2018-11-26 12:00:08 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | | | 1) SHEET E 1 - THE IS A NOTE INDICATING THE USE OF AN | | EMERGENCY LOCKDOWN BUTTON. | | | | THE EMERGENCY LOCKDOWN SHALL NOT RESTRICT EGRESS OF ANY | | REQUIRED EXIT EGRESS DOOR. | | | | PLEASE ENSURE THAT EGRESS IS MAINTAINED PER NFPA 101, | | CHAPTER 7. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|