 (SITE PLAN)
 FBC 110.9 (IMPACT OF CONSTRUCTION)
  
 SEC. R401.3 FBC_RESIDENTIAL:
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED
 WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY
 A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF
 NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE,
 DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES
 AND THE PROPOSED FINISHED GRADES, DEPICTING THE
 PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD
 AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT
 SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF
 DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE
 DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING
 STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE
 SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO
 WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN
 THE
 APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR
 WHEN OTHERWISE WARRANTED.
  
 SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS
 OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A
 SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY
 PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE
 DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION,
 PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY
 INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON
 COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A
 LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE
 INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL
 INSPECTION.
  
 2- PROVIDE PLANS WITH COUNTY IMPACT FEES STAMP AND
 PROVIDE COPY OF PAID RECEIPT ( $21.91).
  
 3- IT LOOKS LIKE SECOND FLOOR BEDROOM WINDOWS DON'T
 COMPLY WITH THE EMERGENCY ESCAPE AND RESCUE OPENINGS
 SEC. R310.2.1 FBC-RESIDENTIAL. WINDOW SCHEDULE SPECIFY
 5'-0" HIGH WINDOWS. TYPICALLY, 5-0" HIGH WINDOWS DON'T
 PROVIDE THE 24" CLEAR OPENING HEIGHT. PROVIDE
 MANUFACTURER'S CUT SHEETS SHOWING THAT SPECIFIED WINDOW
 SIZE PROVIDES 24" CLEAR OPENING AND MIN. TOTAL CLEAR
 OPENING OF 5.7S.F.
 NOTE: CLEARLY SPECIFY ALL WINDOW TYPES IN THE WINDOW
 SCHEDULE TO AVOID CONFLICT/DELAYS.
  
 4- SPECIFY WINDOW SILL HEIGHT OF SECOND FLOOR OPERABLE
 WINDOWS TO VERIFY COMPLIANCE WITH THE WINDOW FALL
 PROTECTION AS REQUIRED BY SEC. R312.2 FBC-RESIDENTIAL.
  
 5- ENERGY CALCULATIONS: NEED TO PROVIDE THE ENERGY
 CALCULATIONS FOR THE MAIN HOUSE. ONLY THE ENERGY
 CALCULATIONS FOR THE GUEST SUITE WERE SUBMITTED. SEC.
 R101.5.1 FBC-ENERGY CONSERVATION.
  
 6- GUEST SUITE ENERGY CALCULATIONS SUBMITTED:
 A)THE ENERGY FORM R405-2017 IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM BY THE OWNER OR OWNER?S LEGALLY
 DESIGNATED AGENT AS REQUIRED BY SEC. R103.1.1.2
 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 C) NUMBER OF BEDROOMS IS INCORRECT. THIS IS THE GUEST
 SUITE. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 D) NEED INSULATION IN FLOOR ABOVE GARAGE AS REQUIRED BY
 SEC. R402.1.2 FBC-ENERGY CONSERVATION. REVISE ITEM #8.
  
 E) ROOF MATERIAL SPECIFIED IS INCORRECT. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 F)WINDOWS ORIENTATION AND AREA DON'T MATCH ACTUAL
 ORIENTATION AND AREA SHOWN ON PLANS. REVISE AS REQUIRED
 TO MATCH. SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G) WINDOWS OVERHANG SEPARATION DOESN'T MATCH PLANS.
 REVISE AS REQUIRED TO MATCH. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 H) PROVIDE WINDOWS AND DOORS MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS ON ITEM #7 AS
 REQUIRED BY SEC. R405.4.3 FBC-ENERGY CONSERVATION.
 NOTE: COORDINATE WITH PLANS AND PRODUCT APPROVALS
 SUBMITTED TO AVOID CONFLICTS/DELAYS.
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS
 ARE NOT USING THE DEFAULT FACTOR.
  
