2018-12-11 16:25:53 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| JOSEAN A. DUPREY |
| PLANS EXAMINER |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6716 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1.PLEASE PROVIDE GARAGE DOOR AND EXIST DOOR PRODUCT |
| APPROVAL PER FBCR 301 |
| |
| 2.PROVIDE WATER-RESISTIVE BARRIER FOR EXTERIOR WALL. |
| R703.7.3WATER-RESISTIVE BARRIERS. |
| WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED |
| IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED |
| SHEATHING, SHALL INCLUDE A WATER-RESISTIVE |
| VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST |
| EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE |
| INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH |
| THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE |
| AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION |
| R703.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE |
| BARRIER IS DIRECTED BETWEEN THE LAYERS. |
| EXCEPTION: WHERE THE WATER-RESISTIVE BARRIER THAT IS |
| APPLIED OVER WOOD-BASED SHEATHING HAS A WATER |
| RESISTANCE EQUAL TO OR GREATER THAN THAT OF 60-MINUTE |
| GRADE D PAPER AND IS SEPARATED FROM THE STUCCO BY AN |
| INTERVENING, SUBSTANTIALLY NONWATER-ABSORBING LAYER OR |
| DESIGNED DRAINAGE SPACE. |
| |
| 3.PLEASE PROVIDE SMOKE ALARM DETAILS PER FLORIDA |
| EXISTING BUILDING CODE SECTION 1104. |
| |
| 4.PLEASE PROVIDE EXTERIOR LANDING FOR EXTERIOR DOOR. |
| R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. THERE |
| SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE |
| LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE |
| DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE |
| PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT |
| VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). |
| |
| |