2019-01-31 16:44:40 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18111031 |
| 1/31/19 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) IN RESPONSE TO THE 1ST REVIEW COMMENTS, THE |
| ARCHITECT HAS SUBMITTED AN OLD PLAN FOR THE EXISTING |
| FACILTIY THAT IS DATED AUGUST 2000. THERE ARE NO CITY |
| STAMPS ON THE PLAN, NO ADDRESS SHOWN, AND NO COPY OF |
| THIS PLAN IN OUR CITY RECORDS TO VALIDATE IT. THE |
| CORRECTED NEW PLAN FOR THE FACILITY IS NOW SHOWING |
| THREE NEW FANS INSTEAD OF ONE. PLEASE REVISE THE NEW |
| PLAN TO ADDRESS COMMENTS #2- 5 BELOW. |
| |
| 2) SHEET ME-1: PROVIDE SIZING CALCULATION FOR THE NEW |
| EXHAUST FANS BASED ON TABLE 403.3.1.1 FBC M. |
| |
| 3) ME-1: INDICATE THE SEQUENCE OF OPERATION FOR THE |
| FANS. WILL THE FAN RUN CONTINUOUSLY OR INTERMITTENTLY? |
| |
| 4) ME-1: INDICATE HOW MAKEUP AIR IS TO BE PROVIDED FOR |
| THE EXHAUST. |
| |
| 5) ME-1: SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE |
| NOA FOR THE NEW LOUVERS- RULE 9N-3 FAC. |
| |
| |