 7- DESIGNER OF RECORD TO SPECIFY INSULATION IN FLOOR
 ABOVE GARAGE AS REQUIRED BY SEC. R402.1.2 FBC-ENERGY
 CONSERVATION AND SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 8-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL)
  
 A) INSWING ARCHED ENTRY DOOR AS SHOWN ON PLANS.
  
 B) PROVIDE FLORIDA PRODUCT APPROVAL COVER THAT
 CORRESPONDS TO DRAWINGS SUBMITTED FOR THE FRENCH DOOR.
  
 C) FRENCH DOORS WITH SIDELITES AS SHOWN ON PLANS.
  
 D) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY
 SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE
 WITH THE CALCULATED DESIGN PRESSURES.
  
 E) METAL ROOF AS SHOWN ON PLANS.
  
 F)ROOF UNDERLAYMENT NOA SUBMITTED: CLEARLY MARK WHICH
 UNDERLAYMENT IS GOING TO BE USED FOR THE CLAY TILE AND
 WHICH ONE IS GOING TO BE USED FOR THE METAL ROOF SHOWN
 AS SHOWN ON PLANS.
  
 G) SHUTTERS SHOWN ON EXTERIOR ELEVATIONS AND PROVIDE
 COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE.
  
 H)ALL SIMPSON AND USP STRUCTURAL CONNECTORS SPECIFIED
 ON PLANS AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR OR DESIGNER OF RECORD TO LIST THE FLORIDA
 PRODUCT APPROVAL NEXT TO THE SPECIFIED CONNECTOR.
  
 9- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 10- SPECIFY ON PLANS CARBON MONOXIDE ALARMS BY FIRST
 AND SECOND FLOOR BEDROOMS AS REQUIRED BY SEC. R315.1
 FBC-RESIDENTIAL.
  
 11- SPECIFY CEILING CONSTRUCTION ABOVE GARAGE TO SHOW
 COMPLIANCE WITH TABLE R302.6 FBC-RESIDENTIAL.
  
 12- STAIR RAILING DETAIL 3/09 DOESN'T APPLY TO THE
 EXTERIOR OR INTERIOR STAIRS. REVISE AS REQUIRED TO
 MATCH.
 TABLE R301.5 FBC-RESIDENTIAL.
  
 13- SPECIFY ATTIC ACCESS SIZE AND LOCATION. SEC. R807
 FBC-RESIDENTIAL.
  
 14- SIZE OF GUEST SUITE ENTRY DOOR (D10) DOESN'T COMPLY
 WITH THE EGRESS REQUIREMENTS OF SEC. R311.2
 FBC-RESIDENTIAL. REVISE AS REQUIRED.
  
 15- PROVIDE WINDOWS AND DOORS STRUCTURAL BUCK DETAILS.
 SPECIFY BUCK SIZE AND FASTENING. SEC. R609.7.1
 FBC-RESIDENTIAL.
  
 16-BATHROOM DOOR #19 ON FIRST FLOOR GUEST SUITE DOESN'T
 COMPLY WITH THE MIN 29" CLEAR OPENING REQUIRED BY SEC.
 R320 FBC-RESIDENTIAL.
  
 17- STRUCTURAL ENGINEER NEEDS TO HAVE A CURRENT
 ENGINEERING FIRM CERTIFICATE OF AUTHORIZATION. SEC.
 61G15-23.002 AND CHAPTER 471 F.S. COORDINATE WITH DBPR.
  
 18- SHEET A-14: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE CONSTRUCTION OF THE PRIVACY
 WALLS AND GATES. SEC. R301.1 FBC-RESIDENTIAL.
  
 19- CHIMNEY TERMINATION DOESN'T SEEM TO COMPLY WITH
 SEC. R1003.9 FBC-RESIDENTIAL. REVISE AS REQUIRED OR
 SHOW PROOF OF COMPLIANCE.
  
 20- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE FIREPLACE INCLUDING FLUE AND
 CHIMNEY. SEC. R301.1 FBC-RESIDENTIAL. AND SEC. R1001
 FBC-RESIDENTIAL.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE/VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 PLEASE DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
  