Plan Review Notes
Plan Review Notes For Permit 18110934
Permit Number 18110934
Review Stop B
Sequence Number 1
Notes
Date Text
2018-12-11 16:25:53BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 JOSEAN A. DUPREY
 PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6716
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1.PLEASE PROVIDE GARAGE DOOR AND EXIST DOOR PRODUCT
 APPROVAL PER FBCR 301
  
 2.PROVIDE WATER-RESISTIVE BARRIER FOR EXTERIOR WALL.
 R703.7.3WATER-RESISTIVE BARRIERS.
 WATER-RESISTIVE BARRIERS SHALL BE INSTALLED AS REQUIRED
 IN SECTION R703.2 AND, WHERE APPLIED OVER WOOD-BASED
 SHEATHING, SHALL INCLUDE A WATER-RESISTIVE
 VAPOR-PERMEABLE BARRIER WITH A PERFORMANCE AT LEAST
 EQUIVALENT TO TWO LAYERS OF GRADE D PAPER. THE
 INDIVIDUAL LAYERS SHALL BE INSTALLED INDEPENDENTLY SUCH
 THAT EACH LAYER PROVIDES A SEPARATE CONTINUOUS PLANE
 AND ANY FLASHING (INSTALLED IN ACCORDANCE WITH SECTION
 R703.4) INTENDED TO DRAIN TO THE WATER-RESISTIVE
 BARRIER IS DIRECTED BETWEEN THE LAYERS.
 EXCEPTION: WHERE THE WATER-RESISTIVE BARRIER THAT IS
 APPLIED OVER WOOD-BASED SHEATHING HAS A WATER
 RESISTANCE EQUAL TO OR GREATER THAN THAT OF 60-MINUTE
 GRADE D PAPER AND IS SEPARATED FROM THE STUCCO BY AN
 INTERVENING, SUBSTANTIALLY NONWATER-ABSORBING LAYER OR
 DESIGNED DRAINAGE SPACE.
  
 3.PLEASE PROVIDE SMOKE ALARM DETAILS PER FLORIDA
 EXISTING BUILDING CODE SECTION 1104.
  
 4.PLEASE PROVIDE EXTERIOR LANDING FOR EXTERIOR DOOR.
 R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. THERE
 SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH
 EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE
 LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A
 MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE
 DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE
 PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT
 VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT).
  
  