2019-01-31 16:44:402ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18111031
 1/31/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IN RESPONSE TO THE 1ST REVIEW COMMENTS, THE
 ARCHITECT HAS SUBMITTED AN OLD PLAN FOR THE EXISTING
 FACILTIY THAT IS DATED AUGUST 2000. THERE ARE NO CITY
 STAMPS ON THE PLAN, NO ADDRESS SHOWN, AND NO COPY OF
 THIS PLAN IN OUR CITY RECORDS TO VALIDATE IT. THE
 CORRECTED NEW PLAN FOR THE FACILITY IS NOW SHOWING
 THREE NEW FANS INSTEAD OF ONE. PLEASE REVISE THE NEW
 PLAN TO ADDRESS COMMENTS #2- 5 BELOW.
  
 2) SHEET ME-1: PROVIDE SIZING CALCULATION FOR THE NEW
 EXHAUST FANS BASED ON TABLE 403.3.1.1 FBC M.
  
 3) ME-1: INDICATE THE SEQUENCE OF OPERATION FOR THE
 FANS. WILL THE FAN RUN CONTINUOUSLY OR INTERMITTENTLY?
  
 4) ME-1: INDICATE HOW MAKEUP AIR IS TO BE PROVIDED FOR
 THE EXHAUST.
  
 5) ME-1: SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE NEW LOUVERS- RULE 9N-3 FAC.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER