Plan Review Notes
Plan Review Notes For Permit 18110885
Permit Number 18110885
Review Stop G
Sequence Number 1
Notes
Date Text
2018-12-07 16:38:011) CLARIFY THE REASON FOR THE CFH NUMBERS AT THE GAS
 OUTLETS AND ALSO AT THE PE PIPE.
 2) SHOW THE SIZE OF THE GALVANIZED PIPE AT THE OUTLET
 OF THE GAS METER.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE GAS
 APPLIANCES. THE APPLIANCES SHALL BE LISTED AND LABELED
 PER 2017 FBC-FUEL GAS SEC. 301.3.
 4) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE
 LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION
 AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN
 RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER
 HEATER SHALL COMPLY WITH THE MANUFACTURER'S
 INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND
 DRAWN. WPB AMEND. TO FBC SEC. 107.2.1.
 5) THE DESCRIPTION OF WORK ON THE APPLICATION NOTES
 THAT THE GAS LINE WILL BE RUNNING UNDER THE HOUSE. IS
 THE INTENT TO INSTALL THE PIPING UNDER A SLAB OR IN A
 CRAWL SPACE? PE PIPING IS ONLY PERMITTED TO BE
 INSTALLLED OUTDOORS UNDERGROUND ONLY. INSTALLING IT
 ABOVEGROUND IN A CRAWL SPACE IS A VIOLATION OF THE CODE
 AND NOT PERMITTED. SECONDLY, GAS PIPING UNDER A
 BUILDING IS ONLY PERMITTED WHEN THERE IS NO OTHER WAY
 TO INSTALL IT. THE INSTALLATION SCOPE OF THIS PORTION
 OF THE WORK IS VAGUE AND VIOLATES THE GAS CODE SEC.
 404.14. CLARIFY.
 6) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE
 DRYER AND STOVE AND SUPPLY COMBUSTION AIR CALCULATIONS
 PER 2017 FBC-FUEL GAS SEC.304.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  