2018-12-10 08:52:461) INDICATE ON BOTH SETS OF PLANS IF THE TANK WILL BE
 FILLED WITH LP GAS AT THE TIME OF INSTALLATION OR WILL
 REMAIN EMPTY. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHOW THE DISTANCE FROM THE END OF THE TANK TO THE
 EDGE OF THE DRIVEWAY. CONTAINERS LOCATED WITHIN 10 FEET
 OF A DESIGNATED PARKING LOCATION SHALL CCOMPLY WITH
 NFPA 58 SEC.6.6.6.1 (B), (C), (E).
 3) A CORROSION PROTECTION SYSTEM SHALL BE INSTALLED ON
 NEW INSTALLATIONS OF UNDERGROUND STEEL CONTAINERS PER
 NFPA 58 SEC. 6.6.6.1 (I). SUBMIT INFORMATION & DETAILS
 AS TO HOW THE REQUIRED CATHODIC PROTECTION WILL BE
 PROVIDED.THE CORROSION PROTECTION SHALL INCCLUDE THE
 FOLLOWING:
 1) A CONTAINER COATING COMPLYING WITH NFPA 58
 SEC.5.2.1.11.
 2) A CATHODIC PROTECTION SYSTEM THAT CONSISTS OF A
 SACRIFICIAL ANODE(S) OR AN IMPRESSED CURRENT ANODE.
 3) A MEANS TO TEST THE PERFORMANCE OF THE CATHODIC
 PROTECTION SYSTEM IN ACCORDANCE WITH NFPA 58 SEC.
 6.17.3.
 SHOW THE NUMBER/TYPE OF ANODE, WWIRE SIZE ETC.
  