2019-03-11 10:39:23***PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PRODUCT APPROVALS FOR LOUVERS, METAL ROOF ARE TO BE
 SUBMITTED PRIOR TO INSTALLATION. IT APPEARS THAT A
 PARTIAL APPROVAL WAS PROVIDED BUT THE FLORIDA STATE
 PRODUCT APPROVAL NUMBER IS NOT ON THE DOCUMENTS
 SUBMITTED.
  
 2. A SEPARATE ROOF PERMIT IS REQUIRED. ROOFING
 CONTRACTOR IS TO INDICATE OPTIONS PROPOSED TO SHOW
 COMPLIANCE WITH DESIGN PRESSURES SPECIFIED ON SHEET S1.
 OR, THIS INFORMATION CAN BE PROVIDED AT THIS TIME.
  
 3. TRUSS ENGINEERING REVIEWED BY ENGINEER OF RECORD IS
 TO BE PROVIDED ON THE JOB PRIOR TO INSPECTION.
  
  