2018-12-10 17:00:301ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18111031
 12/10/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET ME-1: PROVIDE A SIZING CALCULATION FOR THE NEW
 EXHAUST FAN BASED ON TABLE 403.3.1.1 FBC M.
  
 2) ME-1: INDICATE THE SEQUENCE OF OPERATION FOR THE
 FAN. WILL THE FAN RUN CONTINUOUSLY OR INTERMITTENTLY?
 THE NOTES ON THE PLAN SHOW "EXISTING OPERATING
 CONTROLS" BUT THIS IS A "NEW" FAN. ARE THERE GAS
 SENSORS LOCATED IN THE GARAGE? PLEASE SEE SECTION 405.1
 AND PROVIDE MORE INFORMATION.
  
 3) ME-1: SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE
 NOA FOR THE NEW LOUVER- RULE 9N-3 FAC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719